Gender by zones coefficients. Thermal engineering calculation of floors located on the ground

Previously, we calculated the heat loss of the floor on the ground for a house 6m wide with a groundwater level of 6m and +3 degrees in depth.
Results and problem statement here -
The heat losses to the outdoor air and deep into the earth were also taken into account. Now I will separate the flies from the cutlets, namely, I will carry out the calculation purely into the ground, excluding heat transfer to the outside air.

I will carry out calculations for option 1 from the previous calculation (without insulation). and the following data combinations
1. UGV 6m, +3 on UGV
2. UGV 6m, +6 on UGV
3. UGV 4m, +3 on UGV
4. UGV 10m, +3 on UGV.
5. UGV 20m, +3 on UGV.
Thus, we will close the issues related to the influence of the GWL depth and the influence of temperature on the GWL.
The calculation, as before, is stationary, not taking into account seasonal fluctuations, and generally not taking into account the outside air
The conditions are the same. The ground has Lamda=1, walls 310mm Lamda=0.15, floor 250mm Lamda=1.2.

The results, as before, in two pictures (isotherms and "IR"), and numerical - resistance to heat transfer into the soil.

Numerical results:
1.R=4.01
2. R = 4.01 (Everything is normalized for the difference, otherwise it should not have been)
3.R=3.12
4.R=5.68
5.R=6.14

About the sizes. If we correlate them with the GWL depth, we get the following
4m. R/L=0.78
6m. R/L=0.67
10m. R/L=0.57
20m. R/L=0.31
R / L would be equal to one (or rather, the inverse coefficient of thermal conductivity of the soil) for an infinitely large house, but in our case the dimensions of the house are comparable to the depth to which heat loss occurs, and the smaller the house compared to the depth, the smaller this ratio should be.

The resulting dependence R / L should depend on the ratio of the width of the house to the groundwater level (B / L), plus, as already mentioned, with B / L-> infinity R / L-> 1 / Lamda.
In total, there are the following points for an infinitely long house:
L/B | R*lamda/L
0 | 1
0,67 | 0,78
1 | 0,67
1,67 | 0,57
3,33 | 0,31
This dependence is well approximated by an exponential one (see the graph in the comments).
Moreover, the exponent can be written in a simpler way without much loss of accuracy, namely
R*Lambda/L=EXP(-L/(3B))
This formula at the same points gives the following results:
0 | 1
0,67 | 0,80
1 | 0,72
1,67 | 0,58
3,33 | 0,33
Those. error within 10%, i.e. very satisfactory.

Hence, for an infinite house of any width and for any GWL in the considered range, we have a formula for calculating the resistance to heat transfer in the GWL:
R=(L/lamda)*EXP(-L/(3B))
here L is the depth of the GWL, Lamda is the thermal conductivity of the soil, B is the width of the house.
The formula is applicable in the L/3B range from 1.5 to approximately infinity (high GWL).

If you use the formula for deeper groundwater levels, then the formula gives a significant error, for example, for a 50m depth and 6m width of a house, we have: R=(50/1)*exp(-50/18)=3.1, which is obviously too small.

Have a good day everyone!

Findings:
1. An increase in the GWL depth does not lead to a consistent decrease in heat loss to groundwater, since an increasing amount of soil is involved.
2. At the same time, systems with a GWL of the type 20m or more may never reach the hospital, which is calculated during the period of "life" at home.
3. R ​​into the ground is not so great, it is at the level of 3-6, so the heat loss deep into the floor along the ground is very significant. This is consistent with the previously obtained result about the absence of a large reduction in heat loss when the tape or blind area is insulated.
4. A formula has been derived from the results, use it to your health (at your own peril and risk, of course, I ask you to know in advance that I am in no way responsible for the reliability of the formula and other results and their applicability in practice).
5. Follows from a small study conducted below in the commentary. Heat loss to the street reduces heat loss to the ground. Those. It is incorrect to consider two heat transfer processes separately. And by increasing the thermal protection from the street, we increase heat loss to the ground and thus it becomes clear why the effect of warming the contour of the house, obtained earlier, is not so significant.

Usually, floor heat losses in comparison with similar indicators of other building envelopes (external walls, window and door openings) are a priori assumed to be insignificant and are taken into account in the calculations of heating systems in a simplified form. Such calculations are based on a simplified system of accounting and correction coefficients for the resistance to heat transfer of various building materials.

Considering that the theoretical justification and methodology for calculating the heat loss of the ground floor was developed quite a long time ago (i.e. with a large design margin), we can safely say that these empirical approaches are practically applicable in modern conditions. The coefficients of thermal conductivity and heat transfer of various building materials, insulation and floor coverings are well known, and other physical characteristics are not required to calculate heat loss through the floor. According to their thermal characteristics, floors are usually divided into insulated and non-insulated, structurally - floors on the ground and logs.

The calculation of heat loss through an uninsulated floor on the ground is based on the general formula for estimating heat loss through the building envelope:

where Q are the main and additional heat losses, W;

BUT is the total area of ​​the enclosing structure, m2;

tv , tn- temperature inside the room and outside air, °C;

β - share of additional heat losses in total;

n- correction factor, the value of which is determined by the location of the building envelope;

Ro– resistance to heat transfer, m2 °С/W.

Note that in the case of a homogeneous single-layer floor slab, the heat transfer resistance Ro is inversely proportional to the heat transfer coefficient of the uninsulated floor material on the ground.

When calculating heat loss through an uninsulated floor, a simplified approach is used, in which the value (1+ β) n = 1. Heat loss through the floor is usually carried out by zoning the heat transfer area. This is due to the natural heterogeneity of the temperature fields of the soil under the floor.

The heat loss of an uninsulated floor is determined separately for each two-meter zone, the numbering of which starts from the outer wall of the building. In total, four such strips 2 m wide are taken into account, considering the soil temperature in each zone to be constant. The fourth zone includes the entire surface of the uninsulated floor within the boundaries of the first three strips. Heat transfer resistance is accepted: for the 1st zone R1=2.1; for the 2nd R2=4.3; respectively for the third and fourth R3=8.6, R4=14.2 m2*оС/W.

Fig.1. Zoning of the floor surface on the ground and adjacent recessed walls when calculating heat losses

In the case of recessed rooms with a soil base of the floor: the area of ​​the first zone adjacent to the wall surface is taken into account twice in the calculations. This is quite understandable, since the heat loss of the floor is added to the heat loss in the vertical enclosing structures of the building adjacent to it.

Calculation of heat loss through the floor is made for each zone separately, and the results obtained are summed up and used for the thermal engineering justification of the building project. The calculation for the temperature zones of the outer walls of recessed rooms is carried out according to formulas similar to those given above.

In calculations of heat loss through an insulated floor (and it is considered as such if its structure contains layers of material with a thermal conductivity of less than 1.2 W / (m ° C)) the value of the heat transfer resistance of an uninsulated floor on the ground increases in each case by the heat transfer resistance of the insulating layer:

Ru.s = δy.s / λy.s,

where δy.s– thickness of the insulating layer, m; λu.s- thermal conductivity of the material of the insulating layer, W / (m ° C).

The essence of thermal calculations of premises, to some extent located in the ground, is to determine the influence of atmospheric "cold" on their thermal regime, or rather, to what extent a certain soil isolates a given room from atmospheric temperature effects. Because Since the thermal insulation properties of the soil depend on too many factors, the so-called 4-zone technique was adopted. It is based on the simple assumption that the thicker the soil layer, the higher its thermal insulation properties (the more the influence of the atmosphere is reduced). The shortest distance (vertically or horizontally) to the atmosphere is divided into 4 zones, 3 of which have a width (if it is a floor on the ground) or a depth (if it is a wall on the ground) of 2 meters, and the fourth has these characteristics equal to infinity. Each of the 4 zones is assigned its own permanent heat-insulating properties according to the principle - the farther the zone (the larger its serial number), the less the influence of the atmosphere. Omitting the formalized approach, we can make a simple conclusion that the farther a certain point in the room is from the atmosphere (by a factor of 2 m), the more favorable conditions (from the point of view of the influence of the atmosphere) it will be.

Thus, the countdown of conditional zones starts along the wall from the ground level, provided that there are walls along the ground. If there are no ground walls, then the first zone will be the floor strip closest to the outer wall. Next, zones 2 and 3 are numbered, each 2 meters wide. The remaining zone is zone 4.

It is important to consider that the zone can start on the wall and end on the floor. In this case, you should be especially careful when making calculations.

If the floor is not insulated, then the values ​​of heat transfer resistance of the uninsulated floor by zones are equal to:

zone 1 - R n.p. \u003d 2.1 sq.m * C / W

zone 2 - R n.p. \u003d 4.3 sq.m * C / W

zone 3 - R n.p. \u003d 8.6 sq.m * C / W

zone 4 - R n.p. \u003d 14.2 sq. m * C / W

To calculate the heat transfer resistance for insulated floors, you can use the following formula:

- resistance to heat transfer of each zone of an uninsulated floor, sq.m * C / W;

— insulation thickness, m;

- coefficient of thermal conductivity of the insulation, W / (m * C);

Despite the fact that heat losses through the floor of most one-story industrial, administrative and residential buildings rarely exceed 15% of the total heat loss, and sometimes do not even reach 5% with an increase in the number of storeys, the importance of correctly solving the problem ...

The definition of heat loss from the air of the first floor or basement to the ground does not lose its relevance.

This article discusses two options for solving the problem posed in the title. Conclusions are at the end of the article.

Considering heat losses, one should always distinguish between the concepts of "building" and "room".

When performing the calculation for the entire building, the goal is to find the power of the source and the entire heat supply system.

When calculating the heat losses of each individual room of the building, the problem of determining the power and number of thermal devices (batteries, convectors, etc.) required for installation in each specific room in order to maintain a given indoor air temperature is solved.

The air in the building is heated by receiving thermal energy from the Sun, external sources of heat supply through the heating system and from various internal sources - from people, animals, office equipment, household appliances, lighting lamps, hot water supply systems.

The air inside the premises cools due to the loss of thermal energy through the enclosing structures of the building, which are characterized by thermal resistances measured in m 2 ° C / W:

R = Σ (δ i i )

δ i- the thickness of the material layer of the building envelope in meters;

λ i- coefficient of thermal conductivity of the material in W / (m ° C).

The ceiling (ceiling) of the upper floor, external walls, windows, doors, gates and the floor of the lower floor (possibly the basement) protect the house from the external environment.

The external environment is the outside air and soil.

Calculation of heat loss by the building is carried out at the estimated outdoor temperature for the coldest five-day period of the year in the area where the object is built (or will be built)!

But, of course, no one forbids you to make a calculation for any other time of the year.

Calculation inexcelheat loss through the floor and walls adjacent to the ground according to the generally accepted zonal method by V.D. Machinsky.

The temperature of the soil under the building depends primarily on the thermal conductivity and heat capacity of the soil itself and on the ambient air temperature in the area during the year. Since the temperature of the outside air varies significantly in different climatic zones, the soil also has different temperatures in different periods of the year at different depths in different areas.

To simplify the solution of the complex problem of determining heat loss through the floor and walls of the basement into the ground, for more than 80 years, the method of dividing the area of ​​enclosing structures into 4 zones has been successfully used.

Each of the four zones has its own fixed heat transfer resistance in m 2 °C / W:

R 1 \u003d 2.1 R 2 \u003d 4.3 R 3 \u003d 8.6 R 4 \u003d 14.2

Zone 1 is a strip on the floor (in the absence of soil penetration under the building) 2 meters wide, measured from the inner surface of the outer walls along the entire perimeter or (in the case of a subfloor or basement) a strip of the same width, measured down the inner surfaces of the outer walls from soil edges.

Zones 2 and 3 are also 2 meters wide and are located behind zone 1 closer to the center of the building.

Zone 4 occupies the entire remaining central area.

In the picture below, zone 1 is located entirely on the basement walls, zone 2 is partially on the walls and partially on the floor, zones 3 and 4 are completely on the basement floor.

If the building is narrow, then zones 4 and 3 (and sometimes 2) may simply not be.

Square gender zone 1 in the corners is counted twice in the calculation!

If the entire zone 1 is located on vertical walls, then the area is considered in fact without any additions.

If part of zone 1 is on the walls and part is on the floor, then only the corner parts of the floor are counted twice.

If the entire zone 1 is located on the floor, then the calculated area should be increased by 2 × 2x4 = 16 m 2 when calculating (for a rectangular house in plan, i.e. with four corners).

If there is no deepening of the structure into the ground, then this means that H =0.

Below is a screenshot of the Excel calculation program for heat loss through the floor and recessed walls. for rectangular buildings.

Zone areas F 1 , F 2 , F 3 , F 4 calculated according to the rules of ordinary geometry. The task is cumbersome and often requires sketching. The program greatly facilitates the solution of this problem.

The total heat loss to the surrounding soil is determined by the formula in kW:

Q Σ =((F 1 + F1y )/ R 1 + F 2 / R 2 + F 3 / R 3 + F 4 / R 4 )*(t vr -t nr)/1000

The user only needs to fill in the first 5 lines in the Excel table with values ​​​​and read the result below.

To determine heat losses to the ground premises zone areas will have to be calculated manually. and then substitute in the above formula.

The following screenshot shows, as an example, the calculation in Excel of heat loss through the floor and recessed walls. for the lower right (according to the figure) basement room.

The sum of heat losses to the ground by each room is equal to the total heat losses to the ground of the entire building!

The figure below shows simplified diagrams of typical floor and wall structures.

The floor and walls are considered non-insulated if the coefficients of thermal conductivity of materials ( λ i), of which they are composed, is more than 1.2 W / (m ° C).

If the floor and / or walls are insulated, that is, they contain layers with λ <1,2 W / (m ° C), then the resistance is calculated for each zone separately according to the formula:

Rinsulationi = Rnon-insulatedi + Σ (δ j j )

Here δ j- the thickness of the insulation layer in meters.

For floors on logs, heat transfer resistance is also calculated for each zone, but using a different formula:

Ron the logsi =1,18*(Rnon-insulatedi + Σ (δ j j ) )

Calculation of heat losses inMS excelthrough the floor and walls adjacent to the ground according to the method of Professor A.G. Sotnikov.

A very interesting technique for buildings buried in the ground is described in the article “Thermophysical calculation of heat losses in the underground part of buildings”. The article was published in 2010 in №8 of the ABOK magazine under the heading "Discussion Club".

Those who want to understand the meaning of what is written below should first study the above.

A.G. Sotnikov, relying mainly on the findings and experience of other predecessor scientists, is one of the few who, for almost 100 years, has tried to move the topic that worries many heat engineers. I am very impressed with his approach from the point of view of fundamental heat engineering. But the difficulty of correctly assessing the temperature of the soil and its thermal conductivity in the absence of appropriate survey work somewhat shifts the methodology of A.G. Sotnikov into a theoretical plane, moving away from practical calculations. Although at the same time, continuing to rely on the zonal method of V.D. Machinsky, everyone just blindly believes the results and, understanding the general physical meaning of their occurrence, cannot definitely be sure of the obtained numerical values.

What is the meaning of the methodology of Professor A.G. Sotnikov? He proposes to assume that all heat losses through the floor of a buried building “go” into the depths of the planet, and all heat losses through walls in contact with the ground are eventually transferred to the surface and “dissolve” in the ambient air.

This seems to be partly true (without mathematical justification) if there is sufficient deepening of the floor of the lower floor, but with a deepening of less than 1.5 ... 2.0 meters, there are doubts about the correctness of the postulates ...

Despite all the criticisms made in the previous paragraphs, it is the development of the algorithm of Professor A.G. Sotnikova seems to be very promising.

Let's calculate in Excel the heat loss through the floor and walls into the ground for the same building as in the previous example.

We write down the dimensions of the basement of the building and the estimated air temperatures in the block of initial data.

Next, you need to fill in the characteristics of the soil. As an example, let's take sandy soil and enter its thermal conductivity coefficient and temperature at a depth of 2.5 meters in January into the initial data. The temperature and thermal conductivity of the soil for your area can be found on the Internet.

The walls and floor will be made of reinforced concrete ( λ=1.7 W/(m °C)) 300mm thick ( δ =0,3 m) with thermal resistance R = δ / λ=0.176 m 2 ° C / W.

And, finally, we add to the initial data the values ​​of the heat transfer coefficients on the inner surfaces of the floor and walls and on the outer surface of the soil in contact with the outside air.

The program performs the calculation in Excel using the formulas below.

Floor area:

F pl \u003dB*A

Wall area:

F st \u003d 2 *h *(B + A )

Conditional thickness of the soil layer behind the walls:

δ conv. = f(h / H )

Thermal resistance of the soil under the floor:

R 17 =(1/(4*λ gr )*(π / Fpl ) 0,5

Heat loss through the floor:

Qpl = Fpl *(tin tgr )/(R 17 + Rpl +1/α in )

Thermal resistance of the soil behind the walls:

R 27 = δ conv. /λ gr

Heat loss through walls:

Qst = Fst *(tin tn )/(1/α n +R 27 + Rst +1/α in )

General heat loss to the ground:

Q Σ = Qpl + Qst

Remarks and conclusions.

The heat loss of the building through the floor and walls into the ground, obtained by two different methods, differ significantly. According to the algorithm of A.G. Sotnikov value Q Σ =16,146 kW, which is almost 5 times more than the value according to the generally accepted "zonal" algorithm - Q Σ =3,353 kW!

The fact is that the reduced thermal resistance of the soil between the buried walls and the outside air R 27 =0,122 m 2 °C / W is clearly small and hardly true. And this means that the conditional thickness of the soil δ conv. not defined correctly!

In addition, the “bare” reinforced concrete of the walls, which I chose in the example, is also a completely unrealistic option for our time.

An attentive reader of the article by A.G. Sotnikova will find a number of errors, rather than those of the author, but those that arose when typing. Then in formula (3) a factor 2 appears in λ , then disappears later. In the example, when calculating R 17 no division sign after unit. In the same example, when calculating heat loss through the walls of the underground part of the building, for some reason the area is divided by 2 in the formula, but then it is not divided when recording the values ​​... What kind of non-insulated walls and floor are these in the example with Rst = Rpl =2 m 2 ° C / W? In this case, their thickness must be at least 2.4 m! And if the walls and floor are insulated, then, it seems, it is incorrect to compare these heat losses with the calculation option for zones for an uninsulated floor.

R 27 = δ conv. /(2*λ gr)=K(cos((h / H )*(π/2)))/К(sin((h / H )*(π/2)))

As for the question, regarding the presence of a factor of 2 in λ gr has already been said above.

I divided the complete elliptic integrals by each other. As a result, it turned out that the graph in the article shows a function for λ gr =1:

δ conv. = (½) *TO(cos((h / H )*(π/2)))/К(sin((h / H )*(π/2)))

But mathematically it should be:

δ conv. = 2 *TO(cos((h / H )*(π/2)))/К(sin((h / H )*(π/2)))

or, if the factor is 2 λ gr not needed:

δ conv. = 1 *TO(cos((h / H )*(π/2)))/К(sin((h / H )*(π/2)))

This means that the schedule for determining δ conv. gives erroneous underestimated values ​​by 2 or 4 times ...

It turns out that until everyone has nothing else to do, how to continue to either “count”, or “determine” heat losses through the floor and walls into the ground by zones? No other worthy method has been invented in 80 years. Or invented, but not finalized?!

I invite blog readers to test both calculation options in real projects and present the results in the comments for comparison and analysis.

Everything that is said in the last part of this article is solely the opinion of the author and does not claim to be the ultimate truth. I would be glad to hear the opinion of experts on this topic in the comments. I would like to understand to the end with the algorithm of A.G. Sotnikov, because it really has a more rigorous thermophysical justification than the generally accepted method.

ask respecting the work of the author to download a file with calculation programs after subscribing to article announcements!

P.S. (02/25/2016)

Almost a year after writing the article, we managed to deal with the questions raised a little higher.

Firstly, the program for calculating heat losses in Excel according to the method of A.G. Sotnikova thinks everything is correct - exactly according to the formulas of A.I. Pehovich!

Secondly, the formula (3) from the article by A.G. Sotnikova should not look like this:

R 27 = δ conv. /(2*λ gr)=K(cos((h / H )*(π/2)))/К(sin((h / H )*(π/2)))

In the article by A.G. Sotnikova is not a correct entry! But then the graph is built, and the example is calculated according to the correct formulas!!!

So it should be according to A.I. Pekhovich (p. 110, additional task to item 27):

R 27 = δ conv. /λ gr\u003d 1 / (2 * λ gr ) * K (cos((h / H )*(π/2)))/К(sin((h / H )*(π/2)))

δ conv. =R27 *λ gr =(½)*K(cos((h / H )*(π/2)))/К(sin((h / H )*(π/2)))

The methodology for calculating the heat loss of premises and the procedure for its implementation (see SP 50.13330.2012 Thermal protection of buildings, paragraph 5).

The house loses heat through the building envelope (walls, ceilings, windows, roof, foundation), ventilation and sewerage. The main heat losses go through the building envelope - 60–90% of all heat losses.

In any case, heat loss must be taken into account for all enclosing structures that are present in a heated room.

At the same time, it is not necessary to take into account heat losses that occur through internal structures if the difference between their temperature and the temperature in neighboring rooms does not exceed 3 degrees Celsius.

Heat loss through building envelopes

Heat losses of premises mainly depend on:
1 Temperature differences in the house and on the street (the greater the difference, the higher the losses),
2 Heat-shielding properties of walls, windows, doors, coatings, floors (the so-called enclosing structures of the room).

Enclosing structures are generally not homogeneous in structure. And usually consist of several layers. Example: shell wall = plaster + shell + exterior finish. This design may also include closed air gaps (example: cavities inside bricks or blocks). The above materials have different thermal characteristics from each other. The main such characteristic for a structural layer is its heat transfer resistance R.

Where q is the amount of heat lost per square meter of enclosing surface (usually measured in W/m2)

ΔT is the difference between the temperature inside the calculated room and the outside air temperature (the temperature of the coldest five-day period °C for the climatic region in which the calculated building is located).

Basically, the internal temperature in the rooms is taken. Living quarters 22 oC. Non-residential 18 oC. Zones of water procedures 33 °C.

When it comes to a multilayer structure, the resistances of the layers of the structure add up.

δ - layer thickness, m;

λ is the design coefficient of thermal conductivity of the material of the structure layer, taking into account the operating conditions of the enclosing structures, W / (m2 °C).

Well, now we figured out the basic data required for the calculation.

So, to calculate heat losses through building envelopes, we need:

1. Heat transfer resistance of structures (if the structure is multilayer, then Σ R layers)

2. The difference between the temperature in the calculated room and on the street (the temperature of the coldest five-day period is °C.). ∆T

3. Square fences F (Separate walls, windows, doors, ceiling, floor)

4. Another useful orientation of the building in relation to the cardinal points.

The formula for calculating the heat loss of a fence looks like this:

Qlimit=(ΔT / Rlimit)* Flimit * n *(1+∑b)

Qlimit - heat loss through the building envelope, W

Rogr - resistance to heat transfer, m.sq. ° C / W; (If there are several layers, then ∑ Rlimit of layers)

Fogr – area of ​​the enclosing structure, m;

n is the coefficient of contact of the building envelope with the outside air.

Walling Coefficient n
1. External walls and coverings (including those ventilated with outside air), attic floors (with a roof made of piece materials) and over driveways; ceilings over cold (without enclosing walls) undergrounds in the Northern building-climatic zone
2. Ceilings over cold cellars communicating with outside air; attic floors (with a roof made of rolled materials); ceilings over cold (with enclosing walls) undergrounds and cold floors in the Northern building-climatic zone 0,9
3. Ceilings over unheated basements with skylights in the walls 0,75
4. Ceilings above unheated basements without light openings in the walls, located above ground level 0,6
5. Ceilings over unheated technical undergrounds located below ground level 0,4

The heat loss of each enclosing structure is considered separately. The amount of heat loss through the enclosing structures of the entire room will be the sum of heat losses through each enclosing structure of the room


Calculation of heat loss through floors

Uninsulated floor on the ground

Usually, floor heat losses in comparison with similar indicators of other building envelopes (external walls, window and door openings) are a priori assumed to be insignificant and are taken into account in the calculations of heating systems in a simplified form. Such calculations are based on a simplified system of accounting and correction coefficients for the resistance to heat transfer of various building materials.

Considering that the theoretical justification and methodology for calculating the heat loss of the ground floor was developed quite a long time ago (i.e. with a large design margin), we can safely say that these empirical approaches are practically applicable in modern conditions. The coefficients of thermal conductivity and heat transfer of various building materials, insulation and floor coverings are well known, and other physical characteristics are not required to calculate heat loss through the floor. According to their thermal characteristics, floors are usually divided into insulated and non-insulated, structurally - floors on the ground and logs.



The calculation of heat loss through an uninsulated floor on the ground is based on the general formula for estimating heat loss through the building envelope:

where Q are the main and additional heat losses, W;

BUT is the total area of ​​the enclosing structure, m2;

tv , tn- temperature inside the room and outside air, °C;

β - share of additional heat losses in total;

n- correction factor, the value of which is determined by the location of the building envelope;

Ro– resistance to heat transfer, m2 °С/W.

Note that in the case of a homogeneous single-layer floor slab, the heat transfer resistance Ro is inversely proportional to the heat transfer coefficient of the uninsulated floor material on the ground.

When calculating heat loss through an uninsulated floor, a simplified approach is used, in which the value (1+ β) n = 1. Heat loss through the floor is usually carried out by zoning the heat transfer area. This is due to the natural heterogeneity of the temperature fields of the soil under the floor.

The heat loss of an uninsulated floor is determined separately for each two-meter zone, the numbering of which starts from the outer wall of the building. In total, four such strips 2 m wide are taken into account, considering the soil temperature in each zone to be constant. The fourth zone includes the entire surface of the uninsulated floor within the boundaries of the first three strips. Heat transfer resistance is accepted: for the 1st zone R1=2.1; for the 2nd R2=4.3; respectively for the third and fourth R3=8.6, R4=14.2 m2*оС/W.

Fig.1. Zoning of the floor surface on the ground and adjacent recessed walls when calculating heat losses

In the case of recessed rooms with a soil base of the floor: the area of ​​the first zone adjacent to the wall surface is taken into account twice in the calculations. This is quite understandable, since the heat loss of the floor is added to the heat loss in the vertical enclosing structures of the building adjacent to it.

Calculation of heat loss through the floor is made for each zone separately, and the results obtained are summed up and used for the thermal engineering justification of the building project. The calculation for the temperature zones of the outer walls of recessed rooms is carried out according to formulas similar to those given above.

In calculations of heat loss through an insulated floor (and it is considered as such if its structure contains layers of material with a thermal conductivity of less than 1.2 W / (m ° C)) the value of the heat transfer resistance of an uninsulated floor on the ground increases in each case by the heat transfer resistance of the insulating layer:

Ru.s = δy.s / λy.s,

where δy.s– thickness of the insulating layer, m; λu.s- thermal conductivity of the material of the insulating layer, W / (m ° C).