Hydraulic testing of boilers carried out after completion of all welding work and before installation of insulation and application of protective coatings. When testing for strength and density, taps and valves (spring) are blocked or muffled. The boiler is filled with water at a temperature not lower than plus 70C. And not higher than 40-500 C. The temperature in the boiler room should not be lower than + 50C. The pressure is created by a hand pump with a check on the control pressure gauge. The pressure rise time is 10-15 minutes. Inspection is carried out at working pressure (10 min), at test pressure (5 min) and again at working pressure. If during the inspection no leaks, ruptures of welds, residual deformations and other defects are found, then the boiler is recognized as serviceable. The test results are recorded in the boiler's cord book.
The value of the test pressure Ppr for boilers is set for two cases: - during manufacture or repair; - assembled with fittings. The values of test pressures depend on the type of boilers and their operating conditions. For boilers, superheaters, economizers and their elements operating at temperatures up to 3500C, the test pressure is equal to 1.5 of the working pressure Рр, but not less than (Рр +0.1) MPa. And in assembled form with fittings - 1.25Rp, but not less than (Rp +0.1) MPa.
For superheaters and their elements operating at temperatures above 3500C, the test pressure is calculated by the formula:
where is the yield strength of the material at a temperature of 3500C, MPa.
is the yield strength of the material at operating temperature, MPa.
The fittings of the boilers are tested for double working pressure, when testing for sealing closing - at a pressure of 1.25 Pr. The feed valves of the boilers are tested for a pressure of 2.5 Pp. And gas cavities of utilization boilers - with air under pressure of 0.01 MPa.
After hydraulic tests a steam sample of the boiler is made at operating pressure. Safety valves must be adjusted to the following opening pressures (in MPa):
During steam tests, the pressure is increased in stages and with stops during which intermediate inspections are made. At operating pressure, the boiler is checked for at least 30 minutes.
Mooring tests of the boiler are carried out after the steam test. Their purpose is to adjust and test in operation on a working boiler all systems, devices and automation equipment. During mooring tests, the reliability of the boiler plant is evaluated and the operating parameters are determined, as well as the thermal expansion of the boiler on the supports is controlled.
The final stage is sea trials. At the same time, the reliability and safety of the operation of the entire boiler plant in certain modes are determined and comprehensive thermal engineering tests are carried out.
When repairing boilers full program tests are determined by the Register. The scope of the program depends on the category of the repair being carried out.
In accordance with the rules of the USSR Gospromatomnadzor, boilers, superheaters and water economizers operating under an overpressure of more than 0.07 MPa, as well as hot water boilers with a water heating temperature above 115 ° C, are registered with the USSR Gospromatomnadzor bodies and subjected to technical examination.
The technical examination consists of an internal inspection and a hydraulic test of the units. Superheaters and economizers, constituting one unit with the boiler, will be examined simultaneously with it.
The boiler is inspected inside, checking for cracks, ruptures, metal corrosion, violations of rolling and welded joints, and other possible defects.
A hydraulic test is performed to check the strength of the pressurized elements of the boiler and the tightness of their connections. Drums and chambers of steam boilers, screen and convective pipe systems, superheaters and water economizers are subjected to hydraulic testing. Hydraulic tests of individual elements and blocks, carried out on an enlarged assembly site, do not exempt the installed equipment from hydraulic testing.
Before the start of the hydraulic test, all hatches and manholes of the boiler are closed, on which permanent gaskets are installed, shut-off valves that disconnect the boiler unit from other devices and pipelines, and plugs are installed between the boilers and safety valves. For testing, the boiler is filled with water at a temperature not higher than 60 and not lower than 5 °C at an ambient air temperature not lower than 5 °C. When filling the boiler with water, air is removed through a safety valve or a special air cock.
To fill the boiler with water and create a test pressure, which is increased gradually and smoothly, an electric pump or a manual hydraulic press is used. The test pressure is maintained for 5 minutes, after which it is gradually reduced to the working one. In the event of a pressure drop, find out the place where the water passes. With a slight decrease in pressure due to leaky fittings, the hydraulic test can be continued, while the test pressure is maintained by pumping water, but not more than 5 minutes. The water pressure in the boiler is measured by two tested pressure gauges, one of which must be a control one.
The boiler unit is inspected at operating pressure, tapping the welds with light blows of a hammer weighing no more than 1.5 kg. Special attention pay attention to the density of welds, rolling and flanged joints. If, when testing the boiler, shocks, noise, knocking are heard inside it, or a sharp drop in pressure occurs, the hydraulic test is stopped to detect damage.
The boiler is considered to have passed the hydraulic test if there are no breaks, leaks or deformations in it. If water droplets appear in the welds or pipe walls or they fog up, the boiler is considered to have failed the test. Boilers that have passed the hydraulic test can be bricked up and thermal insulation work can be performed on them.
Permission to operate the boiler, superheater and economizer is issued on the basis of the results of the technical examination.
The technical examination of pipelines consists in checking the installation documentation, external examination and hydraulic testing of the installed pipelines. The technical examination of the installed pipelines is carried out by the controller engineer of the USSR Gospromatomnadzor, pipelines that are not subject to registration with the USSR Gospromatomnadzor bodies - the installation site management with the participation of a representative of the customer's technical supervision.
External inspection and hydraulic testing of pipelines from seamless pipes is allowed if they are already insulated and welded joints and flange connections are available for inspection. Pipelines made of welded pipes are subjected to a hydraulic test before thermal and anticorrosive insulation is applied to them. Welded joints are subjected to heat treatment prior to hydraulic testing.
Hydraulic testing of installed pipelines is carried out to check the strength and tightness of their connection. Before testing large-diameter pipelines, it is checked whether the supports and suspensions can withstand the additional load from the weight of water, which will be significant for large pipe diameters. In addition, attention is paid to the protection against additional bending forces of fragile lens compensators and cast iron fittings.
For supply pipelines, the working pressure is taken as the pressure developed feed pumps with closed valves.
When preparing a pipeline for a hydraulic test, the following is checked: whether welding work and heat treatment of welded joints are completed; whether gaskets are supplied in flange connections and whether they are tightened. Then, a scheme of the tested pipeline is assembled and, after checking the serviceability of the hydraulic press, it is connected to a water supply source, and the pressure pipe is connected to the tested pipeline. At the lowest point of the test section there must be a drain valve to empty the pipeline after the test, and at the highest point - an air cock to remove air during filling with water. A serviceable sealed pressure gauge is installed on the discharge pipeline, the verification period of which has not expired. When testing pipelines and vessels, proven spring pressure gauges with an accuracy class of at least 1.5 and a case diameter of at least 150 mm are used.
The assembly of the circuit for testing consists in the fact that the pipeline under test is disconnected from the existing or unmounted pipelines and equipment and all shut-off devices in the test section are opened, except for the valves on the drainage and drain lines, which must be closed. If there are safety valves on the pipeline, plugs are installed between them and the pipeline.
For hydraulic testing of pipelines, hydraulic pumps with electric drive and manual hydraulic presses are used.
The pipeline is slowly filled with raw water at a temperature not lower than the ambient temperature, as this will prevent it from sweating. At the same time, the air vents open completely. After removing the air, the air vent is closed and the pressure is gradually increased to the test one, keeping it for 5 minutes, then the pressure is reduced to the working one. Further, at operating pressure, welded and flanged joints are examined. During inspection, the welded joints are tapped with a hammer and made sure that there are no leaks, cracks, fistulas and other defects. If defective places are found, they are marked with chalk so that after the pressure is removed, they can be easily detected. Defective places in the welds are removed and re-welded. It is not allowed to correct defects before the pressure is reduced to zero.
Flanged joints and gland seals in which a leak was detected are disassembled, the cause of the leak is identified and eliminated. After elimination of defects, the hydraulic test is repeated.
The results of the hydraulic test are considered satisfactory if no pressure drop has occurred (verified by the pressure gauge) and if no leaks or sweating are found in welds, pipes, fittings and fittings. A hydraulic test cannot be performed at a negative ambient temperature, as this may defrost and break fittings, especially cast iron, and small pipes. For the same reason, from pipelines to winter time in unheated premises at the end of the hydraulic test, immediately and carefully drain the water. Areas that do not have a free drain (coils, concave sections) are blown with compressed air. To drain water, flange connections are dismantled near the cast-iron fittings. When the water is lowered, the air vents open.
The results of the inspection of pipelines and permission to put them into operation are recorded in the passport.
Installation of boilers - Hydraulic testing of boilers and pipelines
gardenweb.ru
To check the strength of the structure, the quality of its manufacture, all elements of the boiler, and then the boiler as an assembly, are subjected to hydraulic tests with a test pressure ppr. Hydraulic tests are carried out at the end of all welding work, when insulation and protective coatings are still missing. The strength and density of welded and rolling joints of elements is checked by test pressure pp = 1.5pp, but not less than pp + 0.1 MPa (pp is the working pressure in the boiler).
The dimensions of elements tested with a test pressure of pp + 0.1 MPa, as well as elements tested with a test pressure higher than indicated above, must be subjected to a verification calculation for this pressure. In this case, the stresses should not exceed 0.9 of the yield strength of the material σts, MPa.
After the final assembly and installation of fittings, the boiler is subjected to a final hydraulic pressure test pp = 1.25pp, but not less than pp + 0.1 MPa.
During hydraulic tests, the boiler is filled with water and the working water pressure is brought to the test pressure ppr with a special pump. The test results are determined by visual inspection of the boiler. As well as the rate of pressure drop.
The boiler is recognized as having passed the test if the pressure in it does not drop and no leaks, local bulges, visible changes in shape and residual deformations are detected during inspection. Sweating and the appearance of small water droplets at the rolling joints are not considered leaks. However, the appearance of dew and tears at the welds is not allowed.
steam boilers after installation on the ship, they must be subjected to a steam test at operating pressure, which consists in the fact that the boiler is brought into service and checked in operation at operating pressure.
Gas cavities of utilization boilers are tested with air at a pressure of 10 kPa. Gas ducts of auxiliary and combined PCs are not tested.
External inspection of the boilers complete with apparatus, equipment, service mechanisms and heat exchangers, systems and pipelines is carried out under steam at operating pressure and, if possible, combined with a test of the operation of the ship's mechanisms.
During the inspection, it is necessary to make sure that all water-indicating devices (water-gauge glasses, test taps, remote water level indicators, etc.) are in good condition, as well as that the upper and lower blowing of the boiler is working properly.
The condition of the equipment, the serviceability of the drives, the absence of steam, water and fuel leaks in glands, flanges and other connections should be checked.
Safety valves must be tested in operation for operation. The valves must be adjusted to the following pressures:
Rotkr ≤ 1.05 Pwork for Pwork ≤ 10 kgf/cm2;
Rotkr ≤ 1.03 Pwork for Pwork > 10 kgf/cm2;
The maximum allowable pressure during the action of the safety valve Pmax ≤ 1.1 Rrab.
The safety valves of superheaters must be adjusted to operate with some advance of the boiler valves.
The manual actuation of the blasting must be checked in action. safety valves.
With positive results of external examination and verification in operation, one of the boiler safety valves must be sealed by the inspector.
If it is not possible to check the safety valves on the disposal boilers in the parking lot due to the need for a long operation of the main engine or the impossibility of supplying steam from the auxiliary fuel-fired boiler, then the adjustment and sealing of the safety valves can be checked by the shipowner during the voyage with the issuance of the relevant act.
During the survey, the operation of the systems should be checked. automatic regulation boiler plant.
At the same time, you should make sure that the alarm, protection and blocking devices work flawlessly and are triggered in a timely manner, in particular when the water level in the boiler drops below the permissible level, when the air supply to the furnace is interrupted, when the flame in the furnace is extinguished and in other cases provided for by the automation system.
You should also check the operation of the boiler installation when changing from automatic to manual control and vice versa.
If during the external examination defects are found, the cause of which cannot be established by this examination, the inspector may require an internal examination or hydraulic test.
studfiles.net
For the normal functioning and efficient use of boilers and units that heat water, it is imperative that the mode and adjustment tests of hot water boilers are carried out. The essence of such tests is to select the most optimal modes of operation of the equipment that is involved in the heating system. Content
Tests should be carried out after the installation of all equipment, completion of installation of commissioning mechanisms, as well as after appropriate training of workers in the correct and safe operation mechanisms and units of this system.
Regime and adjustment work should be carried out after installation or repair of the boiler. In exceptional cases, such work may also be carried out during the operation period.
Regime and adjustment tests of hot water boilers are carried out to select best modes works, to compile a regime map and to draw up recommendations for improving the efficiency of equipment.
In the process of setting up the units, fuel consumption, flow rate, pressure, fuel combustion temperature and some other parameters are checked. physical process fuel combustion.
Hot water boilers are installed for space heating. Their main advantage is that they can be installed where there is no central heating.
Read more about wood-fired boilers here.
After the necessary work calculations are carried out to determine the minimum and maximum indicators of the efficiency of the boiler house.
The main objectives of such events are: familiarization with the data of the registration certificate and the operation of the unit, drawing up a test method, drawing up a consistent program, conducting trial and preparatory work, carrying out the main work, calculating the results and compiling a report and regime maps.
Regime and adjustment measures should be carried out: for boilers on liquid and solid fuels - 1 time in 5 years; for gas boilers - 1 time in 3 years.
Mode tests of water-heating units are carried out to install an energy-saving method that does not require large cash costs.
These activities are also called environmental and thermal engineering. During the adjustment, shortcomings in the operation of the entire water heating system are revealed.
After receiving all the necessary data, it is developed integrated system to improve the efficiency of the devices.
The need for routine adjustment of boilers:
Mode tests of solid fuel boilers are carried out 1 time in 5 years, and gas - 1 time in 3 years.
The advantages and benefits of a heating water boiler are beyond doubt, but like any technical means, boilers periodically need maintenance.
How to correctly calculate the power of a gas boiler, read here.
Technical examination (TO) of hot water boilers and hot water equipment is carried out in order to check the operability of all mechanisms and to avoid accidents due to technical reasons.
Maintenance can be carried out in two ways - visual and hydraulic. With visual - internal and external inspection is carried out. With hydraulic - the boiler must be under test pressure for several minutes.
A hydraulic test must be carried out only after the internal and external tests have been carried out.
Technical examinations are carried out: primary - the first time before the boiler is put into operation; periodic - once every eight years for control, and extraordinary - at the end of the service life, in case of accidents or explosions, after natural disasters. Such events are carried out only by an organization that has a license from Gostekhnadzor, specialists and special equipment.
The purpose of testing hot water boilers is to determine the actual operational, thermal and environmental performance.
See the diagram of the hot water boiler here.
For a qualitative inspection of water heating installations, work should be carried out in the following sequence:
The technical condition of the boiler is checked once every 5 years, and hydraulic tests and measurement of the geometric dimensions of the unit are carried out once every 10 years.
Technical diagnostics water-heating devices are carried out for the purpose of safe operation of mechanisms. In the event of a defect, accident or expiration of the service life - to determine the limit service life.
Such a procedure can be carried out only by those public and private organizations that have permission from Gostekhnadzor and with the availability of specialists and equipment for diagnosing.
Procedure for diagnosing heating devices:
Heat recovery boilers are designed for the preparation of hot water for industrial and household purposes with a maximum design temperature of up to 115°C.
Read more about electric hot water boilers here.
The diagnostic devices used must be equipped with non-destructive testing elements that can accurately determine the presence of a defect, its location and size.
To measure parameters such as pipe deflection, diameter, deflections and sags of drums, special tools must be used that determine all dimensions to the nearest mm. To measure the wall thickness, it is necessary to use linear instruments that have an error of no more than 0.1 mm.
Technical diagnostics of metal and welds should be carried out with tools that have passed state testing and meet accepted standards.
Diagnosis should be carried out 1 time in 4 years.
Technical examination, diagnostics and operational and adjustment tests of hot water boilers and hot water equipment - a guarantee of the safe operation of the units, extension of the service life, concern for human health and avoidance of environmental pollution toxic gases and dust.
kotlotech.ru
Hydraulic tests of boilers are carried out after completion of all welding work and before installation of insulation and protective coatings. When testing for strength and density, taps and valves (spring) are blocked or muffled. The boiler is filled with water at a temperature not lower than plus 70C. And not higher than 40-500 C. The temperature in the boiler room should not be lower than + 50C. The pressure is created by a hand pump with a check on the control pressure gauge. The pressure rise time is 10-15 minutes. Inspection is carried out at working pressure (10 min), at test pressure (5 min) and again at working pressure. If during the inspection no leaks, ruptures of welds, residual deformations and other defects are found, then the boiler is recognized as serviceable. The test results are recorded in the boiler's cord book. The value of the test pressure Ppr for boilers is set for two cases: - during manufacture or repair; - assembled with fittings. The values of test pressures depend on the type of boilers and their operating conditions. For boilers, superheaters, economizers and their elements operating at temperatures up to 3500C, the test pressure is equal to 1.5 of the working pressure Рр, but not less than (Рр +0.1) MPa. And when assembled with fittings - 1.25Рр, but not less than (Рр +0.1) MPa. For superheaters and their elements operating at temperatures above 3500С, the test pressure is calculated by the formula:
where is the yield strength of the material at a temperature of 3500C, MPa. is the yield strength of the material at operating temperature, MPa. The feed valves of the boilers are tested for a pressure of 2.5 Pp. And gas cavities of utilization boilers - with air under pressure of 0.01 MPa. After hydraulic tests, a steam sample of the boiler is made at operating pressure. Safety valves must be adjusted to the following opening pressures (in MPa):
During steam tests, the pressure is increased in stages and with stops during which intermediate inspections are made. At operating pressure, the boiler is checked for at least 30 minutes. Mooring tests of the boiler are carried out after a steam test. Their purpose is to adjust and test in operation on a working boiler all systems, devices and automation equipment. During mooring trials, the reliability of the boiler plant is evaluated and the operating parameters are determined, as well as the thermal expansion of the boiler on the supports is controlled. The final stage is sea trials. At the same time, the reliability and safety of the operation of the entire boiler plant in certain modes are determined and comprehensive thermal engineering tests are carried out. When repairing boilers, the full test program is determined by the Register. The scope of the program depends on the category of the repair being carried out.
morez.ru
When dealing with any thermal equipment, regardless of the type of fuel and design, I want to have a guarantee of its reliability, durability and quality.
Hydraulic tests of boilers are just carried out to test the entire structure for strength. All elements of the thermal system are tested separately. Then, in assembled form, hydraulic tests of the boilers as a whole are carried out.
The test is carried out upon completion of welding work, when there are still no protective coatings, as well as insulation. The density and strength of rolling and welded joints are tested with a test pressure equal to 1.5 working pressures in the boiler. Stresses should not exceed the yield of the material by 0.9 of the limit.
After complete assembly and installation of all necessary fittings, the boiler is subjected to a final test at a pressure of 1.25 from the working one. The boiler plant is filled with water. The working pressure of the water is adjusted by a special pump to the test pressure. The result of the test is determined by visual inspection of the boiler plant and by the rate of pressure reduction.
The boiler is deemed to have passed the test if there is no pressure drop and if visual inspection no bulges, leaks, changes in shape or permanent deformations are detected. The appearance of small drops of dew in the metas of rolling joints and sweating are not leaks. The appearance of dew at the welds is unacceptable and is considered a leak.
Similar tests are carried out for all types of boilers, regardless of the model or fuel used. The purpose of hydraulic testing is to check the reliability of thermal equipment in an emergency. Boilers that do not pass the hydraulic test must be rejected.
Steam boilers are also tested. The check is carried out at operating pressure when the boiler is put into operation. Air with a pressure of 10 kPa is used to test the gas cavities of the utilization boiler. Gas ducts of combined and auxiliary steam boilers are not subjected to hydraulic tests.
www.remontdoma-vl.ru
General information about the technical supervision of steam boilers external and internal inspection of the boiler hydraulic test.
The strength and tightness of all elements of the boiler working under pressure are checked after repair of the boiler by a hydraulic test for working pressure.
Hydraulic test of the boiler. A hydraulic test is carried out in order to determine the strength of the pressure elements of the boiler and the density of their joints.
The purpose of the hydraulic (pneumatic) test is to check the strength and tightness of welded joints and all elements of boilers, steam heaters, pressure vessels, as well as steam and hot water product pipelines. Subject to hydraulic test
During hydraulic tests at a permitted working pressure of more than 0.5 MPa, the test pressure should be 1.25 working pressure, with a permitted pressure of more than 0.5 MPa - 1.5 working pressure. Typically, hydraulic tests are carried out at a positive temperature of at least 15 ° C when air is removed from the vessel or boiler. The pressure rise time should be at least 10 minutes and rise smoothly. The exposure time in this case is at least 20 minutes. After that, the pressure is reduced to the working one and the welds are inspected. Sometimes a phosphor is added to the liquid and the surface is examined under ultraviolet light. The surface itself is coated with indicator substances for better detection of leaks (starch, etc.).
Each boiler unit is subject to technical examination by an inspector of Gosgortekhnadzor. External inspection is carried out at least once a year, internal - at least once every three years, hydraulic pressure test (working plus 3 bar) - at least once every six years. An extraordinary survey is carried out after a major repair of the boiler elements operating under pressure.
In gas, gas-oil and dust-gas burners, the welds of gas elements, in addition to technical inspection and measurement, are subjected to a hydraulic strength test with an overpressure of 1 MPa and a density (tightness) test with kerosene according to GOST 3285-77. gas elements burners are also subjected to a leak test when installed together with a gas pipeline within the boiler in accordance with the requirements of the Safety Rules in the gas industry>.
Elements of factory and assembly blocks are exposed to intense oxygen corrosion after their hydraulic testing at boiler plants and assembly sites, as well as in assembly. The water remaining in them after this operation is often the cause of serious ulcerative lesions of the metal of the boilers before they are put into operation. Long-term storage of blocks on the installation site without their conservation also leads to dangerous corrosion before the boiler is installed.
When conducting hydraulic tests of the boiler at the end of the repair, the tract is filled without first draining the preservative solution. Before putting the boiler into operation, the solution is drained from all drained sections, its residues are displaced by condensate through the appropriate drains and the drainage tank, and from there they are sent to the waste water pit for neutralization. Washing the circuit is carried out until the content of hydrazine after the boiler is not more than 3 M g/kg, and the pH of the condensate is not more than 9.5.
It is advisable to perform hydraulic testing of boiler drums with inhibited water of the same composition as is used for pressure testing of pipe
Hydraulic tests of a number of corroded T rub showed their reduced mechanical strength; some pipes showed a leak at a pressure not exceeding the working pressure in the boiler. By etching defective pipes in a 10% hydrochloric acid solution, a weak corrosion resistance of the metal located under the shells was established.
As examples in Fig. Figures 1-6 and 1-7 show the screen block of the rear wall of the B-50-40 boiler furnace and the superheater block. Screen units up to 3 wide are supplied as finished heating surfaces with top and bottom chambers hydraulically tested at the factory.
Each hollow casting must be subjected to a hydraulic test pressure test in accordance with GOST 356-80. Hydraulic testing of castings that have undergone complete control by radiography or ultrasound at the manufacturer of castings can be combined with hydraulic testing of a boiler element or pipeline with a test pressure established by the NTD for the element or object.
Non-ferrous metals and alloys in boilers and pipelines are of limited use for the manufacture of small sizes of valves and instrumentation, and therefore the Rules for boilers and pipelines do not contain such detailed requirements for them as for steel and cast iron. The use of bronze and brass for parts of boilers and pipelines is permissible at a metal temperature not exceeding 250 ° C. The test pressure of hydraulic testing of valve bodies must comply with the requirements of GOST 356-80.
Regular processing of daily graphs of steam temperature behind each boiler (at a steam temperature of 450 C and above) allows you to timely take into account the operating time when the steam temperature exceeds the nominal one. During repairs, as well as when stopping the boilers for hydraulic testing, a thorough inspection of the pipes of the heating surfaces and their welded joints is carried out to identify pipes with large residual deformation, corrosion, ash wear, cracks in welded joints, unacceptable ovality and other defects. These data are analyzed by the metal laboratory, which also monitors
The purpose of the hydraulic test is to check the strength and density of welded joints, as well as all elements of boilers, superheaters, economizers, pressure vessels, and steam and hot water pipelines. Subject to hydraulic test
Hydraulic testing of boilers, superheaters, 39-959 609
All pipes for high and supercritical pressure boilers undergo a hydraulic pressure test, determined by the formulas
Control of welded joints of steam boilers and pipelines is carried out by external examination mechanical testing of samples cut from control plates, from control joints of pipes or from the products themselves; X-ray or gamma-ray transmission; ultrasonic flaw detection; macro- and microstructure studies; and hydraulic testing.
The calculation of steam boiler elements for strength should provide such dimensions of the calculated elements at which the stresses arising during operation and during hydraulic tests would not lead to residual shape distortions or to destruction.
Hydraulic testing of steam and hot water boilers
The boilers are subjected to a hydraulic test after their installation on the foundations, when the lining has not yet been made, all parts of the boilers are available for inspection and the boilers are not connected to the systems.
Hydraulic testing of vertical water-tube steam boilers is carried out before they are bricked up.Based current rules Boiler supervision hydraulic testing of steam boilers with a working pressure above 0.7 atm is carried out according to table. 26.
Hydraulic testing of the boiler must be carried out with fittings installed on it.
Prior to the installation of the superheater in the coils, the absence of visible external defects is checked for the compliance of the outer diameters and wall thicknesses of the steel pipes with the design dimensions, the ovality of the coil pipes, the correctness of the bends and the permeability of the coils, as well as their tightness. The tightness is checked by hydraulic testing of each coil individually for a pressure exceeding the operating pressure of the boiler by 1.25 times.
After installation and alignment of the drums, work is carried out on rolling and assembling the boiler and screen pipes. They install the intra-drum equipment and fittings and test the boiler with hydraulic pressure. After a hydraulic test, the laying of the boiler lining is carried out.
Before assembly, all finned tubes and rolls are subjected to a hydraulic pressure test equal to 1.25 p 4-5 atm (where p is the operating pressure of the boiler in atm).
Hydraulic testing of butt-welded pipes is carried out at a pressure of 2p + 11 atm using devices for individual pressure testing (p is the working steam pressure in the boiler)
The change of rivets is carried out only with the knowledge and permission of the Gosgortekhnadzor inspection. When replacing more than 15 adjacent rivets, an extraordinary hydraulic test of the boiler with the participation of a representative of the Gosgortekhnadzor inspection is mandatory.
An internal inspection is carried out at least once every 4 years. When it is performed, first of all, the boiler drum is inspected from the inside. Hydraulic testing of the boiler for strength and density of its elements is carried out at least every 8 years. Hydraulic and testing is always preceded by an internal inspection. The test is carried out by raising the pressure above the working one in a boiler filled with water in order to check its strength and density. The results of the survey are recorded in the passport of the boiler unit.
At the end repair work the commission checks the acts of operational acceptance, internal inspection of the boiler drums, hydraulic testing, inspection of the boiler safety fittings and devices. Based on the test results of the boiler and the listed documentation, an act of general acceptance of the boiler from the overhaul is drawn up.
When installing the boiler block not on the foundation, but on the laying of the brickwork, an additional lifting of the assembled boiler will be required in this case, the installation sequence will change somewhat and will consist of the following stages of installing the boiler block on the foundation of the installation on temporary extensions of the side walls of the boiler piping frame and side platforms of the ladders for installing fittings installation of a cast-iron partition (if it was not mounted in the block) lifting the boiler block and installing it on temporary support trestles completion of assembly of the framing frame, platforms and ladders laying out the lining to the design mark of the bottom of the boiler support frame installation of the boiler block on the laying of the lining alignment of the installed boiler block pouring cement of the support frame of the steam superheater installation installation of intra-drum devices and a blowing device production of brickwork above the mark of the sole of the support frame of the boiler hydraulic testing of the boiler its pro alkalization and testing for vapor density.
qpeAax used for hydraulic testing must be free of oily and suspended solids. To eliminate corrosion of boiler elements made of pearlite steel, it is advisable to add one of the following mixtures of inhibitors to water [L. 24]
For anti-corrosion protection of internal surfaces of screen coils and steam heaters during their transportation and storage at the boiler plant after a hydraulic test, a volatile inhibitor is introduced into them, and their ends must be sealed with polyethylene caps. External surface these parts of the boiler must be protected
During hydraulic testing of boilers, vessels and pipelines, their strength and density are checked. However, in cases where increased requirements are imposed on the tightness of products, a pneumatic leak test is carried out using one of the following aquarium methods for washing the pressure drop of halogen leak detectors with a mass spectroscopic hot environment of stable traces of pressure increase in the pressure chamber.
For MTO of metal pipes, heating piping and steam boiler piping, it was proposed to use a hydraulic test with increased pressure. However, this raises a number of difficulties. For the implementation of the MTO, the plastic deformation should be 0.5-27o- However, the tolerance for the wall thickness of the pipes reaches 20-25%. The pipes of the heating surfaces have different safety margins at low temperatures, since, for example, the economizer is calculated according to the yield strength at a maximum operating temperature of up to 250-300 ° C, and the superheater is calculated according to the long-term strength limit at operating temperatures. The yield strength of steel of the same grade can vary according to the specifications over a very wide range. If a
It should be noted that only the reduction of the inverse balance of the boiler makes it possible to quantitatively identify heat losses and related shortcomings in its operation and outline ways to eliminate them. Therefore, this method is in many cases preferred, although it gives less accurate results in determining the efficiency of the boiler. Often tests are carried out on a forward and reverse balance. This combination is the most acceptable, as it allows you to get a complete picture, both qualitative and quantitative. Apparently, there is no need to give formulas for determining heat losses with exhaust gases, with chemical underburning, etc. . Currently, there is no approved unified methodology for thermal testing of contact economizers. The scope and nature of the measurements depend on the tasks involved. The most common types of tests are thermotechnical, aerodynamic and thermochemical, carried out when performing commissioning. The purpose of these tests is to determine the possible temperature of heating water and outgoing flue gases, maximum heat output without replacing the smoke exhauster, maximum performance on water while maintaining a normal hydraulic regime and the absence of a noticeable entrainment of water into the gas ducts. At the same time, studies of the quality of heated water are usually carried out simultaneously and changes in its composition, in particular, corrosion activity, are studied. Such tests necessarily accompanied the commissioning of the first industrial contact economizers.
Transportation of the boiler on dirt and paved roads is carried out by tractor traction using special sledges or carts. The montale of the boiler, when it arrives in assembled form, is produced in next order the boiler block delivered from the manufacturer is dragged and installed on the foundation, the correct installation of the boiler block is checked for connection with the foundation, the support frame is poured with cement mortar, the strapping frame, platforms and stairs are installed, the fittings are installed, the boiler is hydraulically tested, the cast-iron baffle is installed, the intra-drum device is installed and blowing device carry out brickwork, alkalize the boiler and test it for steam density.
mash-xxl.info
What water is used to feed the heating network?
What valves can be used as shut-off valves with DN up to 50 mm in hot water supply systems?
When does the heating season start?
In what case is a round-the-clock dispatching control organized in an organization?
Who owns the right to issue orders for work at thermal power plants?
How is the division of responsibility for the operation of thermal power plants between the organization - the consumer of thermal energy and the energy supply organization determined?
mybiblioteka.su - 2015-2018. (0.006 sec)
The hydraulic test of the boiler is carried out in accordance with NP-046-03 after receiving satisfactory results of the internal inspection.
Together with the boiler, its fittings are tested: safety valve, water level indicators, shut-off devices. If it is necessary to install plugs, they are placed behind the locking elements. For hydraulic testing of the boiler, water with a temperature not lower than 5 °C and not higher than 40 °C is used.
When filling the boiler with water to remove air, the safety valve or air valve must be opened until water appears from it. If, as a result of filling the boiler with water, dew appears on its walls, then the test should be carried out only after the walls have dried.
During the test, the pressure in the boiler must be measured with two pressure gauges, one of which must have an accuracy class of at least 1.5.
The value of the test pressure is determined in accordance with paragraph 4.14.2 of NP-046-03. The rise in pressure to the test should be slow and smooth, without shocks. The total pressure build-up time must correspond to that specified in the installation and operating instructions for the boiler. The test pressure shall be controlled by two manometers. Pressure gauges must be of the same type, with the same accuracy class of at least 1.5, measurement limit and division value.
If it is not possible to achieve the required test pressure with a machine-driven pump, the pressure increase must be carried out with a hand pump. Upon reaching the test pressure, the water supply to the boiler is stopped and the supply line is blocked by a shut-off body; after that for 10 min. there should be no pressure drop.
After 10 min. the pressure is reduced to the working one and the boiler is inspected.
If noise, knocks or a sharp drop in pressure appear during the test period, the hydraulic test should be immediately stopped, their cause should be found out and eliminated.
The results of the hydraulic test of the boiler are considered satisfactory if:
If, during the inspection of the boiler, leaks are found in the rolling or riveting joints, it is necessary to check the defective joints using non-destructive methods flaw detection for the absence of intergranular cracks. Elimination of leaks is allowed only with satisfactory results of such a check.
In case of detection of defects by the inspecting person, depending on their nature, a decision may be made to suspend the operation of the boiler, put it into temporary operation, reduce the period of the next examination of the boiler, reduce the operating parameters, etc.
If, during the inspection of the boiler, defects are revealed that raise doubts about its strength, or defects, the cause of which is difficult to establish, the operation of such a boiler should be prohibited until the conclusion of a specialized organization on the causes of the appearance of these defects, as well as on the possibility and conditions of its further operation. The possibility of operating the boiler at reduced parameters must be confirmed by a strength calculation, and a verification calculation of the throughput of the safety valves and their outlet pipes must be carried out.
Hydraulic testing of vessels is carried out in accordance with NP-044-03 after obtaining satisfactory results of external and internal examinations.
The vessel and fittings installed on it are subjected to a hydraulic test.
Vessels having a protective coating (enamelling, lining) or insulation are subjected to an initial hydraulic test before coating or insulation is applied.
Vessels with an outer casing are subjected to a hydraulic test before the installation of the casing.
Hydraulic testing of vertically installed vessels may be carried out in a horizontal position, provided that the strength of the vessel body is ensured, for which the strength calculation must be performed by the developer of the vessel design, taking into account the accepted method of supporting the vessel during its hydraulic testing.
In combined vessels with two or more working cavities designed for different pressures, each cavity must be subjected to a hydraulic test with a test pressure determined depending on its design pressure.
The test procedure must be specified in the design of the vessel and specified in the manufacturer's instructions for the installation and operation of the vessel.
When filling the vessel with water, the air must be completely removed.
For hydraulic testing of vessels, water with a temperature not lower than 5 °C and not higher than 40 °C should be used, unless otherwise specified in the project.
By agreement with the developer of the vessel design, another liquid may be used instead of water.
The value of the test pressure is determined in accordance with paragraphs 4.6.3 - 4.6.5 of NP-044-03.
The test pressure shall be controlled by two manometers. Pressure gauges must be of the same type, with the same accuracy class of at least 1.5, measurement limit and division value.
The pressure in the test vessel should be increased gradually. The total pressure rise time and the holding time of the vessel under test pressure should be specified in the manufacturer's instructions for installation and operation of the vessel.
If it is not possible to achieve the required test pressure with a machine-driven pump, the pressure increase must be carried out with a hand pump. Upon reaching the test pressure, the water supply to the vessel is stopped and the supply line is blocked by a shut-off body; after that for 10 min. there should be no pressure drop.
After exposure under test pressure, the pressure is reduced to the design pressure, at which the outer surface of the vessel, all its detachable and welded joints are inspected.
Tapping of the body walls, welded and detachable joints of the vessel during the tests is not allowed.
In the cases provided for in paragraph 4.6.17 of NP-044-03, it is allowed to replace the hydraulic test with a pneumatic one, provided that this test is controlled by the acoustic emission method. When conducting this test, the owner of the vessel, in addition to the measures provided for by NP-044-03, must develop and implement additional measures safety depending on local test conditions.
The results of a hydraulic test are considered satisfactory if it is not found:
If defects are detected by the inspecting person, depending on their nature, a decision may be made to prohibit the operation of the vessel, put it into temporary operation, reduce the period of the next survey, reduce operating parameters, etc.
After completion of all repair work (before applying protective coatings and insulation), steam boilers are subjected to a hydraulic test and a steam test in the presence of the Surveyor to the Register.
Hydraulic tests are carried out under the condition that the boiler is completely filled with water and air is removed, with two sealed pressure gauges and at a temperature of water and ambient air of at least + 5 C. At the same time, the temperature difference between water and ambient air should exclude the possibility of sweating.
During the test, the pressure should not increase rapidly, it is forbidden to perform work on the ship that causes noise or knocking.
The hydraulic test is carried out in the following order: raising the pressure to the working pressure, preliminary inspection at the working pressure, raising the pressure to the test pressure with a holding time (with the pump turned off) for 10 minutes, lowering the pressure to the working pressure and inspection.
If during the hydraulic test knocks are heard in the boiler or other abnormal phenomena are noticed, the tests are interrupted and after the release of water, the boiler is carefully inspected to determine the location and nature of the damage. After the defect is eliminated, the test is repeated.
The boiler is recognized as serviceable if during the inspection no leaks, residual deformations, ruptures of seams and other signs of violation of the integrity of any parts and connections are found.
The steam sample of the boiler is carried out in combination with fittings, equipment, service mechanisms and pipelines, at operating pressure. At the same time, it is necessary to make sure that the water-indicating devices (water-gauge glasses, test taps, remote water level indicators, etc.) are in good condition, as well as the upper and lower blowing of the boiler. They check the condition of the fittings, the operation of the drives, the absence of steam, water, fuel leaks in glands, flanges and other connections.
Safety valves are tested in operation for operation. They must be adjusted to the following opening pressures: P open. less than 1.05Рр (at Рр less than 1.0 MPa); R open more than 1.03Рр (when Рр is more than 1.0 MPa), where Рр is the working pressure.
The maximum allowable opening pressure of the valve must not exceed 1.1 Pp. The safety valves of superheaters must be adjusted to operate with some advance of the boiler valves.
Check the operation of manual actuators for undermining safety valves. If the results are positive, they will be sealed by the Register inspector.
The operation of automatic control systems of the military-industrial complex is checked: the reliability and timeliness of the operation of signaling, protective and blocking devices (when the water level in the boiler drops below the permissible level, the air supply to the furnace is interrupted, the torch in the furnace is extinguished and in other cases provided for by the automation system).
Check the operation of the military-industrial complex during the transition from automatic to manual control and vice versa.
After the end of the steam test and the elimination of the identified defects, they begin to insulate the boiler. The surfaces of the boiler to be insulated, as well as the frame and casing, are cleaned and painted with red lead or AL 177 paint.
The insulating material is soaked in hot water and applied to hot insulated surfaces with a layer of 10-30 mm. After the first layer has dried, a second layer is applied, and so on, until insulation is obtained. desired thickness. The thickness of the insulation depends on the temperature of the working medium (for boilers - 60-100 mm).
As an insulating material for ship boilers, asbestos fluff, asbestos cloth, asbestos cardboard, asbestos cord, diatomite (diatomaceous earth), asbozurite (a mixture of asbestos with diatomite), sovelit and newvel - a mixture of magnesia MgO and magnesium oxide hydrate Mg (OH) 2 with asbestos.
To save expensive insulating materials (soverite, newel), insulation is made up of different materials. For example, the first layer - 10 mm - is applied from fluff asbestos, the second - 40-50 mm thick - from sovelite or nuvel, the third - 10 mm thick - from asbozurite.
Insulating materials applied to the surfaces of the boilers are fastened with a metal mesh and covered with a sheathing of galvanized roofing iron. Overlay steel bandages. The boilers are also insulated with mattresses made of asbestos fabric filled with sovelite or nuvel. The mattresses are sewn together with brass wire, laid on the insulated parts of the boiler, fitted with bandages and covered with a metal casing.
The walls of the combustion chamber and gas ducts of water-tube boilers are sheathed with removable shields made of thin steel sheets insulated with asbestos cardboard (or other insulating material) with a thickness of at least 10 mm. Asbestos is attached to the shields with bolts, and the shields are attached to the boiler frame on the battens. All joints of the boiler casing are made on asbestos gaskets, which ensures the gas-tightness of the casing.
MINISTRY OF ENERGY AND ELECTRIFICATION OF THE USSRPRODUCTION ASSOCIATION FOR ADJUSTMENT, IMPROVEMENT OF TECHNOLOGY AND OPERATION OF POWER PLANTS AND NETWORKS "SOYUZTEKHENERGO" GUIDELINES FOR TESTING THE HYDRAULIC STABILITY OF DIRECT-FLOW POWER WATER
SOYUZTEKHENERGO
Moscow 1989 Content DEVELOPED by the Moscow head enterprise of the Production Association for the adjustment, improvement of technology and operation of power plants and networks "Soyuztekhenergo" PERFORMERS V.M. LEVINZON, I.M. GIPSHMAN APPROVED by "Soyuztechenergo" 05.04.88 Chief Engineer K.V. SHAHSUVAROV Expiry date set
from 01.01.89
until 01.01.94. These Guidelines apply to stationary once-through steam power boilers and hot water boilers with absolute pressure from 1.0 to 25.0 MPa (from 10 to 255 kgf / cm 2). Guidelines do not apply to boilers: with natural circulation; steam-heating; locomobile installations; waste heat boilers; energy technology, as well as other special-purpose boilers. Based on the experience gained in Soyuztekhenergo and related organizations, methods for testing boilers in stationary and transient modes are specified and described in detail in order to check the conditions hydraulic stability of steam-generating heating surfaces of once-through steam boilers or screen and convective heating surfaces of hot water boilers. Hydraulic stability tests are carried out both for newly created (head) boilers and for those in operation. The tests allow you to check the compliance of the hydraulic characteristics with the calculated ones, evaluate the influence of operational factors and determine the boundaries of hydraulic stability. technology and operation of power plants and networks", approved by Order of the Minister of Energy and Electrification of the USSR No.
313 dated 03.10.83. Methodological instructions can also be used by other commissioning organizations that perform tests of the hydraulic stability of once-through boilers.
Name |
Error |
steam boilers |
Hot water boilers |
Consumption and average mass velocity of the medium in the circuit, % | Temperature at the inlet and outlet of the circuit, °C | Temperature at the inlet and outlet of the circuit elements, °С | Subheating to boiling point, °С | Pressure at the inlet and outlet of the circuit, % | Pressure drop in the circuit (from inlet to outlet), % | Note. The flow rate of the medium in the elements of the contour, the increment of enthalpy, as well as the coefficients of thermal and hydraulic scanning and uneven heat absorption, are determined without accuracy rationing. The temperature of the metal in the heated zone is determined without accuracy standardization according to the guidelines for departmental full-scale tests of the temperature regime of the screen heating surfaces of steam and hot water boilers. |
Name |
Limit deviations, % |
Steam boilers with steam output, t/h |
Hot water boilers |
Steam output | Feed water consumption | Pressure | Superheated steam temperature (primary and intermediate) | Water temperature (boiler inlet and outlet) |
Name |
Quantity, pcs. |
Production of temperature inserts | Insertion of temperature inserts in LF and MF | Opening insulation on collectors and pipelines (NRCH, SRCH, VRC) |
25 plots |
Installation and welding of surface thermocouples | Switching of thermocouples and inserts to junction boxes (SK) | Installation SK-24 | Laying compensation cable KMTB -14 | Installation of pressure pipes (with drilling in supply pipes and LFC coils) | Pressure sampling unit | Installation for selection of signals on the kindling flow of feed water (from the standard diaphragm) | Laying of connecting (impulse) pipes | Installation of flow sensors | Manufacturing and installation of a shield for 20 devices | Installation of secondary devices (KSP, KSU, KSD) | Work space preparation | Technical inspection(revision) of standard measurement systems for the steam-water path | Shield lighting installation. |
Name |
Quantity, pcs. |
Differential pressure sensor DM, 0.4 kgf/cm2 (for 400 kg/cm2) | Pressure sensor MED 0-400 kgf/cm 2 | Differential pressure sensor DME, 0-250 kgf/cm2 (at 400 kgf/cm2) | Single-point KSD device | KSU single-point device | Device KSP-4, 0-600°, XA, 12-point | Compensation wire MK | Thermoelectrode wire XA | Glassstocking | Silica tape (glass) | Insulating tape | Charting strip for KSP, 0-600°, XA | Chart tape for KSU (KSD), 0-100%, | Batteries are flat | Batteries are round |
1. Experience 1. Set the following mode: power unit load - 290-300 MW, fuel - dust (without fuel oil illumination), excess air - 1.2 (3-3.5% oxygen), feed water temperature - 260 ° C , the 2nd and 3rd injections are in operation (30-40 t/h per flow). The rest of the parameters are maintained in accordance with the regime map and the current instructions. During the experiment, if possible, do not make any changes in the mode. All operating automation is in operation. The duration of the experiment is 2 hours. Experiment 1 a. The effect of the "Water-fuel" imbalance on the stability of the hydrodynamics is checked. Set the same mode as in experiment 1. Turn off the fuel regulator. Sharply reduce the feed water flow rate along the "A" stream by 80 t/h without changing the fuel consumption. After 10 minutes, in agreement with the Soyuztekhenergo representative, restore the initial water flow. During the experiment, temperature control along the boiler path should be carried out by injections. Permissible limits of short-term deviation of the temperature of live steam - 525-560 ° C (no more than 3 minutes), temperatures of the medium along the boiler path ± 50 ° C from the calculated ones (no more than 5 minutes, see clause 4 of this appendix). Duration of the experiment - 1 Part 2. Experience 2. Set the following mode: power unit load - 250-260 MW, fuel - dust (without fuel oil illumination), excess air - 1.2-1.25 (3.5-4% oxygen), temperature feed water - 240-245°C, the 2nd and 3rd injections are in operation (25-30 t/h per flow). The rest of the parameters are maintained in accordance with the regime map and the current instructions. During the experiment, if possible, do not make any changes in the mode. All operating automation is in operation. The duration of the experiment is 2 hours. Experiment 2a. The effect of skew on the burners is checked. Set the same mode as in experiment 2, but on 13 dust feeders (dust feeders No. 9,10,11 are turned off). The duration of the experiment is 1.5 hours. Experiment 2b. The effect of the imbalance "Water-fuel" is checked. Set the same mode as in experiment 2a. Turn off the fuel regulator. Dramatically reduce the feed water flow rate on stream "A" by 70 t/h without changing the fuel flow rate. After 10 minutes, in agreement with the Soyuztechenergo representative, restore the initial water flow. During the experiment, temperature control along the boiler path should be carried out by injection. Permissible limits of short-term deviation of the temperature of fresh steam 525-560°C (no more than 3 min), ambient temperatures along the boiler path ± 50°C from the calculated one (no more than 5 min, see clause 4 of this appendix). The duration of the experiment is 1 hour .3. Experiment 3. Set the following mode: power unit load 225-230 MW, fuel - dust (at least 13 dust feeders are in operation, without fuel oil illumination), excess air - 1.25 (4-4.5% oxygen), feed water temperature - 235-240°С, 2nd and 3rd injections are in operation (20-25 t/h per stream). The remaining parameters are maintained in accordance with the regime map and the current instructions. During the experiment, if possible, do not make any changes in the mode. All operating automation is in operation. The duration of the experiment is 2 hours. Experiment 3a. The influence of the imbalance "Water-fuel" and the inclusion of burners is checked. Set the same mode as in experiment 3. Increase the excess air to 1.4 (6-6.5% oxygen). Turn off the fuel regulator. Dramatically increase fuel consumption by increasing the speed of the dust feeders by 200-250 rpm without changing the water flow rate. After 10 minutes, in agreement with the representative of Soyuztechenergo, restore the original speed. Stabilize the regime. Dramatically increase fuel consumption by simultaneously turning on two dust feeders in the left semi-furnace without changing the water flow rate by flow. After 10 minutes, in agreement with the representative of Soyuztekhenergo, restore the initial fuel consumption. During the experiment, temperature control along the boiler path is carried out by injections. Permissible limits of short-term deviation of the overheating temperature - 525-560°C (no more than 3 minutes), ambient temperatures along the boiler path ± 50°C from the calculated ones (no more than 5 minutes, see clause 4 of this appendix). Duration of the experiment - 2 hours Notes: 1. The CTC assigns a responsible representative for each experience. 2. All operational actions during the experiment are carried out by the shift personnel at the direction (or with the knowledge and agreement) of the responsible representative of Soyuztechenergo. 3. In case of occurrence emergencies the experiment is terminated, and the watch personnel act in accordance with the relevant instructions. 4. Limiting short-term temperatures of the medium along the boiler path, ° С: behind SRF-P 470 to VZ 500 behind screens - I 530 behind screens - II 570. Signature: _________________________________________________ (test manager from Soyuztekhenergo) Agreed: _____________________________________________ (heads of GRES workshops)
kayabaparts.ru - Entrance hall, kitchen, living room. Garden. Chairs. Bedroom