Helpful information. How the heating meter works: the principle of operation and types of heat meters

Ph.D. I.P. Andreev, Doctoral student of the Samara State Technical University, director of CJSC "Tochenergo", Togliatti

The article discusses typical ways distortion of meter readings and methods of dealing with them.

One of the main federal problems of accounting and saving natural and energy resources (PER) during their extraction, transportation, processing, storage, sale and use is the distortion of accounting for PER and their losses, especially in monetary terms. The problem of accounting for PER losses has a number of negative organizational and methodological features hidden from the general public, which are not characteristic of civilized accounting systems.

There is a widespread unpunished practice of material incentives for employees to receive income ("savings") by fraudulently unauthorized distortion of meter readings.

Consider the typical ways of distorting meter readings and methods of dealing with it.

1 . Use of hydrodynamic factors to change instrument readings

One of the most affordable ways to change instrument readings using improvised plumbing tools is to change the velocity diagram and flow swirl using a non-standard sealing gasket installed between the straight section at the flow inlet to the sensor and the sensor itself.

The designs and materials of gaskets can be very different. It is possible to reduce the inner diameter of the gasket and even make screw threads with swirling flow. If the gasket is soft, starts to vibrate and cause flow pulsations, then theoretically this can reduce the effect, because. flow pulsations lead, for example, to overestimation of turbine meters. If the gasket is internally threaded and is a flow swirl but not properly designed, this will cause additional pressure drop and possible noise in the piping. A flow swirler can also be installed in front of a straight section along the flow, especially if, according to the recommendation of the manufacturer of the device, a small length of the section is allowed (3 ... 5 nominal diameters).

Dirty filters, dirty internal surfaces pipelines and partially open gate valves (cranes) installed near the flow sensor also cause changes in the velocity diagram and lead to errors. There is a known case when, due to partial clogging of the inlet filter, the readings of the heat meter in one of the Moscow hotels were underestimated by 30%.

Another case was registered by the author at one of the fruit and vegetable bases, where a partial overlap of the inlet valve in front of the heat meter in warm weather systematically led to an underestimation of the flow rate by about an order of magnitude. Increasing the flow rate to the lower limit of the operating range, on the contrary, led to the restoration of reliable readings. However, it has not been determined exactly whether the underestimation of readings is related to the velocity diagram or the sensitivity threshold of the flow measurement channel.

Air flow with centrifugal pump installed in the line, or an external compressor also causes a change in meter readings. It is well known to use compressors for the purpose of overcharging meters at petrol stations. At the same time, the volume counter, due to the physical features of its work, displays the volume of not only the product, but also the air pumped with the product.

At the same time, airing the flow using pumps in Food Industry, in particular in the alcohol industry, leads to an unfavorable imbalance for the manufacturer of volumes measured by the counter and determined by the number of bottles filled through the dispenser. The explanation for this phenomenon is quite simple - air is dissolved in water in an amount of up to 3% by volume (at atmospheric pressure), and with a strong shake, like from champagne, it is released. To get rid of this phenomenon, it is necessary either to change the pump, or to reduce the flow rate, or to install the meter downstream of the pump. If an air collector is installed, then it is necessary to instrumentally check the effectiveness of its operation. It often happens that air collectors, even complex in design, do not create an extinguishing effect on food products.

Changing the roughness of surfaces. It is known that the inner walls of the pipe and the blades of the turbine must have rough surfaces. If the surface of the blades is very smooth, such as coated with a film or polished, this will make it very difficult for the flow to turbulize along the blade and reach the critical Reynolds number. In turn, this will significantly increase the slip of the turbine in operation and lead to a noticeable underestimation of the meter readings (Fig. 1). For information, on gliders, a thread is specially pulled in front of the wings in order to cause flow turbulence and a large, at the same angle of attack, lift.

Another way is to replace the calibrated washers and impellers of verified meters with fake ones, with a different washer hole diameter or a different impeller screw thread angle. In the pipe, the sensitive elements are not visible, and when opened, it is almost impossible to detect a defect or accuse the customer of a fake of deliberately understating the readings.

2. Mechanical and magnetic braking

Mechanical braking of the impeller with a fishing line passed through a tap or with a filter plug, when organizing apartment accounting water consumption. The plug idea is especially effective, as it clearly demonstrates the incompetence of designers and inspectors in matters of instrumentation.

If mesh filters in apartments are installed downstream of water meters and are not sealed, then switching flows through filter plugs using flexible hoses leads to “twisting” of meter readings.

Magnetic braking of impellers and magnetic couplings by means of an external permanent or rotating magnetic field possible, but if there are ferromagnetic screens on the meter, it is usually inefficient. Apparently, more research is needed on this issue.

As for vortex counters with a constant magnetic excitation field, then, as shown by our experimental studies, there are opportunities to change (falsify) the meter registered lower limit measurements on the threshold of sensitivity. In other words, if the vortex counter's electronic recorder is set to 1 m 3 /h, then with artificial magnetic field compensation, operation can occur at a much higher flow rate, for example, at 4 m 3 /h. Volumes with flow rates up to the given value will be recorded at the lower presetting. All that is required for this is to occasionally connect to the magnetic system of the vortex sensor an external electromagnetic system from a power supply unit and a solenoid, the core of which is a vortex sensor magnet. 2-tube measurements require 2 solenoids. However, for technological measurements, the vortex sensor of the described design may be of interest.

3. Temperature factors

At the same metering unit, our instrumental surveys revealed the fact of underestimation of the heat carrier supply temperature readings by 20 °C, which gave a large consumer almost 50% underestimation of the heat metering unit readings. The source of the defect was a non-standard thermowell (thermowell) made of a segment water pipe, which protruded about 8 cm above the supply pipeline and was filled to the top with liquid. Since thermowells are not subject to inspection when they are installed in a pipeline, their special design and filling with liquid above the operating level of the RTD sensing element can also contribute to the change in meter readings.

You can replace the resistance thermometer with a fake one or connect a resistor of a certain rating in parallel with it or the communication line. The effect is similar to the previous one, and in the presence of a hidden switched resistor, it is difficult to detect the cause of underestimation during inspections.

4. Influence of cable asymmetry and correct grounding

At 2 metering stations of the same type, a discrepancy of approximately 4% was found in the readings of digital flow meters and computers connected to them, and, oddly enough, in one case the readings of the flow meter were higher than those of the calculator, and in the other, vice versa. This fact can be explained by the fact that instead of a cable with cores of the same section, asymmetric wires enclosed in a metal hose were used, as well as by incorrectly executed grounding, which led to loop currents of the corresponding direction.

5. Incorrect sealing and the presence of a keyboard

The presence of soft, especially plasticine, seals on the components of the metering units allows you to make impressions from the seals and open the metering units with the provision of a change in readings by any accessible way. Remarkably, but once tax office refused the author to withdraw samples of lead seals from the investigated metering station alcoholic products, because seals with cut ends of the wire were subject to accounting. Perhaps, in the delivery of used seals, the meaning is laid not only of the disposal of lead, but also deep meaning counterfeit control (according to outward signs and composition).

After completing the training of one of the thermal inspections, the author asked to perform a control sealing of any metering unit so that it was impossible, as promised, to underestimate the readings in 5 minutes. What was the general amazement when the author, having examined all the seals, instead of the planned method, opted for the seal of the supply pipeline thermometer and managed to unscrew the resistance thermometer without breaking the seal. The entire operation to underestimate the readings of the metering station took 2 minutes.

The presence of a keyboard allows you to "zombify" the calculator program and control the change in readings directly from the keyboard using only commands known to scammers. In the first developments of domestic heat meters, the power supply of the flowmeter and calculator was separate. Disconnecting the flow meter from the network did not lead to the shutdown of the operating time counter in the calculator. Until now, some meters, installed by the author back in 1994, operate in the mode of unauthorized underestimation of readings, and heating networks compensate for their losses by increasing energy tariffs. Any software tricks of developers in the form of alarms, as it turned out, are easily removed and do not give any benefit, except for problems in operation.

6. Unbalanced Accounting

When organizing a metering system that includes a certain number of metering units combined into a single system, there is an imbalance in the entire system with a significant excess of the resulting error that the entire system as a whole should have. For example, at night apartment meter shows the amount of water consumed by the consumer, and the meter at the entrance to an apartment building, for example, a vortex type, does not respond to the flow due to the presence of a threshold flow rate. Such an imbalance seems to be “beneficial” to the residents of the house, if you do not take into account that unbalanced accounting according to the standards for measuring Information Systems and norms of accuracy is illegal.

Findings:

Thus, from the foregoing, priority measures arise to reduce the uncertainty and distortion of the commercial accounting of PER and their losses:

To improve the reliability of accounting measurements of energy and natural resources metering units must undergo state verification by the bodies of the State Standard of the Russian Federation directly at the places of operation without violating the integrity of metering units.

On strategically important routes for the transportation of natural and energy resources, in addition to metrological control, tax (balance) control should be carried out using portable calibrators, communications, computers, statistical processing methods and other tools for detecting excess losses.

The control of metering stations, interpreted in a peculiar way and actually carried out by power engineers, is illegal, brings huge annual losses to consumers of resources and the treasury in the form of a shortage of products, taxes, customs duties and the presence of losses (up to $ 100 billion annually), hinders technical progress. It is advisable to exclude illegal actions from the Accounting Rules and everyday practice and bring them into line with the standards and basics of metrology of measuring information systems.

It is necessary to import the well-known, primarily tax and customs, requirements for the protection of goods and commercial information from unauthorized access to accounting nodes. Specific methods and means of protection must pass certification tests.

Literature

1.Andreev I.P. Common Mistakes organization of commercial heat metering. Energy Efficiency, CENEf, 1995, No. 9.

2. Andreev I. P. Instrumental survey and detection of defects in urban systems of heat and water accounting. Energy Efficiency, TSENEF, 1998, No. 21, p. 20-22.

3.Andreev I.P. About metrological support of

accounting for energy resources. Report to the Scientific and Technical Committee of the State Standard of the Russian Federation, protocol No. 10 dated June 27, 2000.

4. Andreev I. P. Portable calibrators for rejection, adjustment, operational and metrological control, certification of commodity pipeline metering systems for energy and natural resources and provision of services to eliminate metering defects. The project that won the Russian Competition of Innovative Projects "Science-Technology-Production"

A heat meter is a device for recording the consumed heat carrier, which is currently very profitable, as it allows you to save money by paying only for the consumed heat, eliminating overpayment.

The important point is right choice type of device depending on the place of installation and design features heating networks, as well as the conclusion of an agreement with a service organization that will control technical condition devices.

There are many models of heat meters that differ in design and size, but the principle of how the heating meter works remains the same as on the simplest device that measures the temperature and water flow at the inlet and outlet of the heat supply pipeline. Differences appear only in engineering approaches to solving this issue.

The operation of the heat meter is based on the principle of calculating the amount of heat using data taken from a coolant flow sensor and a pair of temperature sensors. There is a measurement of the amount of water that has passed through the heating system, as well as the temperature difference at the inlet and outlet.

The amount of heat is calculated by the product of the flow rate of water passing through heating system, and the temperature difference between the incoming and outgoing coolant, which is expressed by the formula

Q \u003d G * (t 1 -t 2), gcal/h, in which:

  • Gmass flow water, t/h;
  • T1,2- temperature indicators of water at the inlet and outlet of the system, o C.

All data from the sensors are sent to the calculator, which, after processing them, determines the value of heat consumption and records the result in the archive. The value of the consumed heat is displayed on the display of the device and can be taken from any moment.

What affects the accuracy of the heat meter

Techem compact V

A heat meter, like any precision device, has a certain total error when measuring consumed heat, which is the sum of the errors of temperature sensors, a flow meter and a calculator. In apartment accounting, devices are used that have an allowable error of 6-10%. The actual error rate may exceed the base one, depending on the technical characteristics of the components.

The increase in the indicator is determined by the following factors:

  1. The amplitude of the incoming and outgoing coolant temperature, which less than 30 o C.
  2. Violations during installation in relation to the requirements of the manufacturer (when installed by an unlicensed organization, the manufacturer withdraws warranty obligations from it).
  3. Inadequate quality of pipes, hard water used in the coolant, and the presence of mechanical impurities in it.
  4. At a coolant flow rate below minimum value, indicated in technical specifications devices.

How is heat consumed measured?

It is customary to calculate the tariff for consumed heat in gigacalories. The unit of measurement refers to non-systemic, and has been traditionally used since the existence of the USSR. Appliances made in Europe calculate the consumed heat in GigaJoules (SI), or a generally accepted international non-systemic unit kWh (kWh).

Types of heat meters

All heating meters available for purchase are divided into the following types:

  • Tachometric or mechanical

It measures the amount of coolant that has passed through the section of the pipe using a rotating part. The active part of the device can be screw, turbine or in the form of an impeller.
The devices are affordable and easy to use. Weak side similar devices - sensitivity to dirt and settling inside the mechanism of dirt, rust, and to water hammer. For this, a special magnetic mesh filter is provided in the design. Also, the devices are not able to store the data collected per day.

  • Ultrasonic

More commonly used as a general counter apartment building. It has varieties:

  1. frequency,
  2. temporal,
  3. doppler,
  4. correlation.
    It works on the principle of generating ultrasound passing through water.

The signal is generated by the transmitter and picked up by the receiver after passing through the water column. Guarantees high measurement accuracy only with sufficient purity of the coolant.

  • Electromagnetic

Differs in high accuracy of indications and cost. The operation of the device is based on the principle of passing a magnetic field through the coolant flow, which reacts to its state. The device needs periodic maintenance and cleaning. It consists of a primary converter, an electronic unit and temperature sensors.

  • Vortex

It works on the principle of measuring the number and speed of vortices. It is not sensitive to clogging, but reacts to the appearance of air in the system. The device is installed in horizontal position between two pipes.

How to present evidence correctly

An apartment heat meter is functionally much simpler than a modern one. mobile phone, but users periodically have misunderstandings about the process of taking and sending display readings.

To prevent such situations, before starting the procedure for taking and transferring readings, it is recommended to carefully study his passport, which provides answers to most questions related to the characteristics and maintenance of the device.

Depending on the design features of the device, data collection is carried out in the following ways:

  1. From the liquid crystal display by visual fixation of readings from various sections of the menu, which are switched by the button.
  2. ORTO transmitter, which is included in the basic package of European devices. The method allows you to display on a PC and print extended information about the operation of the device.
  3. M-bus module is included in the delivery of individual meters in order to connect the device to the network of centralized data collection by heat supply organizations. So, a group of devices is combined into a low-current network with a twisted pair cable and connected to a hub that periodically polls them. After that, a report is generated and delivered to heat supply organization or displayed on the computer display.
  4. Radio module, supplied with some meters, transmits data wirelessly over a distance of several hundred meters. When the receiver enters the range of the signal, the readings are recorded and delivered to the heat supply organization. So, the receiver is sometimes attached to a garbage truck, which, when following the route, collects data from nearby counters.

Archiving readings

All electronic heat meters store in the archive data on the accumulated indicators of thermal energy consumption, operating and idle time, coolant temperature in the forward and return pipelines, total time developments and error codes.

By default, the instrument is set to various modes archiving:

  • hourly;
  • daily;
  • monthly;
  • annual.

Some of the data, such as total operating time and error codes, can only be read using a PC and special software installed on it.

Transfer of readings via the Internet

One of the most convenient ways transmission of indications of consumed thermal energy to institutions for its accounting is transmission via the Internet. Its convenience and practicality lies in the ability to independently control payments and debts, as well as track heat consumption in different periods without staying in queues and spending a small amount of time.

To do this, you must have a personal computer connected to the network and the address of the website of the controlling organization, as well as a login and password. personal account, after entering which a form for entering readings will open. To prevent the occurrence of disagreements in the event of a possible failure or malfunction on the site, it is advisable to take “screenshots” of the screen after entering information.

Breakdowns and repairs

Maintenance of the device is limited to maintaining it in working condition, regular inspection, and avoiding causes that cause premature wear and tear. According to paragraph 80 of the Rules for the commercial accounting of the coolant, all maintenance and control of the correct operation of the meter is carried out by the consumer. On the part of the owner, he special care does not need.

lithium battery or the batteries that power the device are not suitable for reuse and should be disposed of if they fail.

If any malfunction in the operation of the metering device is detected, the consumer must notify the service company and the organization providing heat supply within 24 hours. Together with the arrived authorized employee, an act is drawn up, which is then transferred to the heat supply organization with a report on heat consumption for the corresponding period. In case of untimely notification of a breakdown, heat consumption is calculated in a standard way.

The service company will provide services to repair or replace the meter, and may install a replacement device during the repair. The cost of installation and dismantling, repair and other services is regulated by an agreement between the consumer and the service company.

Error logging

As standard, heat meters are equipped with a self-testing system that can detect inaccuracies in operation. The calculator periodically queries the sensors, and if they fail, fixes an error, assigns a code to it and writes it to the archive. The most common reported errors are:

  1. Incorrect installation or damage to the temperature sensor or flow device.
  2. Insufficient battery charge.
  3. The presence of air in the flow path.
  4. No flow if there is a temperature difference for more than 1 hour.

Removal and installation of the heating meter

Before installing a heating meter in an apartment or apartment house, specialists of specialized companies with permits for this type of work are invited. Based on the specific situation, they can take on the following obligations:

  1. Develop a project.
  2. Submit documents to certain authorities in order to obtain permits.
  3. Install and register the device. In the absence of registration, payment for the supplied heat is made according to the established tariffs.
  4. Carry out test tests and put the device into operation.

The developed project should include the following points:

  1. Type and device of the model, which is designed to work in a particular heating system.
  2. Necessary calculations for heat load and coolant flow.
  3. Scheme of the heating system with the installation location of the heat meter.
  4. Calculation possible losses heat.
  5. Calculation of payment for the supply of thermal energy.

Checking heating meters

As a rule, a quality device arrives at the point of sale initially tested. The procedure is carried out at the factory, which is evidenced by a stamp with a record corresponding to the record in the documentation. In addition, the documents indicate the calibration interval.

After the expiration of this period, the owner of the device must contact service center manufacturer or an organization authorized to check and install the meter. There are companies that, after installing the device, are engaged in its maintenance.

Periodic confirmation of the metrological class, or in a word, verification, is carried out by a specialized company that has pouring installations, as well as a permit issued by the metrological supervision authorities.

The calibration period depends on the type of device, and averages 4-5 years.

For this purpose, a metrologist is called, seals are removed, a specialist from a service organization dismantles the meter and sends it for verification. After checking and reassembly, the device is sealed.

A heating meter is a device for accounting for thermal energy, which allows you to save money by paying only for the actually consumed service. Failure to comply with the conditions below will lead to the inability to pay for heat according to the meter readings.

For the correct and long-term operation of the device, it is important to choose the type of meter, which must be present in the state register of measuring instruments acceptable for use, and also have metrological certification in the appropriate authority.

The device is installed by an enterprise licensed to carry out such work.

With filled pipeline and closed shutoff valves(displayed flow must be 0) g1 values ​​are displayed.

Likely cause:

1. An electric current flows through the pipeline, on which a heat meter with a primary flow converter is installed.

2. Malfunction of valves

1. Since heating network not designed to transmit electricity, find and eliminate the source of electric current.

2. Let the current pass through the area where the heat meter is installed, as follows:

Insulate flange bolts. For devices with threaded connection- embed flanges on nearby sections of pipelines or use the flanges of adjacent fittings;

Rice. 1. Diagram of insulating flange bolts

Perform electrical shunting of the pipeline section on which the heat meter is installed with a shunt bus. Use steel wire with a diameter of 6...8 mm. Connection method - welding.

Rice. 2. Scheme of electrical shunting of the pipeline section.

With the assumed uninterrupted flow of the coolant, instability of the readings g1 (g2) is observed.

Most likely causes:

A foreign body got into the channel or the primary flow converter connected to it.

Elimination Methods:

Dismantle PPR (primary flow converter). It is possible to install a filter if the problem persists.

With the expected ratio of flows in the supply and return pipelines, there is a difference in readings between g1 and g2. In this case (g1-g2)/g1*100 > 2%

Most likely causes:

1. A foreign body has entered the channel or the primary flow converter connected to it.

2. The requirements for straight sections of pipelines have not been met.

3. Malfunction of the primary flow converter.

Elimination Methods:

In the event that no clogging of the flow path is detected, send the flow transducer for repair and verification

No signal from flow transducer channel V1.

Most likely causes:

1. The direction of the flow in the pipeline does not correspond to the direction of the arrow printed on the body of the primary converter

2. An electrically conductive foreign body got into the channel or the flow converter connected to it and shorted the electrodes to the body.

Diagnostics:

1. Analyze the correspondence of the direction of the arrow to the direction of flow.

2. Dismantle the PPR, inspect the flow path

3. Ring the power supply circuit from the calculator.

Elimination :

1. Remount the PPR.

2. Clean the flow part and install a magnetic-mechanical filter before the flow converter.

3. Restore the network when it breaks.

Breakage or short circuit of temperature sensors of channel T1 or T2.

Most likely causes:

1. Temperature sensors are not connected or another device is connected instead (flow sensor).

2. Break or short circuit in the wires connecting the temperature sensors to the calculator or the temperature sensors are faulty.

Diagnostics :

1.Check if the connection is correct.

2. Disconnect the wires from the temperature sensors, measure their resistance (resistance from 500 to 780 Ohm is considered normal). If the resistance goes beyond the mentioned limits, this may indicate a break, short circuit or a malfunction of the temperature sensors.

Elimination :

1. Carry out a new installation with the selected measuring circuit.

2. Replace temperature sensors if a malfunction is found in them

T1 2.

Most likely causes:

Introduction

After manufacturing, almost all heat meters are the same. However, if we take metering devices in the process of operation and operation, they are all different, they have little in common in their work, there are very few similarities in their work. The readings of the meter may have an error, which can lead to an overpayment for thermal energy resources or vice versa. In the event that the readings are underestimated, the heat supply organization may have questions for consumers of thermal energy. This fact may be revealed at the first verification of the testimony. As a result, the heat supply organization will insist on an extraordinary verification of heat energy meters, which will be paid by the heat supply organization. In the event that the under-reading occurred due to the fault of the consumers, the heat supply organization will ensure that all costs associated with the dismantling, verification and installation of the meter are borne by the consumers. In most cases, the case goes to trial. In this case, the consumer will be forced to pay for the litigation incurred by the heat supply organization.

If the testimony is too high, the heat supply organization will be found guilty, the consumer has the right to apply to the court for reimbursement of overpaid money, as well as a penalty and compensation for moral damage. Note that the costs of a lawyer, which the consumer will incur, he also has the right to recover from the heat supply organization in court. It is very difficult to reach an agreement without litigation, but we advise you to try to do it anyway, because. Litigation can drag on for months or years.

The most common violation that leads to incorrect calculation of indicators by the heat meter is their incorrect installation. Currently, there are many organizations on the market that promise you the installation of UUTE at the lowest price. Before ordering the installation of a heat metering unit, check the licenses and reviews about them. Nowadays, many organizations are trying to reduce the cost of specialists, which ultimately can lead not only to errors in readings, but also to a breakdown of the device, the repair of which will cost much more than the service of a qualified specialist. You should not look at the cost of doing the work, saving on this, you can pay much more for further consequences.


Rice. one.

The main violations during the installation of heat energy meters

1. In order to save money, the connection of a set of thermal converters with a three- or four-wire connection scheme is carried out using a two-wire scheme. There were cases when such installation was carried out with a telephone wire or a wire with a cross section of 0.22 mm 2 (recommended at least 0.35 mm 2), which led to an error when measuring temperature more than 10 ° C, while the measurement error of the heat meter increases to 50% .

2. If there is no oil in the thermowells, this will eventually lead to calculation errors. The maximum error is 4 degrees. In monetary terms, the approximate loss is 30 thousand rubles. At a flow rate of 8 t/h (and this is a coolant flow rate typical for a four-storey five-story building), the thermal energy measurement error is 0.032 Gcal/h or 0.768 Gcal per day. In monetary terms - approximately 30 thousand rubles. per month.

3. In the pipeline of the heating system with a diameter of 32 or 40 mm, thermal converters are installed - temperature converters, the length of which significantly exceeds the diameters of the pipelines. If such a thermal converter is installed on a small-diameter pipeline without the use of pipeline expanders, then its working part will significantly protrude beyond the pipeline, so the device cannot reliably measure the temperature of the coolant. Therefore, the accuracy and measurement error of the meter does not correspond to those declared by the manufacturer, and such a meter cannot be considered commercial.

4. To reduce the amount of work, when installing a heat meter, temperature sensors are installed in the sump. As a result, their working surface is located outside the energy flow movement system. The lack of isolation also negatively affects the transmitted readings. As a result, the reading error is 5-7 degrees. If we express this error in monetary terms, we get 108 thousand rubles (a nine-story building with four entrances)

5. Sometimes, instead of temperature sensors, for example, KTPTR (KTSPN), which are prescribed in the project, they are replaced by single ones, for example, TSP100. Note that the additional error can reach 3%, which will affect the parity of the transmitted data.

6. Lack of thermal insulation of the upper part of the resistance transducers everywhere, especially if these sections are located on the street. It is clear that in this case there will be an additional temperature measurement error, and, as a result, the accuracy and error of heat energy measurement.

7. Flow transducers must be installed in the pipeline through paronite gaskets. Very often, when dismantling the flow transducer for state verification, we remove paronite gaskets with an internal, cut chisel, triangular or rectangular hole (Fig. 2). What measurement accuracy can we talk about if the water flow in the flow meters is unpredictable in this case?

Rice. 2. A flow meter that has had a square gasket installed.

8. Electromagnetic flow transducers (in the "sandwich" version) must be mounted in the system using a torque wrench, with the obligatory installation of additional damping pads. Violations of these recommendations are observed everywhere at the facilities, which leads to a change in the inner diameter of the fluoroplastic lining of the flow meter, violation of the gaps between the lining and the electrodes for retrieving information about the coolant flow rate, and a significant error in measuring the coolant flow rate (Fig. 3).

Rice. 3. A non-genuine spacer was installed on the flow meter, and a magnetic strainer was not installed.

9. In order to save money, when mounting flowmeters, standard flanges are used instead of the flanges recommended by manufacturers with centering recesses. In this case, the primary flow converters can be installed with an offset of up to 10 mm from the axis of the pipeline. At the same time, it is difficult to establish the error in measuring the flow rate by the heat meter for this pipeline.

10. Application everywhere instead of paronite gaskets - rubber, 3-4 mm thick. Uneven compression of the rubber leads to misalignment (skew) of the flow meters and an increase in the measurement error of the heat meter. The inner diameter here is also impossible to withstand due to the compression of the rubber. This, by the way, is one of the main reasons why the devices on the stand come with zero error, and at the site the measurement error exceeds that established for the heat meter. If the measurement error shows a leak, then the consumer overpays for it. If vice versa, then the excess consumption of the heating network feed is fixed at the heat source. In this case, the readings are not taken into account, and the heat meter itself is simply rejected.

11. When installing flow meters, there are cases when cables are connected to them in such a way that water condensate flows through the cable into the heat meter's flow converter, first distorting the measurement result, and then leading to failure of the primary flow converter (Fig. 4).

12. There are facilities where meters that do not correspond to actual loads are installed to measure the flow of the coolant (especially for hot water in systems with variable flow (various temperature maintenance controllers are installed in the heating system or hot water supply). At a low flow rate, the error of the flow devices does not allow it to be used for the purposes of commercial metering of thermal energy.

14. When checking at a number of objects, some of the instruments have expired verification dates, or the instruments are out of order. No one knows what measurement error we can talk about in this case.

Conclusion

The accuracy of the calculation of thermal energy directly depends on the installation and quality of service. Therefore, it is very important that the design, maintenance and installation of the UUTE be carried out by professionals who have the necessary specialization. Employees of the organization must have certificates for electrical safety and labor protection. As an example, let's provide Figure 5, which shows the difference between a meter serviced by a qualified organization and not.

Rice. 5. The difference between appliances that have been serviced correctly and not.

Answers to search queries of site visitors: how to take readings from a heat meter, how to take readings from a heat meter correctly, how heat is calculated from a heat meter. Let's take a look at 2 options:


a) You take readings yourself, manually, i.e. just overwrite the values ​​in .

Now there is no need for this (if only for your own complacency). New - the accounting journal was canceled. Is this good or bad. It is good that the quality of heat meters has increased so much that there is no need to keep a log, all data can be read at any time directly from the heat meter directly or via a flash drive, computer or laptop.

It is bad if you have an old heat meter. Since this year, he is outlawed, which means he will live until the next state inspection, after which the heat meter will have to be replaced without fail.

If you still want to take readings, for yourself, for this, manually study the operating manual for your heat meter - the heat meter maintenance section, or the operating instructions - a mandatory application to the heat metering unit project.

Moreover, the readings must be taken at the same time. You can set the pick-up time yourself, as you wish, we recommend the morning hours. accounting and is also a mandatory annex to the project.

What values ​​for removal are required depends on the specific node. As a rule, this is the temperature in the supply and return pipelines, the flow rate of the coolant in the supply and return pipelines is better in (t), the amount of heat energy received - the value can be in any units - Gcal, MW, kJ.

On counters of domestic production, these values ​​look like this - Gcal; MW; kJ; imported kW (kWh-current); MW; MJ or GJ.

For heating networks, it's all the same. They themselves will recalculate into Gcal. For verification, I recommend downloading or remembering that 1 Gcal is 1.163 MW (MW) or 4.187 GJ (GJ). The last mandatory value is the operating time of the meter or operating time.

b) You take readings yourself (the rules do not prohibit this) using technical means - a cumulative remote control, a printer, a laptop. The most acceptable for you is, of course, the printer - with it you will make the least mistakes.

How to shoot is again in the "instructions" - an appendix to the project. I would certainly recommend you to hire specialists. Why - .

If you hire specialists, for control, put a small notebook in the shield with a heat meter, where they will record for you the date of taking readings and the amount of thermal energy at the time of taking them. This is your requirement to voice in advance, before the conclusion of the contract, otherwise they have every right to refuse.

Analyzing the records of readings, you can easily control the amount billed to you for heat by thermal networks. And it is imperative that they themselves transmit the readings to the heating networks, otherwise why do you need them. As my first master said, even a monkey can do such work if it is taught to press buttons.

And a final note, never try to save heat by cheating. With modern methods of control, everything is very easily controlled. Punishment court costs and payment of five times the amount. This is the best economy.

How to correctly take readings of a kwh meter manufactured in 1985;

Read a little higher - section "a". I would recommend replacing the heat meter of 1985, because already in 1995, after the release of the rules for accounting for thermal energy and coolant, it ceased to comply with them, and it does not comply with the new rules all the more, and the worst thing is that it is unknown what.

Based on operating experience, heat meters of 1998-99 do not pass state verification - they do not correspond to the declared parameters due to wear. Although there are individuals, pressure gauges manufactured in 1961 pass state verification without additional adjustments, and new ones out of the box do not pass it. It all depends on the manufacturer.

How is heat calculated?

The amount of received thermal energy is calculated in Gcal. It is accepted for calculation by thermal networks in any values ​​- it can be - Gcal, MW, kJ, GJ.

On counters of domestic production, these values ​​look like this - Gcal; MW; kJ; imported kW; MW; MJ or GJ. For heating networks, in what quantities you will transfer the data anyway. They themselves will recalculate into Gcal.

1 Gcal is 1.163 MW (MW) or 4.187 GJ (GJ).

Saving heat with the help of UUTE.

Is an SRO (old license) required for the installation of heat meters;

Yes, the answer is clear. In addition, the specialists of the company installing the devices are required to have initial training and valid certification in the technical supervision bodies. Therefore, if you are a manager concluding a contract, check the certification documents with the contractor in advance. Otherwise, your heat meter will never become commercial.

How to install a heat meter yourself;
Do I have the right to install a heat meter myself;

As follows from the above, it is impossible, and moreover, I do not advise you to undertake it. The rules for installing heat meters from different manufacturers are very different from each other. Even if you are a heating engineer, metrologist, instrumentation engineer, welder, electrician, plumber, all rolled into one, which is unlikely, you will have to remember or study all the rules, GOSTs, SNiPs and also installation manuals for this heat meter. The cost of services in this market has now fallen. And the area of ​​heat supply is so complex that sometimes even specialists lack knowledge and experience. My personal opinion is that it is high time for us to forget the communist times and earn money where we work. Thankfully it's not banned now. No offense. I myself am like you. Brought up in communist times, I know how to do everything better than modern "specialists". Why do kids always scold me.

How are heat meter readings calculated?

The following is taken into account:
- the amount of thermal energy received by the heat meter.
- the amount of heat spent on feeding the heating system, if there was a leak in the heating system. In this case, the possible error of the flow meters and the permitted normative leakage of water from the heating system must be taken into account.
- loss of thermal energy to metering devices in accordance with the contract.
These data are summarized and multiplied by the cost of 1 Gcal.

How to check if the payment for heat according to the heat meter is correctly calculated;

Calculate the difference, the value of Q is the amount of heat energy consumed between the last and penultimate reporting dates. Since, for example, if it were an electric meter.
Convert your heat meter readings to Gcal.
To do this, if you have Q in MW, multiply by 0.8598; if in GJ, multiply by 0.2388, you will get the value in Gcal.
Add the amount of contractual losses, if any. Losses should be stipulated in the contract and painted by months.
Multiply the amount of heat received by the cost of 1 Gcal.
If this value differs from the one set for you, check if you have had any water leakage from the heating system. To do this, look at the consumption readings, parameter G in (t) as well as in the case of Q by reporting dates. If the data do not differ by more than 2% (for closed heating systems), in some heating networks they accept 4%, 2% error of one flow meter, 4%, respectively, of 2 flow meters - flow meters are devices that count the amount of water that has passed through your heating system or hot water supply. If they differ, it means that you have been charged an additional cost for drawing water from the heating system.
It is considered so. The amount of water withdrawal, (taking into account the error of the instruments) in (t) is multiplied by the temperature difference between the return pipeline and the temperature of cold water for a given period. Get the value in Gcal, which is added to the heat you consumed. Data is usually rounded to whole numbers, the remainder is carried over to the next reporting period.
Checked, you can now go argue or sleep peacefully. I'm always in control, because errors are common, both through the fault of people and the fault of programmers writing programs for reports.

What else to read