Temperature chart of the heating system 105 70. Selecting the temperature regime for heating: description of the main parameters and calculation examples

In the article, we will find out how the average daily temperature is calculated when designing heating systems, how the temperature of the coolant at the outlet of the heating system depends on the temperature outside. elevator node and what can be the temperature of the radiators in winter.

We will touch on the topic self fight cold in the apartment.

Cold in winter is a sore subject for many residents of city apartments.

general information

Here we present the main provisions and excerpts from the current SNiP.

Outside temperature

Design temperature heating period, which is included in the design of heating systems, is nothing less than the average temperature of the coldest five-day periods for the eight coldest winters of the last 50 years.

This approach allows, on the one hand, to be prepared for severe frosts that happen only once every few years, and on the other hand, not to invest excessive funds in the project. On the scale of mass construction, we are talking about very significant amounts.

Target room temperature

It should be noted right away that the temperature in the room is affected not only by the temperature of the coolant in the heating system.

Several factors are at work in parallel:

  • Outdoor air temperature. The lower it is, the greater the heat leakage through walls, windows and roofs.
  • Presence or absence of wind. Strong wind increases the heat loss of buildings by blowing porches, basements and apartments through unsealed doors and windows.
  • The degree of insulation of the facade, windows and doors in the room. It is clear that in the case of a hermetically sealed plastic window With double glazing heat loss will be much lower than with dried out wooden window and glazing in two threads.

It is curious: now there has been a trend towards construction apartment buildings with the highest degree of thermal insulation.
In Crimea, where the author lives, new houses are being built immediately with facade insulation mineral wool or polystyrene and with hermetically closing doors of entrances and apartments.

  • And finally, the actual temperature of the heating radiators in the apartment.

So, what are the current temperature standards in rooms for various purposes?

  • In the apartment: corner rooms- not lower than 20C, other living rooms - not lower than 18C, bathroom - not lower than 25C.
    Nuance: at an estimated air temperature below -31C, more than high values, +22 and +20C (source - Decree of the Government of the Russian Federation of May 23, 2006 "Rules for providing utilities citizens").
  • AT kindergarten: 18-23 degrees depending on the purpose of the room for toilets, bedrooms and playrooms; 12 degrees for walking verandas; 30 degrees for indoor swimming pools.
  • AT educational institutions: from 16C for boarding school bedrooms to +21 in classrooms.
  • In theaters, clubs, other places of entertainment: 16-20 degrees for the auditorium and + 22C for the stage.
  • For libraries (reading rooms and book depositories), the norm is 18 degrees.
  • In grocery stores, the normal winter temperature is 12, and in non-food stores - 15 degrees.
  • The temperature in the gyms is maintained at 15-18 degrees.

  • In hospitals, the maintained temperature depends on the purpose of the room. For example, the recommended temperature after otoplasty or childbirth is +22 degrees, in the wards for premature babies it is maintained at +25, and for patients with thyrotoxicosis (excessive secretion of thyroid hormones) - 15C. In surgical wards, the norm is + 26C.

temperature graph

What should be the temperature of the water in the heating pipes?

It is determined by four factors:

  1. Air temperature outside.
  2. Type of heating system. For single pipe system Maximum temperature water in the heating system in accordance with current standards - 105 degrees, for a two-pipe - 95. The maximum temperature difference between the supply and return is 105/70 and 95/70C, respectively.
  3. The direction of the water supply to the radiators. For houses of the upper bottling (with supply in the attic) and lower (with pairwise looping of the risers and the location of both threads in the basement), the temperatures differ by 2 - 3 degrees.
  4. Type of heating appliances in the house. Radiators and have different heat transfer; accordingly, to ensure the same temperature in the room, the temperature regime of heating must be different.

So, what should be the temperature of heating - water in the supply and return pipes - at different outdoor temperatures?

We present only a small part temperature table for the estimated ambient temperature of -40 degrees.

  • At zero degrees, the temperature of the supply pipeline for radiators with different wiring is 40-45C, the return one is 35-38. For convectors 41-49 supply and 36-40 return.
  • At -20 for radiators, the supply and return must have a temperature of 67-77 / 53-55C. For convectors 68-79/55-57.
  • At -40C outside, for all heaters, the temperature reaches the maximum allowable temperature: 95/105, depending on the type of heating system, at the supply and 70C at the return pipe.

Useful extras

To understand the principle of operation of the heating system apartment building, separation of areas of responsibility, you need to know a few more facts.

The temperature of the heating main at the outlet of the CHP and the temperature of the heating system in your home are completely different things. At the same -40, a CHP or boiler house will produce about 140 degrees at the supply. Water does not evaporate only due to pressure.

In the elevator unit of your house, part of the water from the return pipeline, returning from the heating system, is mixed into the supply. Nozzle squirts hot water with high pressure into the so-called elevator and involves the masses of cooled water in re-circulation.

Why is this needed?

To provide:

  1. Reasonable mixture temperature. Recall: the heating temperature in the apartment cannot exceed 95-105 degrees.

Attention: for kindergartens, a different temperature norm applies: no higher than 37C. low temperature heating appliances have to be compensated large area heat exchange.
That is why in kindergartens the walls are decorated with radiators of such great length.

  1. Large volume of water involved in circulation. If you remove the nozzle and let the water flow directly from the supply, the return temperature will differ little from the supply, which will dramatically increase heat loss along the route and disrupt the operation of the CHP.

If you turn off the suction of water from the return, the circulation will become so slow that the return pipeline can simply freeze in winter.

The areas of responsibility are divided as follows:

  • The temperature of the water injected into the heating mains is the responsibility of the heat producer - the local CHPP or boiler house;
  • For the transportation of the coolant with minimal losses - the organization serving the heating networks (KTS - communal heating networks).

  • For maintenance and adjustment of the elevator unit - ZhEU. In this case, however, the diameter of the elevator nozzle - something on which the temperature of the radiators depends - is coordinated with the CTC.

If your house is cold and all the heating devices are those installed by the builders, you will settle this issue with the residents. They are required to provide the temperatures recommended by sanitary standards.

If you undertake any modification of the heating system, for example, you thereby assume full responsibility for the temperature in your home.

How to deal with the cold

Let us, however, be realistic: most often we have to solve the problem of cold in the apartment ourselves, with our own hands. Not always housing organization can provide you with warmth in a reasonable time, and sanitary norms not everyone will be satisfied: I want the house to be warm.

What will the instructions for dealing with cold in an apartment building look like?

Jumpers in front of radiators

In front of the heaters in most apartments there are jumpers that are designed to ensure the circulation of water in the riser in any condition of the radiator. For a long time they were supplied three-way valves, then began to be put without any stop valves.

The jumper in any case reduces the circulation of the coolant through heater. In the case when its diameter is equal to the diameter of the eyeliner, the effect is especially pronounced.

The simplest way to make your apartment warmer is to insert chokes into the jumper itself and the connection between it and the radiator.

With their help, it is possible to conveniently adjust the temperature of the heating batteries: when the jumper is closed and the throttle to the radiator is fully open, the temperature is maximum, just open the jumper and cover the second throttle - and the heat in the room comes to naught.

The great advantage of such a refinement is the minimum cost of the solution. The price of the throttle does not exceed 250 rubles; spurs, couplings and locknuts cost a penny at all.

Important: if the throttle leading to the radiator is at least slightly covered, the throttle on the jumper opens completely. Otherwise, adjusting the heating temperature will result in batteries and convectors that have cooled down at the neighbors.

Warm floor

Even if the radiator in the room hangs on a return pipe with a temperature of about 40 degrees, with the help of modification heating system can make the room warm.

Exit - low temperature systems heating.

It is difficult to apply in a city apartment due to the limited height of the room: raising the floor level by 15-20 centimeters will mean completely low ceilings.

Much more real option- warm floor. Due to where larger area heat transfer and more rational distribution of heat in the volume of the room low temperature heating warms up the room better than a hot radiator.

What does the implementation look like?

  1. Chokes are placed on the jumper and the eyeliner in the same way as in the previous case.
  2. The outlet from the riser to the heater is connected to metal-plastic pipe, which fits into the screed on the floor.

So that communications do not spoil appearance rooms, they are put away in a box. As an option, the tie-in to the riser is moved closer to the floor level.

Conclusion

You can find more information about the operation of centralized heating systems in the video at the end of the article. Warm winters!

The normative water temperature in the heating system depends on the air temperature. Therefore, the temperature schedule for the supply of coolant to the heating system is calculated in accordance with weather conditions. In the article we will talk about the requirements of SNiP for the operation of the heating system for objects for various purposes.

from the article you will learn:

In order to economically and rationally use energy resources in the heating system, the heat supply is tied to the air temperature. The dependence of the water temperature in the pipes and the air outside the window is displayed as a graph. The main task of such calculations is to maintain comfortable conditions for residents in apartments. For this, the air temperature should be about + 20 ... + 22ºС.

The temperature of the coolant in the heating system

The stronger the frost, the faster the living quarters heated from the inside lose heat. To compensate for the increased heat loss, the temperature of the water in the heating system increases.

The calculations use normative indicator temperature. It is calculated according to special technique and included in the governing documents. This figure is based on the average temperature of the 5 coldest days of the year. The calculation is based on the 8 coldest winters over a 50-year period.

Why is the drawing up of a temperature schedule for the supply of coolant to the heating system happening in this way? The main thing here is to be ready for the most severe frosts that happen every few years. Climatic conditions in a particular region can change over several decades. This will be taken into account when recalculating the schedule.

The value of the average daily temperature is also important for calculating the margin of safety of heating systems. By understanding the ultimate load, you can accurately calculate the characteristics necessary pipelines, stop valves and other elements. This saves on the creation of communications. Given the scale of construction for urban heating systems, the amount of savings will be quite large.

The temperature in the apartment directly depends on how much the coolant is heated in the pipes. In addition, other factors also matter here:

  • air temperature outside the window;
  • wind speed. With strong wind loads, heat losses through doorways and windows increase;
  • the quality of sealing joints on the walls, as well as the general condition of the decoration and insulation of the facade.

Building codes change as technology advances. This is reflected, among other things, in the indicators in the coolant temperature graph, depending on outdoor temperature. If the premises retain heat better, then energy resources can be spent less.

Developers in modern conditions more carefully approach the thermal insulation of facades, foundations, basements and roofs. This increases the value of objects. However, along with the growth of construction costs are reduced. The overpayment at the construction stage pays off over time and gives good savings.

The heating of the premises is directly affected not even by how hot the water in the pipes is. The main thing here is the temperature of the heating radiators. It is usually in the range of + 70 ... + 90ºС.

Several factors affect battery heating.

1. Air temperature.

2. Features of the heating system. The indicator indicated in the temperature chart for supplying coolant to the heating system depends on its type. In single-pipe systems, water heating up to + 105ºС is considered normal. Two-pipe heating due to better circulation gives a higher heat transfer. This allows you to reduce the temperature to + 95ºС. Moreover, if at the inlet the water needs to be heated, respectively, to + 105ºС and + 95ºС, then at the outlet its temperature in both cases should be at the level of + 70ºС.

So that the coolant does not boil when heated above + 100ºС, it is supplied to the pipelines under pressure. Theoretically, it can be quite high. This should provide a large supply of heat. However, in practice, not all networks allow water to be supplied under high pressure due to their deterioration. As a result, the temperature drops, and during severe frosts there may be a lack of heat in apartments and other heated premises.

3. The direction of the water supply to the radiators. At top wiring the difference is 2ºС, at the bottom - 3ºС.

4. Type of heaters used. Radiators and convectors differ in the amount of heat they give off, which means that they must work in different temperature conditions. Better performance heat transfer from radiators.

At the same time, the amount of heat released is affected, among other things, by the temperature of the outdoor air. It is she who is the determining factor in the temperature schedule for supplying coolant to the heating system.

When the water temperature is +95ºС, we are talking about the coolant at the entrance to the dwelling. Given the heat loss during transportation, the boiler room should heat it much more.

In order to supply water of the required temperature to the heating pipes in the apartments, a special equipment. It mixes hot water from the boiler room with the one that comes from the return.

Temperature chart for supplying coolant to the heating system

The graph shows what the water temperature should be at the entrance to the dwelling and at the exit from it, depending on the street temperature.

The presented table will help to easily determine the degree of heating of the coolant in the system central heating.

Temperature indicators of air outside, °С

Temperature indicators of water at the inlet, °С

Temperature indicators of water in the heating system, °С

Temperature indicators of water after the heating system, °С

Representatives of utilities and resource-supplying organizations measure the water temperature using a thermometer. The 5th and 6th columns indicate the figures for the pipeline through which hot coolant. 7 column - for the return.

The first three columns indicate fever- these are indicators for heat generating organizations. These figures are given without taking into account heat losses that occur during the transportation of the coolant.

The temperature schedule for supplying coolant to the heating system is needed not only by resource-supplying organizations. If the actual temperature differs from the standard one, consumers have reasons to recalculate the cost of the service. In their complaints, they indicate how warm the air in the apartments is. This is the easiest parameter to measure. Inspecting authorities can already track the temperature of the coolant, and if it does not comply with the schedule, force the resource supplying organization to perform its duties.

A reason for complaints appears if the air in the apartment cools below the following values:

  • in the corner rooms in the daytime - below + 20ºС;
  • in the central rooms in the daytime - below + 18ºС;
  • in corner rooms at night - below +17ºС;
  • in the central rooms at night - below +15ºС.

SNiP

Requirements for the operation of heating systems are fixed in SNiP 41-01-2003. Much attention in this document is given to security issues. In the case of heating, the heated coolant carries a potential hazard, which is why its temperature for residential and public buildings limited. It, as a rule, does not exceed + 95ºС.

If the water in the internal pipelines of the heating system is heated above + 100ºС, then the following safety measures are provided for at such facilities:

  • heating pipes are laid in special mines. In the event of a breakthrough, the coolant will remain in these reinforced channels and will not be a source of danger to people;
  • pipelines in high-rise buildings have special structural elements or devices that do not allow water to boil.

If the building has heating made of polymer pipes, then the temperature of the coolant should not exceed + 90ºС.

We have already mentioned above that in addition to the temperature schedule for supplying coolant to the heating system, responsible organizations need to monitor how hot the accessible elements of heating devices are. These rules are also given in SNiP. Permissible temperatures vary depending on the purpose of the room.

First of all, everything here is determined by the same security rules. For example, in children's and medical institutions allowable temperatures are minimal. AT in public places and there are usually no special restrictions for them at various production facilities.

Surface of heating radiators general rules should not be heated above +90ºС. If this figure is exceeded, Negative consequences. They consist, first of all, in the burning of paint on batteries, as well as in the combustion of dust in the air. This fills the indoor atmosphere with substances harmful to health. In addition, damage to the appearance of heating devices is possible.

Another issue is safety in rooms with hot radiators. According to the general rules, it is supposed to protect heating devices, the surface temperature of which is above + 75ºС. Usually, lattice fences are used for this. They do not interfere with air circulation. At the same time, SNiP provides for mandatory protection of radiators in children's institutions.

In accordance with SNiP, the maximum temperature of the coolant varies depending on the purpose of the room. It is determined both by the characteristics of the heating of different buildings, and by security considerations. For example, in hospitals allowable temperature water in the pipes is the lowest. It is + 85ºС.

The maximum heated coolant (up to +150ºС) can be supplied to the following facilities:

  • lobbies;
  • heated pedestrian crossings;
  • landings;
  • technical premises;
  • industrial buildings, in which there are no aerosols and dust prone to ignition.

The temperature schedule for supplying coolant to the heating system according to SNiP is used only in the cold season. In the warm season, the document in question normalizes the microclimate parameters only in terms of ventilation and air conditioning.

The basis of an economical approach to energy consumption in a heating system of any type is the temperature graph. Its parameters indicate optimal value heating water, thereby optimizing costs. In order to apply these data in practice, it is necessary to learn more about the principles of its construction.

Terminology

Temperature graph - the optimal value of heating the coolant to create comfortable temperature in room. It consists of several parameters, each of which directly affects the quality of the entire heating system.

  1. The temperature in the inlet and outlet pipes of the heating boiler.
  2. The difference between these indicators of heating the coolant.
  3. Temperature indoors and outdoors.

The latter characteristics are decisive for the regulation of the first two. Theoretically, the need to increase the heating of water in the pipes comes with a decrease in the temperature outside. But how much should be increased so that the heating of the air in the room is optimal? To do this, draw up a graph of the dependence of the parameters of the heating system.

When calculating it, the parameters of the heating system and the residential building are taken into account. For district heating the following temperature parameters systems:

  • 150°C/70°C. Before reaching the users, the coolant is diluted with water from the return pipe to normalize the incoming temperature.
  • 90°C/70°C. In this case, there is no need to install equipment for mixing streams.

According to the current parameters of the system, utilities must monitor compliance with the heating medium heating value in the return pipe. If this parameter is less than normal, it means that the room is not warming up properly. The excess indicates the opposite - the temperature in the apartments is too high.

Temperature chart for a private house

The practice of drawing up such a schedule for autonomous heating not very developed. This is explained by his fundamental difference from centralized. It is possible to control the water temperature in the pipes in manual and automatic mode. If during design and practical implementation the installation of sensors for automatic regulation operation of the boiler and thermostats in each room, then there will be no urgent need to calculate the temperature schedule.

But to calculate future expenses depending on weather conditions he will be irreplaceable. In order to compose it according to current rules, the following conditions must be taken into account:

Only after these conditions are met, you can proceed to the calculation part. At this stage, difficulties may arise. The correct calculation of an individual temperature graph is a complex mathematical scheme that takes into account all possible indicators.

However, to facilitate the task, there are ready-made tables with indicators. Below are examples of the most common modes of operation of heating equipment. The following input data were taken as initial conditions:

  • The minimum air temperature outside is 30°С
  • The optimum room temperature is +22°C.

Based on these data, charts were drawn up for the following types operation of heating systems.




It is worth remembering that these data do not take into account the design features of the heating system. They only show the recommended values ​​\u200b\u200bof the temperature and power of heating equipment, depending on weather conditions.

Looking through the statistics of visiting our blog, I noticed that search phrases such as, for example, “what should be the temperature of the coolant at minus 5 outside?” appear very often. Decided to post the old chart quality regulation heat release by average daily temperature outside air. I want to warn those who, on the basis of these figures, will try to sort out relations with the housing department or heating networks: the heating schedules for each individual settlement are different (I wrote about this in the article regulating the temperature of the coolant). Thermal networks in Ufa (Bashkiria) operate according to this schedule.

I also want to draw attention to the fact that regulation takes place according to the average daily outdoor temperature, so if, for example, it is minus 15 degrees outside at night and minus 5 during the day, then the coolant temperature will be maintained in accordance with the schedule at minus 10 °C.

As a rule, the following temperature graphs are used: 150/70, 130/70, 115/70, 105/70, 95/70. The schedule is selected depending on the specific local conditions. House heating systems operate according to schedules 105/70 and 95/70. According to schedules 150, 130 and 115/70, main heat networks operate.

Let's look at an example of how to use the chart. Suppose the temperature outside is minus 10 degrees. Heating network operate according to a temperature schedule of 130/70, which means that at -10 ° C the temperature of the coolant in the supply pipeline of the heating network should be 85.6 degrees, in the supply pipeline of the heating system - 70.8 ° C with a schedule of 105/70 or 65.3 ° C with a schedule of 95 /70. The water temperature after the heating system should be 51.7 °C.

As a rule, the temperature values ​​in the supply pipeline of heat networks are rounded off when setting the heat source. For example, according to the schedule, it should be 85.6 ° C, and 87 degrees are set at the CHP or boiler house.

Outside temperature

Temperature network water in the supply pipeline Т1, оС Water temperature in the supply pipeline of the heating system Т3, оС Water temperature after the heating system Т2, оС

150 130 115 105 95 8 7 6 5 4 3 2 1 0 -1 -2 -3 -4 -5 -6 -7 -8 -9 -10 -11 -12 -13 -14 -15 -16 -17 -18 -19 -20 -21 -22 -23 -24 -25 -26 -27 -28 -29 -30 -31 -32 -33 -34 -35
53,2 50,2 46,4 43,4 41,2 35,8
55,7 52,3 48,2 45,0 42,7 36,8
58,1 54,4 50,0 46,6 44,1 37,7
60,5 56,5 51,8 48,2 45,5 38,7
62,9 58,5 53,5 49,8 46,9 39,6
65,3 60,5 55,3 51,4 48,3 40,6
67,7 62,6 57,0 52,9 49,7 41,5
70,0 64,5 58,8 54,5 51,0 42,4
72,4 66,5 60,5 56,0 52,4 43,3
74,7 68,5 62,2 57,5 53,7 44,2
77,0 70,4 63,8 59,0 55,0 45,0
79,3 72,4 65,5 60,5 56,3 45,9
81,6 74,3 67,2 62,0 57,6 46,7
83,9 76,2 68,8 63,5 58,9 47,6
86,2 78,1 70,4 65,0 60,2 48,4
88,5 80,0 72,1 66,4 61,5 49,2
90,8 81,9 73,7 67,9 62,8 50,1
93,0 83,8 75,3 69,3 64,0 50,9
95,3 85,6 76,9 70,8 65,3 51,7
97,6 87,5 78,5 72,2 66,6 52,5
99,8 89,3 80,1 73,6 67,8 53,3
102,0 91,2 81,7 75,0 69,0 54,0
104,3 93,0 83,3 76,4 70,3 54,8
106,5 94,8 84,8 77,9 71,5 55,6
108,7 96,6 86,4 79,3 72,7 56,3
110,9 98,4 87,9 80,7 73,9 57,1
113,1 100,2 89,5 82,0 75,1 57,9
115,3 102,0 91,0 83,4 76,3 58,6
117,5 103,8 92,6 84,8 77,5 59,4
119,7 105,6 94,1 86,2 78,7 60,1
121,9 107,4 95,6 87,6 79,9 60,8
124,1 109,2 97,1 88,9 81,1 61,6
126,3 110,9 98,6 90,3 82,3 62,3
128,5 112,7 100,2 91,6 83,5 63,0
130,6 114,4 101,7 93,0 84,6 63,7
132,8 116,2 103,2 94,3 85,8 64,4
135,0 117,9 104,7 95,7 87,0 65,1
137,1 119,7 106,1 97,0 88,1 65,8
139,3 121,4 107,6 98,4 89,3 66,5
141,4 123,1 109,1 99,7 90,4 67,2
143,6 124,9 110,6 101,0 94,6 67,9
145,7 126,6 112,1 102,4 92,7 68,6
147,9 128,3 113,5 103,7 93,9 69,3
150,0 130,0 115,0 105,0 95,0 70,0

Please do not focus on the diagram at the beginning of the post - it does not correspond to the data from the table.

Calculation of the temperature graph

The method for calculating the temperature graph is described in the handbook "Setting up and operation of water heating networks" (Chapter 4, p. 4.4, p. 153,).

This is quite laborious and long process, since several values ​​must be read for each outdoor temperature: T1, T3, T2, etc.

To our joy, we have a computer and a MS Excel spreadsheet. A colleague at work shared with me a ready-made table for calculating the temperature graph. She was once made by his wife, who worked as an engineer for a group of regimes in thermal networks.


Table for calculating the temperature graph in MS Excel

In order for Excel to calculate and build a graph, it is enough to enter several initial values:

  • design temperature in the supply pipeline of the heating network T1
  • design temperature in the return pipe of the heating network T2
  • design temperature in the supply pipe of the heating system T3
  • Outdoor air temperature Tn.v.
  • Indoor temperature Tv.p.
  • coefficient "n" (it is usually not changed and is equal to 0.25)
  • Minimum and maximum cut of the temperature graph Cut min, Cut max.

Entering initial data into the table for calculating the temperature graph

All. nothing more is required of you. The results of the calculations will be in the first table of the sheet. It is highlighted in bold.

The charts will also be rebuilt for the new values.


Graphical representation of the temperature graph

The table also considers the temperature of direct network water, taking into account wind speed.

Download temperature chart calculation

energoworld.com

Appendix e Temperature chart (95 – 70) °С

Design temperature

outdoor

Water temperature in

server

pipeline

Water temperature in

return pipeline

Estimated outdoor temperature

Supply water temperature

Water temperature in

return pipeline

Appendix e

CLOSED HEATING SYSTEM

TV1: G1 = 1V1; G2=G1; Q = G1(h2 –h3)

OPEN HEATING SYSTEM

WITH WATER TANK INTO A DEAD-END DHW SYSTEM

TV1: G1 = 1V1; G2 = 1V2; G3 = G1 - G2;

Q1 \u003d G1 (h2 - h3) + G3 (h3 - hх)

Bibliography

1. Gershunsky B.S. Fundamentals of electronics. Kyiv, Vishcha school, 1977.

2. Meyerson A.M. Radio-measuring equipment. - Leningrad.: Energy, 1978. - 408s.

3. Murin G.A. Thermotechnical measurements. -M.: Energy, 1979. -424 p.

4. Spector S.A. Electrical measurements physical quantities. Tutorial. - Leningrad.: Energoatomizdat, 1987. –320s.

5. Tartakovskii D.F., Yastrebov A.S. Metrology, standardization and technical means measurements. - M .: Higher school, 2001.

6. Heat meters TSK7. Manual. - St. Petersburg.: CJSC TEPLOKOM, 2002.

7. Calculator of the amount of heat VKT-7. Manual. - St. Petersburg.: CJSC TEPLOKOM, 2002.

Zuev Alexander Vladimirovich

Neighboring files in the Process Measurements and Instruments folder

studfiles.net

Heating temperature chart

The task of organizations servicing houses and buildings is to maintain standard temperature. The temperature curve of heating directly depends on the temperature outside.

There are three heating systems

Graph of outside and inside temperature
  1. District heating a large boiler house (CHP), standing at a considerable distance from the city. In this case, heat supply organization, Considering heat loss in networks, selects a system with a temperature graph: 150/70, 130/70 or 105/70. The first digit is the temperature of the water in the supply pipe, the second digit is the temperature of the water in the return pipe.
  2. Small boiler houses, which are located near residential buildings. In this case, the temperature curve 105/70, 95/70 is selected.
  3. Individual boiler installed on a private house. The most acceptable schedule is 95/70. Although it is possible to reduce the supply temperature even more, since there will be practically no heat loss. Modern boilers operate in automatic mode and maintain a constant temperature in the supply heat pipe. The 95/70 temperature chart speaks for itself. The temperature at the entrance to the house should be 95 ° C, and at the exit - 70 ° C.

AT Soviet times when everything was state-owned, all the parameters of the temperature charts were maintained. If according to the schedule there should be a supply temperature of 100 degrees, then this will be so. Such a temperature cannot be supplied to residents, so elevator units were designed. Water from the return pipeline, cooled down, was mixed into the supply system, thereby lowering the supply temperature to the standard one. In our time of universal economy, the need for elevator nodes is no longer necessary. All heat supply organizations switched to the temperature chart of the heating system 95/70. According to this graph, the coolant temperature will be 95 °C when the outside temperature is -35 °C. As a rule, the temperature at the entrance to the house no longer requires dilution. Therefore, all elevator units must be eliminated or reconstructed. Instead of conical sections that reduce both the speed and volume of the flow, put straight pipes. Seal the supply pipe from the return pipeline with a steel plug. This is one of the heat saving measures. It is also necessary to insulate the facades of houses, windows. Change old pipes and batteries to new ones - modern ones. These measures will increase the air temperature in dwellings, which means you can save on heating temperature. Lowering the temperature on the street is immediately reflected in the residents in the receipts.


heating temperature chart

Most Soviet cities were built with an "open" heating system. This is when water from the boiler room comes directly to consumers in homes and is used for personal needs of citizens and heating. During the reconstruction of systems and the construction of new heating systems, a "closed" system is used. The water from the boiler house reaches the heating point in the microdistrict, where it heats the water to 95 °C, which goes to the houses. It turns out two closed rings. This system allows heat supply organizations to significantly save resources for heating water. Indeed, the volume of heated water leaving the boiler room will be almost the same at the entrance to the boiler room. No need to get into the system cold water.

Temperature charts are:

  • optimal. The heat resource of the boiler room is used exclusively for heating houses. Temperature control takes place in the boiler room. The supply temperature is 95 °C.
  • elevated. The heat resource of the boiler house is used for heating houses and hot water supply. A two-pipe system enters the house. One pipe is heating, the other pipe is hot water supply. Supply temperature 80 - 95 °C.
  • adjusted. The heat resource of the boiler house is used for heating houses and hot water supply. One-pipe system approaches the house. From one pipe in the house, a heat resource is taken for heating and hot water for residents. Supply temperature - 95 - 105 °C.

How to carry out the temperature heating schedule. It is possible in three ways:

  1. quality (regulation of the temperature of the coolant).
  2. quantitative (regulation of the coolant volume by turning on additional pumps on the return pipeline, or installing elevators and washers).
  3. qualitative-quantitative (to regulate both the temperature and the volume of the coolant).

The quantitative method prevails, which is not always able to withstand the heating temperature graph.

Fight against heat supply organizations. This struggle is waged by management companies. By law Management Company is obliged to conclude an agreement with the heat supply organization. Will it be a contract for the supply of heat resources or just an agreement on interaction, the management company decides. An annex to this agreement will be a temperature schedule for heating. The heat supply organization is obliged to approve the temperature schemes in the city administration. The heat supply organization supplies the heat resource to the wall of the house, that is, to the metering stations. By the way, the legislation establishes that thermal workers are obliged to install metering stations in houses at their own expense with an installment payment of the cost for residents. So, having metering devices at the entrance and exit from the house, you can control the heating temperature daily. We take the temperature table, look at the air temperature on the weather site and find in the table the indicators that should be. If there are deviations, you need to complain. Even if the deviations are higher, residents will pay more. At the same time, the windows will be opened and the rooms will be ventilated. It is necessary to complain about insufficient temperature to the heat supply organization. If there is no response, we write to the city administration and Rospotrebnadzor.

Until recently, there was a multiplying coefficient on the cost of heat for residents of houses that were not equipped with common house meters. Due to the sluggishness of managing organizations and thermal workers, ordinary residents suffered.

Important indicator in the heating temperature chart is the return temperature of the network. In all graphs, this is an indicator of 70 ° C. In severe frosts, when heat losses increase, heat supply organizations are forced to turn on additional pumps on the return pipeline. This measure increases the speed of water movement through the pipes, and, therefore, the heat transfer increases, and the temperature in the network is maintained.

Again, during the period of general savings, it is very problematic to force thermal workers to turn on additional pumps, which means increasing electricity costs.

The heating temperature graph is calculated based on the following indicators:

  • ambient air temperature;
  • supply pipeline temperature;
  • return pipeline temperature;
  • the amount of heat energy consumed at home;
  • required amount of thermal energy.

For different rooms temperature curve is different. For children's institutions (schools, gardens, palaces of art, hospitals), the temperature in the room should be between +18 and +23 degrees according to sanitary and epidemiological standards.

  • For sports facilities - 18 °C.
  • For residential premises - in apartments not lower than +18 °C, in corner rooms + 20 °C.
  • For non-residential premises– 16-18 °C. Based on these parameters, heating schedules are built.

It is easier to calculate the temperature schedule for a private house, since the equipment is mounted right in the house. A zealous owner will provide heating to the garage, bathhouse, and outbuildings. The load on the boiler will increase. Counting heat load depending on the maximum low air temperatures of past periods. We select equipment by power in kW. The most cost-effective and environmentally friendly boiler is natural gas. If gas is brought to you, this is already half the battle done. You can also use bottled gas. At home, you do not have to adhere to standard temperature schedules of 105/70 or 95/70, and it does not matter that the temperature in the return pipeline is not 70 ° C. Adjust the network temperature to your liking.

By the way, many city dwellers would like to put individual counters on the heat and control the temperature chart yourself. Contact the heat supply companies. And there they hear such answers. Most of the houses in the country are built on a vertical heating system. Water is supplied from the bottom - up, less often: from top to bottom. With such a system, the installation of heat meters is prohibited by law. Even if a specialized organization installs these meters for you, the heat supply organization simply will not accept these meters for operation. That is, savings will not work. Installation of meters is possible only with horizontal heating distribution.

In other words, when a heating pipe comes into your home not from above, not from below, but from the entrance corridor - horizontally. At the place of entry and exit of heating pipes, individual heat meters can be installed. Installation of such counters pays off in two years. All houses are now being built with just such a wiring system. Heating appliances are equipped with control knobs (taps). If the temperature in the apartment is high in your opinion, then you can save money and reduce the heating supply. Only ourselves we will save from freezing.

myaquahouse.com

Temperature chart of the heating system: variations, application, shortcomings

The temperature chart of the heating system 95 -70 degrees Celsius is the most demanded temperature chart. By and large, we can say with confidence that all central heating systems operate in this mode. The only exceptions are buildings with autonomous heating.

But also in autonomous systems there may be exceptions when using condensing boilers.

When using boilers operating on the condensation principle, the temperature curves of heating tend to be lower.


Temperature in pipelines depending on the outside air temperature

Application of condensing boilers

For example, when maximum load for a condensing boiler, there will be a mode of 35-15 degrees. This is due to the fact that the boiler extracts heat from the exhaust gases. In a word, with other parameters, for example, the same 90-70, it will not be able to work effectively.

Distinctive properties of condensing boilers are:

  • high efficiency;
  • profitability;
  • optimal efficiency at minimum load;
  • quality of materials;
  • high price.

You have heard many times that the efficiency of a condensing boiler is about 108%. Indeed, the manual says the same thing.


Condensing boiler Valliant

But how can this be, because we are still with school desk taught that more than 100% does not happen.

  1. The thing is that when calculating the efficiency of conventional boilers, 100% is taken as the maximum. But ordinary gas boilers for heating a private house, flue gases are simply thrown into the atmosphere, and condensing ones utilize part of the outgoing heat. The latter will go to heating in the future.
  2. The heat that will be utilized and used in the second round is added to the efficiency of the boiler. Typically, a condensing boiler utilizes up to 15% of flue gases, this figure is adjusted to the efficiency of the boiler (approximately 93%). The result is a number of 108%.
  3. Undoubtedly, heat recovery is a necessary thing, but the boiler itself costs a lot of money for such work. High price boiler due to stainless steel heat exchange equipment, which utilizes heat in the last path of the chimney.
  4. If instead of such stainless equipment we put ordinary iron equipment, then it will become unusable after a very short span time. Since the moisture contained in the flue gases has aggressive properties.
  5. main feature condensing boilers lies in the fact that they achieve maximum efficiency with minimum loads. conventional boilers(gas heaters), on the contrary, reach the peak of economy at maximum load.
  6. The beauty of it useful property is that during the entire heating period, the load on heating is not always maximum. On the strength of 5-6 days, an ordinary boiler works at maximum. Therefore, a conventional boiler cannot match the performance of a condensing boiler, which has maximum performance at minimum loads.

You can see a photo of such a boiler a little higher, and a video with its operation can be easily found on the Internet.


Principle of operation

conventional heating system

It is safe to say that the heating temperature schedule of 95 - 70 is the most in demand.

This is explained by the fact that all houses that receive heat from central heat sources are designed to work in this mode. And we have more than 90% of such houses.

District boiler house

The principle of operation of such heat production occurs in several stages:

  • heat source (district boiler house), produces water heating;
  • heated water, through the main and distribution networks moves towards consumers;
  • in the house of consumers, most often in the basement, through the elevator unit, hot water is mixed with water from the heating system, the so-called return flow, the temperature of which is not more than 70 degrees, and then heated to a temperature of 95 degrees;
  • further heated water (the one that is 95 degrees) passes through the heaters of the heating system, heats the premises and again returns to the elevator.

Advice. If you have a cooperative house or a society of co-owners of houses, then you can set up the elevator with your own hands, but this requires you to strictly follow the instructions and correctly calculate the throttle washer.

Poor heating system

Very often we hear that people's heating does not work well and their rooms are cold.

There can be many reasons for this, the most common are:

  • schedule temperature system heating is not observed, the elevator may be incorrectly calculated;
  • house system heating is heavily polluted, which greatly impairs the passage of water through the risers;
  • fuzzy heating radiators;
  • unauthorized change of the heating system;
  • poor thermal insulation of walls and windows.

A common mistake is an incorrectly dimensioned elevator nozzle. As a result, the function of mixing water and the operation of the entire elevator as a whole is disrupted.

This could happen for several reasons:

  • negligence and lack of training of operating personnel;
  • incorrectly performed calculations in the technical department.

During the many years of operation of heating systems, people rarely think about the need to clean their heating systems. By and large, this applies to buildings that were built during the Soviet Union.

All heating systems must be hydropneumatic flushing in front of everyone heating season. But this is observed only on paper, since ZhEKs and other organizations carry out these works only on paper.

As a result, the walls of the risers become clogged, and the latter become smaller in diameter, which violates the hydraulics of the entire heating system as a whole. The amount of transmitted heat decreases, that is, someone simply does not have enough of it.

You can do hydropneumatic purge with your own hands, it is enough to have a compressor and a desire.

The same applies to cleaning radiators. Over many years of operation, radiators inside accumulate a lot of dirt, silt and other defects. Periodically, at least once every three years, they need to be disconnected and washed.

Dirty radiators greatly impair the heat output in your room.

The most common moment is an unauthorized change and redevelopment of heating systems. When replacing old metal pipes with metal-plastic ones, diameters are not observed. And sometimes various bends are added, which increases local resistance and worsens the quality of heating.


Metal-plastic pipe

Very often, with such unauthorized reconstruction and replacement of heating batteries with gas welding, the number of radiator sections also changes. And really, why not give yourself more sections? But in the end, your housemate, who lives after you, will receive less of the heat he needs for heating. And the last neighbor, who will receive less heat the most, will suffer the most.

An important role is played thermal resistance building envelopes, windows and doors. As statistics show, up to 60% of heat can escape through them.

Elevator node

As we said above, all water jet elevators are designed to mix water from the supply line of heating networks into the return line of the heating system. Thanks to this process, system circulation and pressure are created.

As for the material used for their manufacture, both cast iron and steel are used.

Consider the principle of operation of the elevator in the photo below.


The principle of operation of the elevator

Through pipe 1, water from heating networks passes through the ejector nozzle and with high speed enters the mixing chamber 3. There, water is mixed with it from the return of the heating system of the building, the latter is supplied through pipe 5.

The resulting water is sent to the heating system supply through diffuser 4.

In order for the elevator to function correctly, it is necessary that its neck be correctly selected. To do this, calculations are made using the formula below:

Where ΔРnas - design circulation pressure in the heating system, Pa;

Gcm - water consumption in the heating system kg / h.

Note! True, for such a calculation, you need a building heating scheme.

The appearance of the elevator unit

Have a warm winter!

Page 2

In the article, we will find out how the average daily temperature is calculated when designing heating systems, how the temperature of the coolant at the outlet of the elevator unit depends on the temperature outside, and what the temperature of the heating batteries can be in winter.

We will also touch on the topic of self-combating the cold in the apartment.


Cold in winter is a sore subject for many residents of city apartments.

general information

Here we present the main provisions and excerpts from the current SNiP.

Outside temperature

The design temperature of the heating period, which is included in the project of heating systems, is nothing less than the average temperature of the coldest five-day periods for the eight coldest winters of the last 50 years.

This approach allows, on the one hand, to be prepared for severe frosts that occur only once every few years, and on the other hand, not to invest excessive funds in the project. On the scale of mass construction, we are talking about very significant amounts.

Target room temperature

It should be noted right away that the temperature in the room is affected not only by the temperature of the coolant in the heating system.

Several factors are at work in parallel:

  • Air temperature outside. The lower it is, the greater the heat leakage through walls, windows and roofs.
  • Presence or absence of wind. A strong wind increases the heat loss of buildings, blowing porches, basements and apartments through unsealed doors and windows.
  • The degree of insulation of the facade, windows and doors in the room. It is clear that in the case of a hermetically sealed metal-plastic window with a two-chamber double-glazed window, heat losses will be much lower than with a cracked wooden window and double-glazed windows.

It is curious: now there has been a trend towards the construction of apartment buildings with the maximum degree of thermal insulation. In the Crimea, where the author lives, new houses are being built right away with the facade insulated with mineral wool or foam plastic and with hermetically closing doors of entrances and apartments.


The facade is covered from the outside with basalt fiber slabs.

  • And finally, the actual temperature of the heating radiators in the apartment.

So, what are the current temperature standards in rooms for various purposes?

  • In the apartment: corner rooms - not lower than 20C, other living rooms - not lower than 18C, bathroom - not lower than 25C. Nuance: when the design air temperature is below -31C for corner and other living rooms, higher values ​​are taken, +22 and +20C (source - Decree of the Government of the Russian Federation of 05/23/2006 "Rules for the provision of public services to citizens").
  • In kindergarten: 18-23 degrees, depending on the purpose of the room for toilets, bedrooms and playrooms; 12 degrees for walking verandas; 30 degrees for indoor swimming pools.
  • In educational institutions: from 16C for boarding school bedrooms to +21 in classrooms.
  • In theaters, clubs, other places of entertainment: 16-20 degrees for the auditorium and + 22C for the stage.
  • For libraries (reading rooms and book depositories) the norm is 18 degrees.
  • In grocery stores, the normal winter temperature is 12, and in non-food stores - 15 degrees.
  • The temperature in the gyms is maintained at 15-18 degrees.

For obvious reasons, the heat in the gym is useless.

  • In hospitals, the maintained temperature depends on the purpose of the room. For example, the recommended temperature after otoplasty or childbirth is +22 degrees, in the wards for premature babies it is maintained at +25, and for patients with thyrotoxicosis (excessive secretion of thyroid hormones) - 15C. In surgical wards, the norm is + 26C.

temperature graph

What should be the temperature of the water in the heating pipes?

It is determined by four factors:

  1. Air temperature outside.
  2. Type of heating system. For a single-pipe system, the maximum water temperature in the heating system in accordance with current standards is 105 degrees, for a two-pipe system - 95. The maximum temperature difference between supply and return is 105/70 and 95/70C, respectively.
  3. The direction of the water supply to the radiators. For houses of the upper bottling (with supply in the attic) and lower (with pairwise looping of the risers and the location of both threads in the basement), the temperatures differ by 2 - 3 degrees.
  4. Type of heating appliances in the house. Radiators and gas heating convectors have different heat transfer; accordingly, to ensure the same temperature in the room, the temperature regime of heating must be different.

The convector somewhat loses to the radiator in terms of thermal efficiency.

So, what should be the temperature of heating - water in the supply and return pipes - at different outdoor temperatures?

We give only a small part of the temperature table for the estimated ambient temperature of -40 degrees.

  • At zero degrees, the temperature of the supply pipeline for radiators with different wiring is 40-45C, the return one is 35-38. For convectors 41-49 supply and 36-40 return.
  • At -20 for radiators, the supply and return must have a temperature of 67-77 / 53-55C. For convectors 68-79/55-57.
  • At -40C outside, for all heaters, the temperature reaches the maximum allowable temperature: 95/105, depending on the type of heating system, at the supply and 70C at the return pipe.

Useful extras

To understand the principle of operation of the heating system of an apartment building, the division of areas of responsibility, you need to know a few more facts.

The temperature of the heating main at the outlet from the CHP and the temperature of the heating system in your home are completely different things. At the same -40, a CHP or boiler house will produce about 140 degrees at the supply. Water does not evaporate only due to pressure.

In the elevator unit of your house, part of the water from the return pipeline, returning from the heating system, is mixed into the supply. The nozzle injects a jet of hot water at high pressure into the so-called elevator and recirculates the masses of cooled water.

Schematic diagram of the elevator.

Why is this needed?

To provide:

  1. Reasonable mixture temperature. Recall: the heating temperature in the apartment cannot exceed 95-105 degrees.

Attention: for kindergartens, a different temperature norm applies: no higher than 37C. The low temperature of the heating devices has to be compensated by a large heat exchange area. That is why in kindergartens the walls are decorated with radiators of such great length.

  1. Large volume of water involved in circulation. If you remove the nozzle and let the water flow directly from the supply, the return temperature will differ little from the supply, which will dramatically increase heat loss along the route and disrupt the operation of the CHP.

If you stop the suction of water from the return, the circulation will become so slow that the return pipeline can simply freeze in winter.

The areas of responsibility are divided as follows:

  • The temperature of the water injected into the heating mains is the responsibility of the heat producer - the local CHP or boiler house;
  • For the transportation of the coolant with minimal losses - the organization serving the heating networks (KTS - communal heating networks).

Such a state of heating mains, as in the photo, means huge heat losses. This is the area of ​​responsibility of the KTS.

  • For maintenance and adjustment of the elevator unit - housing department. In this case, however, the diameter of the elevator nozzle - something on which the temperature of the radiators depends - is coordinated with the CTC.

If your house is cold and all the heating devices are those installed by the builders, you will settle this issue with the residents. They are required to provide the temperatures recommended by sanitary standards.

If you undertake any modification of the heating system, for example, replacing the heating batteries with gas welding, you thereby assume full responsibility for the temperature in your home.

How to deal with the cold

Let us, however, be realistic: most often we have to solve the problem of cold in the apartment ourselves, with our own hands. Not always a housing organization can provide you with heat in a reasonable time, and not everyone will be satisfied with sanitary standards: you want your home to be warm.

What will the instructions for dealing with cold in an apartment building look like?

Jumpers in front of radiators

In front of the heaters in most apartments there are jumpers that are designed to ensure the circulation of water in the riser in any condition of the radiator. For a long time they were supplied with three-way valves, then they began to be installed without any shut-off valves.

The jumper in any case reduces the circulation of the coolant through the heater. In the case when its diameter is equal to the diameter of the eyeliner, the effect is especially pronounced.

The simplest way to make your apartment warmer is to insert chokes into the jumper itself and the connection between it and the radiator.


Here, ball valves perform the same function. It's not entirely correct, but it will work.

With their help, it is possible to conveniently adjust the temperature of the heating batteries: when the jumper is closed and the throttle to the radiator is fully open, the temperature is maximum, it is worth opening the jumper and covering the second throttle - and the heat in the room comes to naught.

The great advantage of such a refinement is the minimum cost of the solution. The price of the throttle does not exceed 250 rubles; spurs, couplings and locknuts cost a penny at all.

Important: if the throttle leading to the radiator is at least slightly covered, the throttle on the jumper opens completely. Otherwise, adjusting the heating temperature will result in batteries and convectors that have cooled down at the neighbors.


Another helpful change. With such a tie-in, the radiator will always be evenly hot along the entire length.

Warm floor

Even if the radiator in the room hangs on a return riser with a temperature of about 40 degrees, by modifying the heating system, you can make the room warm.

An output - low-temperature systems of heating.

In a city apartment, it is difficult to use underfloor heating convectors due to the limited height of the room: raising the floor level by 15-20 centimeters will mean completely low ceilings.

A much more realistic option is underfloor heating. Due to the much larger heat transfer area and more rational distribution of heat in the volume of the room, low-temperature heating will warm the room better than a red-hot radiator.

What does the implementation look like?

  1. Chokes are placed on the jumper and the eyeliner in the same way as in the previous case.
  2. The outlet from the riser to the heater is connected to a metal-plastic pipe, which is laid in a screed on the floor.

So that communications do not spoil the appearance of the room, they are put away in a box. As an option, the tie-in to the riser is moved closer to the floor level.


It is not a problem at all to transfer the valves and throttles to any convenient place.

Conclusion

You can find more information about the operation of centralized heating systems in the video at the end of the article. Warm winters!

Page 3

The building heating system is the heart of all engineering and technical mechanisms of the whole house. Which of its components will be selected will depend on:

  • Efficiency;
  • Profitability;
  • Quality.

Selection of sections for the room

All of the above qualities directly depend on:

  • heating boiler;
  • pipelines;
  • Method of connecting the heating system to the boiler;
  • heating radiators;
  • coolant;
  • Adjustment mechanisms (sensors, valves and other components).

One of the main points is the selection and calculation of sections of heating radiators. In most cases, the number of sections is calculated by design organizations that develop a complete project for building a house.

This calculation is affected by:

  • Enclosing materials;
  • The presence of windows, doors, balconies;
  • Room dimensions;
  • room type ( living room, warehouse, corridor);
  • Location;
  • Orientation to the cardinal points;
  • Location in the building of the calculated room (corner or in the middle, on the first floor or last).

The data for the calculation are taken from the SNiP "Construction Climatology". The calculation of the number of sections of heating radiators according to SNiP is very accurate, thanks to which you can perfectly calculate the heating system.

Looking through the statistics of visits to our blog, I noticed that search phrases such as, for example, appear very often “What should be the temperature of the coolant at minus 5 outside?”. Decided to post the old one. graph of quality regulation of heat supply based on the average daily outdoor temperature. I want to warn those who, on the basis of these figures, will try to sort out relations with the housing department or heating networks: the heating schedules for each individual settlement are different (I wrote about this in an article). Thermal networks in Ufa (Bashkiria) operate according to this schedule.

I also want to draw attention to the fact that regulation occurs according to average daily outside temperature, so if, for example, outside at night minus 15 degrees, and during the day minus 5, then the coolant temperature will be maintained in accordance with the schedule minus 10 o C.

As a rule, the following temperature charts are used: 150/70 , 130/70 , 115/70 , 105/70 , 95/70 . The schedule is selected depending on the specific local conditions. House heating systems operate according to schedules 105/70 and 95/70. According to schedules 150, 130 and 115/70, main heat networks operate.

Let's look at an example of how to use the chart. Suppose the temperature outside is minus 10 degrees. Heating networks operate according to the temperature schedule 130/70 , which means at -10 o С the temperature of the heat carrier in the supply pipeline of the heating network must be 85,6 degrees, in the supply pipeline of the heating system - 70.8 o C with a schedule of 105/70 or 65.3 about C on a 95/70 schedule. The temperature of the water after the heating system must be 51,7 about S.

As a rule, the temperature values ​​in the supply pipeline of heat networks are rounded off when setting the heat source. For example, according to the schedule, it should be 85.6 ° C, and 87 degrees are set at the CHP or boiler house.


Temperature
outdoor
air
Tnv, o C
Temperature of network water in the supply pipeline
T1, about C
Water temperature in the supply pipe of the heating system
T3, about C
Water temperature after heating system
T2, about C
150 130 115 105 95
8 53,2 50,2 46,4 43,4 41,2 35,8
7 55,7 52,3 48,2 45,0 42,7 36,8
6 58,1 54,4 50,0 46,6 44,1 37,7
5 60,5 56,5 51,8 48,2 45,5 38,7
4 62,9 58,5 53,5 49,8 46,9 39,6
3 65,3 60,5 55,3 51,4 48,3 40,6
2 67,7 62,6 57,0 52,9 49,7 41,5
1 70,0 64,5 58,8 54,5 51,0 42,4
0 72,4 66,5 60,5 56,0 52,4 43,3
-1 74,7 68,5 62,2 57,5 53,7 44,2
-2 77,0 70,4 63,8 59,0 55,0 45,0
-3 79,3 72,4 65,5 60,5 56,3 45,9
-4 81,6 74,3 67,2 62,0 57,6 46,7
-5 83,9 76,2 68,8 63,5 58,9 47,6
-6 86,2 78,1 70,4 65,0 60,2 48,4
-7 88,5 80,0 72,1 66,4 61,5 49,2
-8 90,8 81,9 73,7 67,9 62,8 50,1
-9 93,0 83,8 75,3 69,3 64,0 50,9
-10 95,3 85,6 76,9 70,8 65,3 51,7
-11 97,6 87,5 78,5 72,2 66,6 52,5
-12 99,8 89,3 80,1 73,6 67,8 53,3
-13 102,0 91,2 81,7 75,0 69,0 54,0
-14 104,3 93,0 83,3 76,4 70,3 54,8
-15 106,5 94,8 84,8 77,9 71,5 55,6
-16 108,7 96,6 86,4 79,3 72,7 56,3
-17 110,9 98,4 87,9 80,7 73,9 57,1
-18 113,1 100,2 89,5 82,0 75,1 57,9
-19 115,3 102,0 91,0 83,4 76,3 58,6
-20 117,5 103,8 92,6 84,8 77,5 59,4
-21 119,7 105,6 94,1 86,2 78,7 60,1
-22 121,9 107,4 95,6 87,6 79,9 60,8
-23 124,1 109,2 97,1 88,9 81,1 61,6
-24 126,3 110,9 98,6 90,3 82,3 62,3
-25 128,5 112,7 100,2 91,6 83,5 63,0
-26 130,6 114,4 101,7 93,0 84,6 63,7
-27 132,8 116,2 103,2 94,3 85,8 64,4
-28 135,0 117,9 104,7 95,7 87,0 65,1
-29 137,1 119,7 106,1 97,0 88,1 65,8
-30 139,3 121,4 107,6 98,4 89,3 66,5
-31 141,4 123,1 109,1 99,7 90,4 67,2
-32 143,6 124,9 110,6 101,0 94,6 67,9
-33 145,7 126,6 112,1 102,4 92,7 68,6
-34 147,9 128,3 113,5 103,7 93,9 69,3
-35 150,0 130,0 115,0 105,0 95,0 70,0

Please do not focus on the diagram at the beginning of the post - it does not correspond to the data from the table.

Calculation of the temperature graph

The method for calculating the temperature graph is described in the reference book (Chapter 4, p. 4.4, p. 153,).

This is a rather laborious and lengthy process, since several values ​​must be calculated for each outdoor temperature: T 1, T 3, T 2, etc.

To our joy, we have a computer and a MS Excel spreadsheet. A colleague at work shared with me a ready-made table for calculating the temperature graph. She was once made by his wife, who worked as an engineer for a group of regimes in thermal networks.

In order for Excel to calculate and build a graph, it is enough to enter several initial values:

  • design temperature in the supply pipeline of the heating network T 1
  • design temperature in the return pipeline of the heating network T 2
  • design temperature in the supply pipe of the heating system T 3
  • Outside temperature T n.v.
  • Indoor temperature T v.p.
  • coefficient " n» (it is usually not changed and is equal to 0.25)
  • Minimum and maximum cut of the temperature graph Cut min, Cut max.

All. nothing more is required of you. The results of the calculations will be in the first table of the sheet. It is highlighted in bold.

The charts will also be rebuilt for the new values.

The table also considers the temperature of direct network water, taking into account wind speed.

What else to read