The act of a comprehensive inspection of fire alarms. Comprehensive testing of apz systems

(the form)
City _______________" "______19____
An object _________________________________________________________________________
Working committee consisting of:
chairman-representative of the customer (general contractor)

(position, full name)

(position, full name)

(position, full name)
state fire supervision ________________________________________________

(position, full name)

________________________________________________________________________________
inspected the installation

(Name)
assembled according to the project

________________________________________________________________________________

(notation

________________________________________________________________________________

project and the full name of the design organization)
It was found by inspection that the

________________________________________________________________________________

(Name)
fully assembled in accordance with the project and the "Rules for the production and acceptance of work. Automatic fire extinguishing installations." To check the operability of the installed installation, the commission carried out a comprehensive test _________________________________________________________________________________

(name of protected premises,

________________________________________________________________________________

plant sections tested)

________________________________________________________________________________

________________________________________________________________________________
Artificial fires size ______________________________________________

________________________________________________________________________________
with combustible material ____________________________________________________________
were installed in ______________________________________________________________

(places of installation of fire seats)

________________________________________________________________________________

________________________________________________________________________________
As a result of the test, it was found


Section

Protect-

room


Time arose

fire source,

h-min


Opening time

clair sprinkler (notice-

h-min


The time of appearance of water (foam, gas),

h-min


Complete extinguishment of the fire

h-min


Note-

chanting

Representatives:
customer ________________________________________________________________

(signature)
installation organization ___________________________________________________

(signature)
state fire supervision ______________________________________________

(signature)

APPENDIX 29
ACT

INSTALLATION ACCEPTANCE IN OPERATION

(the form)
City ____________" "_______________19____
Commission appointed by ___________________________________________________________

________________________________________________________________________________

(name of the customer organization)
decision of "____" ______ 19___, No. _____, consisting of:
chairman - representative of the customer (general contractor)

________________________________________________________________________________

(position, full name)
Commission members - representatives:
installation organization _______________________________________________________________

(position, full name)

________________________________________________________________________________
commissioning organization _____________________________________________________

(position, full name)

________________________________________________________________________________
state fire supervision ________________________________________________

(position,

________________________________________________________________________________

f. and. about.)
checked the work done and found:
1. The assembly and commissioning (commissioning) organization presented the installation for acceptance

________________________________________________________________________________

(installation name)
mounted in ________________________________________________________________

(Object name)
according to the project developed by _____________________________________________________________

(name of company)
2. Installation work completed

________________________________________________________________________________

(name of company)
from "____" _____________ 19___ to "____" ____________ 19___


Thousand rub.
3. Commissioning completed

_______________________________________________________________

(name of commissioning organization)
from "____" ____________ 19___ to "____" ____________ 19___
Estimated cost commissioning

Thousand rub.
Actual cost of commissioning

Thousand rub.
4. The defects and shortcomings identified during the complex testing have been eliminated (if necessary, indicate in the appendix to this act).

Commission conclusion

An installation that has passed a comprehensive testing, including commissioning, is considered accepted for operation from "_____" __________ 19___ with an assessment of the quality of the work performed

________________________________________________________________________________

(excellent, good, satisfactory)
List of documents attached to the act:

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________
Commission:
Chairman of the Commission _______________________________________________________________

(signature)
M.P.
members of the commission _________________________________________________________________

(signature)

________________________________________________________________________________
APPENDIX 30
PRODUCTION DOCUMENTATION ISSUED DURING THE INSTALLATION OF FIRE ALARM EQUIPMENT

During the installation of technical means of signaling, the production documentation given in the table should be drawn up, and upon their delivery - handed over to the working commission (with the exception of paragraphs 2, 3).


Document

Document content

Note

1. Survey report

Name of the object, number of buildings, rooms, number of floors, type of building, indication of the type of detectors, receiving- control devices, annunciators and their installation locations for each building (premises); indication of the length, types of wire laying and their protection; power supply instruction estimated cost and the planned installation time; signatures of representatives of the customer, state fire supervision authorities

Attached to the act is an estimate for installation and commissioning, a plan-scheme of the facility. The act is drawn up in the absence of a project

2. The act of transferring equipment, products and materials for installation



3. The act of readiness of buildings, structures for production installation work


According to the form of application 11

4. Certificate of examination-

niya hidden works (during installation electrical wiring)


Compiled for work performed in walls, ceilings, floors, ground, sewers

According to the form of application 21

5. Certificate of conduct input control

Name, type and brand, serial number or product marking, manufacturer, date of manufacture and receipt; conclusion on readiness; signature of the responsible representative of the organization that performed the input control


6. Cable warm-up protocol on drums

drum number; cable brand, number of cores and cross section (mm); cable length (m); temperature at the beginning and end of heating (°C); voltage (V); current (A); air temperature at the place of cable laying (°С); date of completion of laying works; signatures of representatives of the customer, installation organization

Compiled in the case when the cable is installed at negative temperatures (according to the form of Appendix 20)

7. The act of testing protective pipelines with separating seals for tightness

Number pipe wiring; nominal diameter (mm); test pressure(kPa), holding time (h); pressure drop (% in h); allowable pressure value (kPa); conclusion on the suitability of pipelines for operation, indicating the class of the explosive zone. Signatures of the customer's representatives to the installation organization

It is drawn up during the installation of technical means of signaling in explosive zones (according to the form of Appendix 22)

8. Protocol for measuring the insulation resistance of electrical wiring

Name and item number according to working drawings; data of control devices; test data: brand of wire (cable), number and cross-section of cores, insulation resistance. Test Conclusion. Signatures of representatives of the customer, installation organization

According to the form of application 19

9. Certificate of completion of installation work

The name of the installed signaling means, the name of the object, the organization-developer of the project (inspection report); installation organization; the period of performance of work, the result of the audit, the conclusion of the commission; signatures of representatives of the customer, installation and commissioning organization

Compiled (according to the form of Appendix 12) in the event that the installation organization performed only the installation. A list of mounted control panels (PPU) and detectors is attached to the act

10. Certificate of completion of commissioning

The period of commissioning, the name of the installed alarm complex; date and number of the contract; list of work performed, conclusion of the commission; signatures of representatives of the customer and commissioning organization

According to the application form 24

11. List of mounted control panels (PPU) and detectors

Name of the object, installed signaling means, position number of the project specification, name, type, manufacturer, quantity; signatures of representatives of the installation and commissioning organization and the customer

APPENDIX 31
DOCUMENTATION ISSUED WHEN DEFECTS ARE DETECTED IN SIGNALING TECHNICAL MEANS

APPENDIX 32

DOCUMENTATION TO BE MADE UPON ACCEPTANCE OF SIGNALING TECHNICAL MEANS FOR OPERATION

When accepting and putting technical means of signaling into operation working commission the documentation shown in the table must be drawn up.


Document

Document content

Note

System acceptance certificate fire alarm into operation

The name of the installed signaling facilities of the facility, the organization that developed the project; name of the installation organization, period of performance of work, estimated and actual cost of installation work; name of the commissioning organization; period of work performance, estimated and actual cost of commissioning; results of measurements of the insulation resistance of the alarm loop and the resistance of the alarm loop; the result of testing the operability of technical means; conclusion of the commission, signatures of representatives of the customer, installation, commissioning organization, state fire supervision authorities

APPENDIX 33

MAGAZINE

FAULT RECORDING OF FIRE AUTOMATIC INSTALLATION

Type of instalation ___________________________________________________________________
Date of installation of the unit __________________________________________________________
Protected object ______________________________________________________________

________________________________________________________________________________


No. p / p

Date and time of failure of the element or its component part

Character-

nye external manifestations

troubleshooting

news


Cause of malfunction

(failure), the number of hours of operation of the failed element


Taking measures to eliminate

fault

equipment, spare parts consumption


Signature eliminated

faulty

ness


Note

APPENDIX 34
ACT

PRIMARY SURVEY OF AUTOMATIC FIRE EXTINGUISHING INSTALLATIONS, FIRE ALARMS

(the form)
g.________________________ "____"______19___
We, the undersigned:
customer representative

________________________________________________________________________________

(name of the enterprise, organization, institution)
represented by ________________________________________________________________________


on the one hand, and
performer's representative

________________________________________________________________________________

(position, surname, initials)
on the other hand, drew up this act in that, when examining installations

________________________________________________________________________________

________________________________________________________________________________
________________________________________________________________________________

(list settings)

________________________________________________________________________________
mounted _________________________________________________________________

(name of the installation organization,

________________________________________________________________________________

installation date)
for the project completed by _______________________________________________________________

________________________________________________________________________________

(name of design organization,

________________________________________________________________________________

project number and release date)
well-established ___________________________________________________________________________

________________________________________________________________________________

(name of the commissioning organization, commissioning date)
installed:
technical condition of installations _________________________________________________

________________________________________________________________________________

(specify faults)

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________
design and technical documentation, acts

________________________________________________________________________________

(indicate the missing documentation, give comments on the existing one)

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________
Conclusions, proposals ____________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

Representative of the GPN bodies ____________________________________________________________
Chairman of the installation and commissioning organization

________________________________________________________________________________

APPENDIX 35
ACT

The formation of the act must be treated very carefully, trying not to make mistakes, inaccuracies, and even more so not to enter unverified or deliberately false data into the document, because. they can subsequently lead to severe penalties from supervisory authorities. What to look for when drawing up In determining the legality of a document, how exactly the act is drawn up is practically irrelevant. It may be written in letterhead or on a regular sheet of any convenient format, typed on a computer or compiled in handwritten form. It is only necessary to make sure that the act includes the "live" signatures of responsible persons - at the same time, in this case, the use of facsimile autographs, i.e. printed in any way is prohibited.

Comprehensive test program for fire protection systems

It is drawn up by a separate act, since often the internal fire water supply system is combined with the water supply system, in addition to the fire extinguishing installation.

  • List of installed equipment. Similar to the acceptance certificate, it is possible to draw up one statement for all fire-fighting automation installations.
  • Passports and technical documentation (labels, operating instructions, etc.) for all system equipment.
  • Certificates of conformity and fire safety for materials and equipment (pipelines, valves, pumping equipment, cables and wires, control equipment, etc.).
  • Program complex tests systems fire protection- is a step-by-step protocol for testing the interaction of all systems. Free form and approved responsible person installation organization.

(((data.title)))

The general meaning is: worked smoke detector- the siren howled - the fire warning system went off - the ventilation turned off - all the elevators went down to the first floor and so on. The program should include tests for all types of fire detectors (manual, smoke, heat), as well as for triggering sprinklers or opening fire hydrants (manual opening of deluge curtains). For each test, describe the complete sequence of events that occur.

  • The act of checking the performance of the fire alarm.
    Confirms that tests have been carried out according to the program described above.
  • The act of testing (checking the performance) of the installation automatic fire extinguishing. Confirms visual inspection and testing of the AUPT system.

Fire alarm test report

Filling in the header of the act In the "header", in particular, you should always indicate:

  • name of the document, place and date of its compilation;
  • the commission that conducted the fire alarm check - you can limit yourself to the names of organizations, but if necessary, you should enter the positions, first names, last names, patronymics of specific employees participating in control measures.

Filling out the main part of the act In the main part you need:

  • certify the fact of the inspection;
  • write the name of the organization - the owner of the fire alarm and the address at which it is installed;
  • provide a link to the contract in accordance with which verification work is carried out.

If desired, other information can be entered in the act (for example, describe in more detail the data on the fire alarm, the results of its examination).

The act of checking the performance of the fire alarm

  • serial number of the fire cabinet;
  • fire brigade telephone;
  • in the absence of viewing windows, an inventory of the contents of the cabinet;
  • seal with the seal of the service organization and the signature of the responsible person.

Requirements for other fire protection systems will be published later. If you have comments, you have found inaccuracies, outdated information or its absence, please comment. The article will be updated based on your comments and new incoming information.

POZHPROEKT.RU Program of final complex testsFederal state budgetary educational institution higher vocational education Moscow State...
Must include all changes from the original design included in the system during installation. All sheets of the project must be signed by responsible persons (executive designer, Chief Engineer project, director, etc.) and have the stamps "Works performed in accordance with the project."

  • Approved estimate documentation on work performed. It must also be approved by the Contractor and the Owner.
  • Acceptance and test certificates
  1. The act of acceptance of technical means into operation.
    If several systems are rented at the same time, it is allowed to draw up one act for all systems.
  2. The act of acceptance into operation of the internal fire water supply.

Act for a comprehensive test of the aps system

The role of fire alarms cannot be overestimated - with a serious load on Electricity of the net who very often experience communication ( a large number of devices switched on at the same time, bright lights, etc.), sounding an alarm in time can prevent the most serious consequences. That is why the conditions for the installation and maintenance of fire systems, including fire alarms, are regulated by law and must be strictly enforced. Who can install and maintain a fire alarm Not everyone is allowed to install and maintain fire alarms.

Only special licensed organizations whose employees have undergone professional training have a permit.
Joint Stock Company "Mobile TeleSystems" Offers for the right to conclude an agreement for the installation of fire protection systems ( automatic installation gas ... Instructions for the maintenance of technical means of fire protectionThis Instruction is developed in addition to the General Facility Instruction and establishes uniform requirements on the content of technical… Topic №1 Organization of fire protection in a military unit.
Events… Lecture topic: accounting systemsThis means that manufacturers are no longer focused on the development of individual components of automation of control systems, but on the creation of… Terms of Reference for the supply, implementation and optimization of complex……
Form and sample of the inspection report Installation of a fire alarm must be carried out by specialists in compliance with all fire safety standards, state standards and regulations, and before starting work, the equipment must pass an input control. However, is the installation of a fire alarm a guarantee that in the event of an emergency, in this case a fire, alarm system will it work on time and allow to protect the health of personnel and material resources of the enterprise? It is possible to answer this question in the affirmative only when the equipment is in good condition. That is, it is necessary to constantly monitor its performance, and it is important not to confuse this procedure with the maintenance of this equipment.

  • Each fire extinguishing section should have a sign indicating the operating pressures, the name of the protected premises, the type and number of sprinklers in the section, the position (state) stop valves in standby mode.
  • room pumping station must be equipped with a telephone connection with the post-control room.
  • On all pipelines in the pumping station room, the direction of movement of the fire extinguishing agent must be indicated.
  • All pressure gauges must be marked with the operating pressure range of the system.
  • At the entrance to the premises of the pumping station, a sign "Fire extinguishing station" should be posted and a light board with a similar inscription should be constantly functioning.
  • All fire cabinets must be numbered, there must be stickers on the cabinet with information:
  • fire safety signs "fire hydrant" and "fire extinguisher" in accordance with paragraph.

For written confirmation of such inspections, an appropriate fire alarm inspection certificate is drawn up, in which it is required to indicate the date of the inspection, the state of the fire alarm systems, whether there are malfunctions or not, indicate the state of such systems. The act is signed by all persons conducting such an audit, and endorsed by the head of the audited enterprise, which proves his awareness of the audit. Violations identified during the procedure are subject to prompt elimination by the company responsible for this. The verification date is fixed in special magazine accounting for such actions. According to Russian law, such checks should be carried out once every three months.

Fire alarm test certificate sample form

The role of fire alarms cannot be overestimated - with a serious load on electrical networks, which very often experience communications (a large number of devices turned on at the same time, bright lighting, etc.), a timely alarm can prevent the most serious consequences. That is why the conditions for the installation and maintenance of fire systems, including fire alarms, are regulated by law and must be strictly enforced. Who can install and maintain a fire alarm Not everyone is allowed to install and maintain fire alarms.

Only special licensed organizations whose employees have undergone professional training have a permit.

Fire alarm test report

  • serial number of the fire cabinet;
  • fire brigade telephone;
  • in the absence of viewing windows, an inventory of the contents of the cabinet;
  • seal with the seal of the service organization and the signature of the responsible person.
  1. All fire cabinets must be numbered, there must be stickers on the cabinet with information:

Requirements for other fire protection systems will be published later. If you have comments, you have found inaccuracies, outdated information or its absence, please comment. The article will be updated based on your comments and new incoming information.

POZHPROEKT.RU The program of the final comprehensive testsFederal State Budgetary Educational Institution of Higher Professional Education "Moscow State…

The act of checking the performance of the fire alarm

Must include all changes from the original design included in the system during installation. All sheets of the project must be signed by responsible persons (executive designer, chief engineer of the project, director, etc.) and have the stamps "Works performed in accordance with the project."

  • Approved estimate documentation for the work performed. It must also be approved by the Contractor and the Owner.
  • Acceptance and test certificates
  1. The act of acceptance of technical means into operation.
    If several systems are rented at the same time, it is allowed to draw up one act for all systems.
  2. The act of acceptance into operation of the internal fire water supply.

In the application, it is necessary to have the terms of reference for the installation of foundations, developed by the organization - the designer of the fire protection system.

  • The act of heating cables on drums - is drawn up in the case of installation of cable routes in conditions low temperatures with cable heating on drums.
  • The test report for the tightness of the separating seals of protective pipelines for electrical wiring in hazardous areas is drawn up only when laying cable routes in hazardous areas. The test is carried out by air pressure
  • Hydropneumatic capacity test report
  • Passport for charging cylinders of the installation gas fire extinguishing
  • Instructions and diagrams
  1. Fire alarm installation operating manual.

Fire alarm test report

It fixes:

  • the very fact of verification;
  • instrument status;
  • identified breakdowns, deficiencies and other defects.

During the verification process, the degree of deterioration of the fire alarm system, the risks during its further operation are also assessed, and measures are proposed to eliminate shortcomings with the setting of specific deadlines. The act is a very important document, it indicates that fire alarm maintenance work is carried out in a timely manner and in full. Also, its presence allows, in case of inspections by employees of supervisory departments, to avoid possible penalties.

(((data.title)))

Attention

At the same time, even at the stage of putting the building into operation, the fire alarm system must pass an “exam” from the State Fire Control, and subsequently all actions with these devices must be carried out in compliance with certain requirements and standards. Carrying out checks Checking the installed fire alarm system should be carried out with a certain frequency. At this event, at least two parties must be present: a representative of the organization serving this object, and an employee of the enterprise in whose possession the building or room with a fire alarm is located.


If necessary, the composition of the commission can be expanded by third-party experts. Why do we need an act of verification Every time test papers must be accompanied by an appropriate act.

Comprehensive test program for fire protection systems

  • The act of complex testing of technical means of automatic fire protection. If, according to the test program, several interacting systems are tested (for example, automatic fire alarms, fire warning people and a powder fire extinguishing installation), then one general test report should be issued. Questions and mechanics of the interaction of systems are set out in the test program.
  • The act of carrying out the input control - indicates that technical means listed in it, as well as in the list of installed equipment (the list should usually match), correspond to the regulatory documentation and documentation of manufacturers.
  • Insulation resistance measurement report - one report can be issued for all loops of the APS and SOiUE system.
  • The act of examination of hidden works - everything is clear with this.

The act of a comprehensive check of the fire alarm

It is drawn up by a separate act, since often the internal fire water supply system is combined with the water supply system, in addition to the fire extinguishing installation.

  • List of installed equipment. Similar to the acceptance certificate, it is possible to draw up one statement for all fire-fighting automation installations.
  • Passports and technical documentation (labels, operating instructions, etc.) for all system equipment.
  • Certificates of conformity and fire safety for materials and equipment (pipelines, valves, pumping equipment, cables and wires, control equipment, etc.).
  • The program of complex tests of fire protection systems is a step-by-step protocol for testing the interaction of all systems. It is drawn up in a free form and approved by the responsible person of the installation organization.

Any devices installed to ensure the safety of the enterprise are subject to periodic checks - this rule has become an axiom. The most common category of such equipment is an automatic fire alarm (APS), without which no enterprise can do today.

Principles of operation of automatic fire alarms

The main principles of APS work are:

  1. Fire detection at an early stage
  2. Launch of people warning systems
  3. Activation of evacuation control systems
  4. launch ventilation system
  5. Turning on automatic fire extinguishing systems

Early detection of the source of fire and well-conducted timely evacuation will help to avoid casualties among the people in the building. Starting the ventilation system is necessary to create overpressure, which will prevent smoke from entering the evacuation paths - halls and stairwells.

If there are elevators in the building, then the APS returns them to the first floor, where they remain with open doors. In the event of a fire, the evacuation of people in elevators is prohibited due to the threat of smoke in the elevator shaft, and the personnel must leave the building using the stairs.

Systems used to eliminate fires are divided into several groups:

  1. Water or water-foam
  2. Powder
  3. Gas

The systems of the first group are the most common, and devices from the other two are used when it is impossible to use water, for example, in electrical substations or museums where valuable exhibits are stored that will suffer from water: documents, books, paintings, works of art and other items.

Form and sample of the inspection report

Installation of fire alarms must be carried out by specialists in compliance with all fire safety standards, GOSTs and regulations, and before starting work, the equipment must pass an input control.

However, is the installation of a fire alarm a guarantee that in the event of an emergency, in this case a fire, the alarm system will work on time and will save the health of personnel and material resources of the enterprise?

It is possible to answer this question in the affirmative only when the equipment is in good condition. That is, it is necessary to constantly monitor its performance, and it is important not to confuse this procedure with the maintenance of this equipment. Checking the performance of the fire alarm is carried out by the employees of the enterprise, and for its maintenance it is necessary to involve contractors - representatives of companies with a special license, since this service is subject to federal law About Licensing certain types activities".

Each of these procedures has its own rules and frequency. The results of maintenance are recorded in the registration log, and the control ends with the preparation of a special document - an act of checking the performance of fire safety equipment for buildings and structures.

The form of this document is defined in Appendix No. 19 to the Order of the Ministry of Emergency Situations of the Russian Federation No. 292 dated May 28, 2012. The act indicates the address of the object being checked, type installed system, a list of work performed, the timing of the inspection and the final conclusion on the condition of the equipment. document in without fail signed by officials and certified by a seal.

Periodicity of registration of the act and responsible persons

In the procedure for drawing up an act based on the results of a performance check fire alarm a representative of the enterprise (organization) who is responsible for the implementation of measures for the fire safety of the object (enterprise, organization) takes part without fail.

The head of the enterprise is obliged to publish - it can be himself or any employee. In any case, the person specified in the order must undergo a special fire-fighting minimum training course with the issuance of an appropriate certificate.

The duties of the head of the enterprise include ensuring compliance with fire safety requirements and fulfilling the requirements of supervisory authorities, including those set out in resolutions, instructions and other documents, carrying out fire prevention promotional activities, introducing clauses into the collective agreement that affect the safety of the work process, including and fire, as well as monitoring the serviceability of all protective equipment and fire extinguishing and preventing their use for purposes that do not meet their intended purpose. These are only the main tasks, the solution of which must be ensured by the head responsible for the safety of personnel and material assets.

The inspection should also include a representative of the contractor company, with whom a contract has been concluded for the maintenance of alarms installed at the facility. As such a contractor can be selected entity or individual entrepreneur having required license to carry out this kind of work. This requirement is prioritized as an unlicensed contractor is not authorized to perform these inspections.

It would not be superfluous to invite an inspector of the State Fire Supervision to such an event, which is especially important if this alarm was not previously subject to verification. Although the inspector of this organization is not required to attend such an event, contacting him will help to establish good relations with the State Fire Supervision Service. And since you will have to cooperate with the inspector in the future, good relations will not hurt.

According to the requirements of the legislation, such an audit should be carried out at least once a quarter.

In addition, inspections of enterprises by representatives of the State Fire Supervision Authority are possible. Representatives of this structure will definitely ask about the existence of an agreement for Maintenance APS with a licensed contractor. The frequency of scheduled inspections of the alarm system by the contractor is one month. During this event, the health of the system is assessed and the necessary measurements are made. If problems are found, they will be fixed free of charge.

Inspectors of the State Fire Supervision Authority will pay attention not only to the operability of the fire alarm, but also to the condition of the evacuation routes, the presence of signs in case of emergency evacuation, the absence or incorrect installation of fire extinguishers, checking their pressure gauges and the date of refueling.

In order to avoid instructions and complaints from the fire control authorities, it is necessary to correctly draw up documents on the regular maintenance of fire alarm equipment, as well as have developed and approved special instructions on fire safety.

(Size: 38.0 KiB | Downloads: 6,118)

Commissioning of fire protection systems

Finally, the work on the design and installation of automatic fire extinguishing, fire alarm and fire warning systems has been completed, it's time to put the system into operation for the Customer. The rules for handing over systems change frequently. Until recently, the acceptance committee included a specialist from the UGPN, now his place is taken by an employee of the GASN, but this change is of no fundamental importance. The requirements remain the same. So, for the successful delivery of the installation, it is necessary to prepare the following documents:


  1. Licenses, SRO permits. With this, everything is clear. Installation of fire protection installations is a licensed activity. Additionally, instead of licenses for construction works now the approvals of self-regulatory organizations are used.
Design and estimate documentation

  1. Executive project documentation across all systems. Must include all changes from the original design included in the system during installation. All sheets of the project must be signed by responsible persons (executive designer, chief engineer of the project, director, etc.) and have the stamps "Works performed in accordance with the project."

  2. Approved estimate documentation for the work performed. It must also be approved by the Contractor and the Owner.
Acceptance and test certificates

  1. The act of acceptance of technical means into operation. If several systems are rented at the same time, it is allowed to draw up one act for all systems.

  2. The act of acceptance into operation of the internal fire water supply. It is drawn up by a separate act, since often the internal fire water supply system is combined with the water supply system, in addition to the fire extinguishing installation.

  3. List of installed equipment. Similar to the acceptance certificate, it is possible to draw up one statement for all fire-fighting automation installations.

  4. Passports and technical documentation(labels, operating instructions, etc.) for all system equipment.

  5. Certificates of conformity and fire safety for materials and equipment (pipelines, valves, pumping equipment, cables and wires, control equipment, etc.).

  6. Comprehensive test program for fire protection systems- is a step-by-step protocol for testing the interaction of all systems. It is drawn up in free form and approved by the responsible person of the installation organization. The general meaning is as follows: the smoke detector worked - the siren howled - the fire warning system worked - the ventilation turned off - all the elevators went down to the first floor and so on. The program should include tests for all types of fire detectors (manual, smoke, heat), as well as for triggering sprinklers or opening fire hydrants (manual opening of deluge curtains). For each test, describe the complete sequence of events that occur.

  7. The act of checking the performance of the fire alarm. Confirms that tests have been carried out according to the program described above.

  8. The act of testing (checking the performance) of the automatic fire extinguishing installation. Confirms external inspection and testing of the AUPT system. For water fire extinguishing - confirms the compliance of the actual consumption of the fire extinguishing agent with the design and, accordingly, the normative.

  9. The act of complex testing of technical means of automatic fire protection. If, according to the test program, several interacting systems are tested (for example, automatic fire alarms, fire warning people and a powder fire extinguishing installation), then one general test report should be issued. Questions and mechanics of the interaction of systems are set out in the test program.

  10. Act of input control- indicates that the technical means listed in it, as well as in the list of installed equipment (the list should usually match), correspond to the regulatory documentation and documentation of manufacturers.

  11. The act of measuring the insulation resistance- you can issue one act for all loops of the APS and SOiUE system.

  12. Certificate of inspection of hidden works- with this everything is clear. All wires and pipes that cannot be seen with the naked eye and touched with the naked hand must be examined. The fact that they are not visible, but they are.

  13. Certificate of completion of installation works. Compiled by the installation company.

  14. Certificate of completion of commissioning Compiled by the commissioning organization.

  15. Act hydraulic test pipelines of the fire extinguishing installation. In the case of the delivery of an automatic water fire extinguishing system.

  16. The act of testing units idle or under load. Again, in the case of the delivery of a water fire extinguishing system. Evidence of testing of mounted pumping units (main fire pump, backup fire pump, jockey pump, compressor unit, etc.).

  17. The act of transferring equipment, products and materials for installation- an intermediate act, not required to be presented to the acceptance committee, but it is recommended to have it available.

  18. The act of readiness of buildings, structures for the production of installation work- an intermediate act, similar to the previous act, the presentation of the act is not mandatory.

  19. The act of readiness of trenches for laying pipelines (cables).

  20. Reinforcement test report

  21. Act on detected defects of devices, equipment and assemblies.

  22. Foundation Readiness Act- compiled during the installation of equipment (pumping units, compressor units, impulse device) on prepared foundations. In the application, it is necessary to have the terms of reference for the installation of foundations, developed by the organization - the designer of the fire protection system.

  23. The act of heating cables on drums- compiled in the case of installation of cable routes at low temperatures with cable heating on drums.

  24. Leak test protocol for separating seals of protective conduits for electrical installations in hazardous areas- compiled only when laying cable routes in hazardous areas. The test is carried out by air pressure

  25. Hydropneumatic capacity test report

  26. Passport for charging cylinders of a gas fire extinguishing installation
Instructions and diagrams

  1. Fire alarm installation operating instructions. It is located in the staff room on duty, not far from the fire alarm control panels.

  2. Operating instructions for automatic fire extinguishing installation. It is located in the staff room. In case of delivery of the water fire extinguishing system - also in the pumping station room.

  3. Functional diagrams for tying control nodes water (foam, gas) fire extinguishing systems are hung out at each control unit. A plate is posted in each direction indicating the operating pressures of the system, the names of the protected premises, the type and number of sprinklers (gas fire extinguishing nozzles) in each section (direction), the position (state) of the locking elements in standby mode.

  4. Station piping scheme water (foam, gas) fire extinguishing systems. Located in the station building.

  5. circuit diagram installations of water (foam, gas) fire extinguishing. It is also located in the station building.
Service Organization Documentation

  1. Regulations for the maintenance of fire protection systems. Compiled in agreement with the Customer.

  2. Maintenance contract fire protection systems.

  3. Schedules maintenance and scheduled preventive maintenance of fire alarm installations, automatic fire extinguishing, etc.

  4. Work logs for maintenance and scheduled preventive maintenance of fire protection installations.

  5. Fault logs.

  6. Cylinder weighing log with extinguishing agent for gas fire extinguishing installations.

  7. Job Descriptions duty personnel responsible for maintenance and preventive maintenance and service personnel.
In addition to having the above documentation, normative documents A certain set of requirements for fire protection installations is presented:

General requirements


  1. The post-control room or the room with personnel on duty around the clock should, as a rule, be located on the first or ground floor building. It is allowed to place the specified room above the first floor, while the exit from it must be in the lobby or corridor adjacent to stairwell with direct access to the outside of the building.

  2. The room of the post-control room or the room with personnel on duty around the clock should have the following characteristics:

  • the area, as a rule, is not less than 15 m2;

  • air temperature within 18–25°С at relative humidity not more than 80%;

  • presence of natural and artificial lighting, as well as emergency lighting, which must comply with the requirements of SNiP 23.05-95;

  • the presence of natural or artificial ventilation in accordance with SNiP 2.04.05-91;

  • availability of telephone communication with the fire department of the object or settlement.

  • batteries should not be installed in these rooms backup power except for sealed ones.

  1. The control room must be provided with direct telephone communication with the fire extinguishing station, emergency warning zones, city telephone communication, serviceable electric lights in the amount of at least 3 pieces, as well as personal protective equipment.

  2. Instructions for the use of fire protection installations, instructions on the actions of duty personnel in case of receipt of signals about the operation of installations, and job descriptions should be posted in the control room.
Fire (security and fire) alarm system

  1. The facility must have a reserve stock of fire detectors of each type to replace faulty or expired ones in an amount of at least 10% of the installed ones.

  2. Control and reception devices must have a capacity margin for loops of at least 10%.
Water (foam) fire extinguishing system

  1. The room of the fire extinguishing pumping station must have emergency lighting.

  2. All premises where the equipment of the fire extinguishing system is located (pumping station, premises of automatic water feeders, control units, etc.) must be permanently closed. Sets of keys to these premises should be kept by the service organization and the operational duty officer at the facility. Placement of personnel workplaces in these premises is not allowed.

  3. The facility must have a constant supply of sprinklers in the amount of 10% of the installed ones.

  4. In case of use foam fire extinguishing, the facility must have a 100% reserve stock of foam concentrate.

  5. Each control node must have a functional diagram strapping.

  6. Piping diagrams should be posted in the pumping station pumping equipment and circuit diagram fire extinguishing installations.

  7. Each fire extinguishing section should have a sign indicating the operating pressures, the name of the protected premises, the type and number of sprinklers in the section, the position (state) of the shut-off valves in standby mode.

  8. The room of the pumping station must be equipped with a telephone connection with the control room.

  9. On all pipelines in the pumping station room, the direction of movement of the fire extinguishing agent must be indicated.

  10. All pressure gauges must be marked with the operating pressure range of the system.

  11. At the entrance to the premises of the pumping station, a sign "Fire extinguishing station" should be posted and a light board with a similar inscription should be constantly functioning.


  • fire safety signs "fire hydrant" and "fire extinguisher" in accordance with clauses 15 and 16 of Table 2 of NPB 160-97;

  • serial number of the fire cabinet;

  • fire brigade telephone;

  • in the absence of viewing windows, an inventory of the contents of the cabinet;

  • seal with the seal of the service organization and the signature of the responsible person.

  1. All fire cabinets must be numbered, there must be stickers on the cabinet with information:
Requirements for other fire protection systems will be published later.