Complete pumping units Grundfos Hydro MX designed for fire extinguishing systems in residential buildings of various heights, shops, production and storage facilities, cultural and social facilities.
Settings Hydro MX meet the requirements of TU 28.13.14-005-59379130-2019 and have a fire safety certificate NSOPB.RU.EO.PR087.N.00154. Installation design Hydro MX represents pumps or, piping, shutoff valves, pressure gauges and pressure switches mounted on one frame, as well as a fire control device Control MX.
A color display located on the PPU door displays all the necessary information about the state of the fire extinguishing installation Hydro MX in a clear graphical form, and also provides access to settings and a log that stores up to 1024 events.
Hydro MX allows you to transfer information about the state of the installation via a communication channel directly to a centralized monitoring point or to a room with personnel on duty around the clock. For full duplication of the PPU control panel Control MX a Remote Dispatch Panel is supplied as an accessory.
Built-in PPU Control MX the ability to control the jockey pump, drain pump, and electric gate valves ensure the operation of auxiliary equipment without the need to make any design changes to the complete product.
Certificates can be found in the section.
Areas of use:
Fire safety certificates:
Advantages:
Options:
General information
Hydro MX (hereinafter referred to as units) are complete pumping units for water and foam fire extinguishing systems. Hydro MX units comply with the requirements of TU 4854-05-59379130-2006 and have a fire safety certificate SSRP-RU.PB01.N.00145.
Application area
Hydro MX can be used in sprinkler and deluge water and foam fire extinguishing systems, as well as in systems with hydrants.
Pumped liquids
Water is used that does not contain impurities that can have a chemical or mechanical effect on the flow path of the Hydro MX installation and the automation devices included in the delivery.
Contents of delivery
Two or three (depending on the configuration) fire pumps of the CR or NB type with a set of fittings and equipment in accordance with the requirements of the Technical Regulations for fire fighting - Control MX fire control device connected to the pumps and equipment.
Design features:
- Full compliance with Russian standards
- Supply up to 500 m 3 / h
- Developed pressure up to 16 bar
- Triggered by pressure switch/dry contacts.
Areas of use:
- The main units in sprinkler and deluge systems
- It is also possible to use it for power supply systems of fire hydrants.
jockey pump
The jockey pump is designed to maintain water pressure in sprinkler fire extinguishing systems. From design experience, it is recommended to take the parameters of the jockey pump according to the following dependencies:
Q jockey \u003d 2-3 m 3 / hour, if Q fire. pump<= 100 м 3 /ч
Q jockey \u003d 3-4 m 3 / hour, if Q fire. pump >= 100 m 3 / h.
The pressure of the jockey pump must exceed the pressure of the fire pump at the operating point by 10%, but not less than 5 m.w.s. However, depending on specific project requirements, it may be necessary to install a jockey pump that provides other parameters.
The choice of jockey pump parameters should be made by the person designing the fire suppression system.
It can be used as a jockey pump with Hydro MX units.
CR pumps as a jockey pump
CR pumps are ideal for use as jockey pumps with the following benefits:
- develop high pressure at relatively low feeds; - allow frequent switching on and off (100-200 times per hour, depending on engine power); - take up little space due to the vertical design; - have easily replaceable cartridge face seals.
The jockey pump is powered by. Signals from the pressure switch are also sent to the control cabinet.
The jockey pump is on signal is sent to the remote control panel.
The Control MX cabinet as standard allows you to connect a jockey pump with a motor up to 5.5 kW (inclusive), 3x380-415V, 50Hz.
Drainage pump
As standard, Hydro MX units allow you to control a drain pump.
The drain pump is usually installed in the pumping station room and is designed to remove water collected in the pit after the fire extinguishing system has been emptied.
Grundfos pumps of the series , , , , , with three-phase and single-phase electric motors up to 4 kW inclusive can be used as a drainage pump. On request, you can install a starter, designed for a more powerful pump.
It is allowed to use a drainage pump with a built-in level switch (floater) or with an external level switch. In the second case, the level switch is connected to the corresponding terminal in the Control MX PPU.
Gate valves with electric drive
Optionally, Hydro MX units allow you to control one electric valve in the basic version and up to 4 electric valves using the Control VLV module.
Description of Hydro MX pumping units
The wide application that the Grundfos Hydro MX d001 fire pumping station has found convinces: this is a reliable and functional device. In a situation where every minute counts, the fire station must start up instantly and work powerfully. These properties fully characterize this Grundfos jockey pump.
The Hydro MX fire extinguishing system is certified in the Russian Federation. This means that this fire alarm station will become an indisputable plus in assessing the fire safety of premises and entire buildings.
Compact fire extinguishing systems
Automatic fire extinguishing installations must have a universal set of characteristics: easy commissioning, efficiency in the fight against flames, the possibility of long-term non-stop operation. To effectively eliminate the source of fire, the installation of a fire extinguishing system must be thought out to the smallest detail.
To date, installations of powder, foam and water fire extinguishing are known. What distinguishes them is the composition of the substance acting on the flame. Each such unit is effective in its own way, having individual advantages.
Thus, water fire extinguishing installations in extreme conditions become a real "lifeline". Made of special water-storing materials, they are ready to deliver powerful pressure at any time. Chemical reactions from contact with the liquid are completely excluded even at high temperatures. Autonomous water fire extinguishing installations do not require expensive maintenance - water is a cheap filler.
The principle of generating a large amount of steam is used by water mist fire extinguishing installations - no less powerful, capable of adsorbing soot and carbon monoxide. The principle of spraying water over a wide area is also used by sprinkler fire extinguishing installations. They are a network of branched pipelines integrated into the ceiling and triggered by a danger signal. By the same principle, deluge fire extinguishing installations operate.
Foam, powder and aerosol fire fighting
In industrial buildings, foam fire extinguishing installations are most effective. Foam, spraying, "takes" oxygen from burning objects and thus reduces the combustion process to nothing. In addition, by distributing the foam composition, an automatic foam fire extinguishing installation stops the release of fumes that are dangerous in terms of ignition. So modular fire extinguishing installations with water mist eliminate the source of fire and prevent the formation of a new one.
Stationary automatic powder fire extinguishing installations are adapted for extinguishing electrical equipment. Served under high pressure, the powder extinguishes the flame without affecting the burning equipment and household items. Autonomous fire extinguishing installations operating with powder filler are widely used in administrative buildings and production shops.
Fire pumping units can also use the principle of aerosol spraying - a fire extinguishing composition that is harmless to people and the environment. Aerosol fire extinguishing pumping units also showed their best performance in the treatment of burning electrical equipment, including those under high voltage.
Fire installation selection options
The fire pump control station is a device on which, no less, the safety of people, the safety of property, equipment, and products of production depend. Centrifugal fire pumps must be certified equipment. Fire pumps should be controlled in a simple and efficient manner. To do this, the kit includes a cabinet (board) for controlling fire pumps, shut-off and control valves, and control devices.
The installation of increasing the pressure for fire extinguishing is also important - it is she who will maintain the water pressure at the optimum level. The Grundfos fire booster pumps, which have been tested and certified in the Russian Federation, have proven themselves well.
When choosing automatic fixed fire extinguishing installations or modular fire extinguishing installations, it is necessary to take into account: the units must not only effectively extinguish the flame. The device must be adapted to a long "idle", but immediately start working in a situation of need.
The Hydro MX 1/1 CR 10-3 installation is most often used to solve the problems of water or foam fire extinguishing. Each of the two pumps is connected to the relay network. The unit meets all modern requirements and is capable of operating both in the "sprinkler" mode (the fire pipeline in standby mode is always under a certain pressure created by the jockey pump), and in the "drencher" mode (the fire pipeline in standby mode is not filled). The jockey pump can be a CR 1-6 (CR 3-7) or a small pressure booster with a diaphragm tank. In the basic delivery set, for each installation it is allowed to connect a drainage pump, which must be purchased separately.
Only pure water (which does not contain any substances that can have a chemical or mechanical effect on the flow part of the pump) can be attributed to the pumped liquids.
The type designation for fire extinguishing equipment Grundfos MX 1/1 CR X-Y is deciphered, as MX - fire extinguishing installation, 1/1 - one working pump, one in reserve, CR X-Y - brand of pumps used.
Connection: 2 inputs of 3x380-410V / 50 Hz;
Degree of protection of a case of automatic equipment: IP54.
Hydro MX are fully prepared automatic pumping units that are widely used in water and foam fire extinguishing installations. The pumping unit is characterized by impeccable workmanship and complies with the provisions of the Technical Specifications and the current fire safety certificate.
Such equipment can be installed in sprinkler and deluge fire extinguishing systems, as well as in hydrant installations. Water is used, which does not include impurities that can have an aggressive effect on the flow component of the equipment and the automatic device.
These fire extinguishing installations are used:
Specifications for Hydromx 1 1
kayabaparts.ru - Entrance hall, kitchen, living room. Garden. Chairs. Bedroom